111
Solutions for centralized heating systems installations
RVS46
Note: keep attention to set correctly the address of the device on the LPB bus. The boilers in cascade and the RVS46 must have a
different address between each other (n°6600 parameter of each boiler or device as RVS46 present on LPB bus)
Menù
Programme line
Description
Configuration
6021
Enabling heating circuit 2
Menù
Programme line
Parameter
Value
Description
RVS46
Heating circuit 1
741
< 45 °C
Set point of the maxinum temperature for the mixed zone
N
L
EX21
FX23
L
C
S
T
Q
X23
Q
X22
L
N
Q
X21
N
L
N
L
X50
H2
M
BX22
M
BX21
X30
n
n
n
A
D
C
B
M
ON
1 2
1 2
1
2
3
230V
A Flow sensor QAD36
B Mixing valve
C Mixed zone pump
D Safety thermostat
A Flow sensor QAD36
D
OCI 345
B Outdoor sensor
E
Mixing valve
C Remote control
F
Mixed zone pump
In the case of a mixed zone, hook up the safety thermostat between the “FX23-L” terminals and jump the terminals “EX21-FX23”. In this
way the circuit pump connected to relay “QX23” is internally connected in series with the safety thermostat.
Should it be necessary to use relay outlet “QX23” for functions other than those envisaged for the mixed zone, jump terminals “FX23-L”.