107
Solutions for centralized heating systems installations
MASTER (main) boiler parameter configuration
Parameter configuration on non-MASTER boiler
Using the control panel, access menu 3 and carry out the following settings.
Menù
Programme
line
Value
Description
Configuration
5977
None
Disabling of thermostat on terminal board M1 (1-2)
Configuration
6020
Multifunctional
Enabling unit AVS75
Configuration
6030
Heat circ. pump. 1Q2
Control of circuit 1 pump
Configuration
6040
Common delivery probe
B10
Control of cascade delivery temperature
Configuration
6041
Cascade return probe B70 Control of cascade return temperature
Configuration
6046
Ambiance thermostat CR1
Enabling of thermostat in inlet H2 of the AVS75
Configuration
6200
Si (*)
Memorisation of modifications carried out
LPB
6630
Always
Identification of master boiler
LPB
6640
Autonomous
Setting of master cascade clock
*The value returns automatically to “No” immediately after setting.
Having configured he master boiler parameters as described in the previous paragraph, proceed to configuration of the other
boilers.
The operations listed below are repeated for each boiler in the cascade, excluding the MASTER boiler.
For correct system functioning an address must be assigned to each boiler so that it can be recognised by the master boiler (the
master boiler has default =1). Moreover it is also necessary to synchronise the boiler clocks with that of the master boiler. Using
the control panel, access menu 3 and carry out the following settings.
Menù
Programme
line
Value
Description
Configuration
5710
OFF
Enabling of thermostat for circuit 2(terminal board M1 (1-2) in boiler)
LPB
6600
2..3..4..
Enabling unit AVS75
LPB
6640
Slave with imp. Remote
Setting cascade boiler clocks with master boiler
Menù
Programme
line
Value
Description
Cascade
3540
N° of hours
Period of functioning before automatic change of sequence of main boiler.
Cascade
3541
First – Last – First and
Last.
Exclusion of the boiler(s) from periodic rotation of sequence
After connecting the pump to the relay, set outlet QX22 as shown in the following table.
Menù
Programme
line
Value
Description
Cascade
6031
actuator HSW Q3
Control load pump of HSW storage on relay QX22