110

MASTER (main) boiler parameter configuration

Parameter configuration on non-MASTERS boiler

Using the control panel, access menu 3, and carry out the following settings.

Menù

Programme 

line

Value

Description

Configuration

5977

None

Disabling of thermostat on terminal board M1 (1-2)

Configuration

6020

Multifunctional

Enabling unit AVS75

Configuration

6030

Heat circ. pump. 1Q2

Control of circuit 1 pump

Configuration

6040

Common delivery probe 

B10

Control of cascade delivery temperature

Configuration

6041

Cascade return probe B70 Control of cascade return temperature

Configuration

6046

Ambiance thermostat CR1

Enabling of thermostat in inlet H2 of the AVS75 

Configuration

6200

Yes (*)

Memorisation of modifications carried out

LPB

6630

Always

Identification of master boiler

LPB

6640

Autonomous

Setting of master cascade clock

*The value returns automatically to “No” immediately after setting.

Having configured he master boiler parameters as described in the previous paragraph, proceed to configuration of the other 
boilers. To this purpose, connect the Remote Control (if not already present) to the boiler to be configured and proceed as 
follows.

The operations listed below are repeated for each boiler in the cascade, excluding the MASTER boiler.

For correct system functioning an address must be assigned to each boiler so that it can be recognised by the master boiler (the 
master boiler has default =1). Moreover it is also necessary to synchronise the boiler clocks with that of the master boiler. Using 
the control panel, access menu 3 and carry out the following settings.

Menù

Programme 

line

Value

Description

Configuration

5710

OFF

Enabling of thermostat for circuit 2(terminal board M1 (1-2) in boiler)

LPB

6600

2..3..4..

Enabling unit AVS75

LPB

6640

Slave with imp. Remote

Setting cascade boiler clocks with master boiler

Menù

Programme 

line

Value

Description

Cascade

3540

N° of hours

Period of functioning before automatic change of sequence of main boiler.

Cascade

3541

First – Last – First and 

Last. 

Exclusion of the boiler(s) from periodic rotation of sequence

After connecting the pump to the relay, set outlet QX22 as shown in the following table.

Menù

Programme 

line

Value

Description

Cascade

6031

actuator HSW Q3

Control load pump of DHW storage on relay QX22

The pumps of the high temperature zone have to be connected one to each other, and through a relè, linked to the terminal of 
module AVS75 identified with QX21-N.

Содержание Luna Platinum 1.12

Страница 1: ...m installation Coaxial flue system accessories Dual flue system installation Dual flue system accessories Flexible ducting system accessories Electronics Programming setting and digital control Cascade installation Schemes for cascade installation Hydraulic separators and condensate neutralizer kit Other accessories Luna Platinum P 82 83 84 85 86 87 88 89 90 92 93 94 96 102 115 116 ...

Страница 2: ...0 80 Maximum flue mass flow rate kg s 0 006 0 008 0 012 0 016 Minimum flue mass flow rate kg s 0 001 0 001 0 002 0 003 Maximum flue temperature C 75 75 80 80 Residual flue prevalence m h 16 8 23 5 33 4 44 6 Comburent air flow at Qn Pa 100 100 100 100 Dimensions h x w x d mm 760x450x345 Net weight kg 34 5 34 5 34 5 37 5 Gas type Natural Gas LPG Natural Gas LPG Natural Gas LPG Natural Gas LPG Power ...

Страница 3: ...trolled by a latest generation electronics circuit board which makes for simple reliable boiler management using the extractable control panel with wide LCD display Daily and weekly programming of heating and DHW functions is possible as is climatic setting according to the comfort criteria chosen by the user and the visualisation of error messages relating to any faults In addition such boiler el...

Страница 4: ... below shows the variations in efficiency as the ratio of the flow rate to the heat output of the condensing generator specified depending on the return temperature of the boiler The last figure shows the trend of the flue temperature of the generator depending on the return temperature 30 35 40 Efficiency of the boiler Return temperature of the system C EFFICIENCY OF THE BOILER ACCORDING TO THE R...

Страница 5: ... N C C R R M N C M V N C M V N N V M C C C C C V N M C M C M C G V G V G V G V G V G V G V G V G V G V G V 1 15 G V G V G V Y P M M P Y FUSIBILI L N 1 2 FUSIBILI M C G V G V G V M N N M M C M C M C M C M V N N V M2 V V 22 V V B R N 13 b a 10 9 8 7 6 5 4 3 2 1 7 6 5 4 3 2 1 M3 1 Pump with air separator 9 Hydraulic pressure sensor 17 Coaxial connector 2 Boiler drain tap 10 3 way valve with motor 18 ...

Страница 6: ...oard M2 The sensitive element of the NTC sensor should be inserted in the dedicated well provided on the boiler itself The temperature of the domestic hot water and choice of DHW timer can be made directly from the boiler control panel KEY A HEATINGUNIT B THREE WAYVALVE C HEATINGFLOW D BOILERFLOW E HEATING BOILERRETURN G NTCSENSORDHWBOILER F BOILERUNIT M2 CONNECTIONTERMINALBOARD BOILERUNITCONNECTI...

Страница 7: ... Max duct length m Length reduction with a 90 bend insertion Length reduction with a 45 bend insertion Ø60 100 Ø80 125 10 25 1 0 5 Examples of installation with horizontal flue system Ø 60 100 Installation examples with LAS chimney ø60 100 Installation example with vertical flue ducts ø60 100 ...

Страница 8: ...e extension 60 100 L 500 mm KHG 714119810 PP coaxial flue tube extension 80 125 L 500 mm KHG 714088610 PP coaxial 90 bend Ø 60 100 KHG 714059716 PP coaxial 87 bend Ø 80 125 KHG 714088711 PP coaxial 45 bend Ø 60 100 KHG 714059816 PP coaxial 45 bend Ø 80 125 KHG 714088811 Internal sealing collar Ø 100 KHG 714017710 PP vertical chimney terminal 80 125 KHG 714093510 PP reduction from 80 125 to 60 100 ...

Страница 9: ...lues and intake pipes in any direction thanks to the fact that they can rotate by 360 It can also be used as an additional bend in combination with the pipe or 45 bend A B For special installations of the flues inlet outlet ducts B the orienting dual flue system supplied as an accessory can be used This accessory in fact can be used to move the inlet and out let in any direction thanks to the poss...

Страница 10: ...pe installation KHG 714111011 PP reduction from Ø 80 to Ø 60 KHG 714075610 PP tube extension Ø 80 L 1000 mm KHG 714059411 PP tube extension Ø 80 L 500 mm KHG 714059910 PP tube extension Ø 60 L 1000 mm KHG 714075310 PP tube extension Ø 60 L 500 mm KHG 714075210 PP 90 bend Ø80 KHG 714059211 PP 90 bend Ø60 KHG 714075410 PP 45 bend Ø80 KHG 714059311 PP 45 bend Ø60 KHG 714075510 Luna Platinum 1 12 1 18...

Страница 11: ...HG 714037310 Internal sealing collar Ø 80 KHG 714018510 External sealing collar Ø 80 KHG 714018411 Coaxial vertical chimney terminal 80 125 KHG 714093510 Dual flue tubes adapter for coaxial chimney Ø80 125 KHG 714093810 Flat roof tile Ø 125 to be used with a vertical chimney terminal KHG 714093610 Pitched roof tile Ø 125 to be used with a vertical chimney terminal it is adjustable from 15 to 45 KH...

Страница 12: ... KHG 714105710 PP flexible tube Ø 80 L 20 m KHG 714105810 PP 90 bend Ø 80 with supporting bracket and condensate drainings KHG 714105910 PP 90 bend Ø 80 with supporting bracket KHG 714106010 Flexible centring kit Ø 80 pack of 3 KHG 714106210 Triple lips gaskets kit Ø 80 pack of 5 KHG 714111210 ...

Страница 13: ... 1 holidays 9 Heating circuit 10 DHW circuit 11 Instantaneous heater ACS 12 Error 13 Diagnostic parameters Set heating timer Heating zones DHW mode enabled Heating mode on Automatic Data transmission with WIRELESS device only 2 levels of heating temperature comfort reduced Baxi has developed an innovative extractable control panel for the new Platinum series of boilers with a large easy to read di...

Страница 14: ...allation of the control panel on the wall in a representative room of the home The control panel can be used to control the temperature of the room to be heated and to programme and control a heating system comprising boilers in cascade and various low temperature zones 710244101 Wireless aerial This accessory permits installation of the WIRELESS outdoor sensor If the 5 LED interface circuit with ...

Страница 15: ...mostat limit and 1 control input such as TA 710503701 Bus interface kit OCI345 The OCI345 interface is an electronic device enabling the communication via bus two cables between boilers connected in cascade or between one boiler or the boilers in cascade and a mixed zone controller RVS46 710025602 Climate regulator for mixed zones RVS46 Heat adjustment control unit permits piloting of a mixed zone...

Страница 16: ... boilers ø 125 ø 160 ø 200 Vertical flue system B23 type of installation Shutter kit 110 80 with condensing trap Manifold pipes third Platinum boiler in cascade Manifold pipes 2 Platinum boilers in cascade See complete list of accessories codes on page 116 for Luna Platinum 1 12 1 18 1 24 1 32 ...

Страница 17: ...8 Manifold pipe Ø mm A 125 125 125 125 Chimney flue Ø mm B H 5 10 m 125 125 125 125 Chimney flue Ø mm B H 10 15 m 125 125 160 160 Chimney flue Ø mm B H 15 20 m 160 160 160 160 2 m A B H Distance of the manifold from the first boiler to the vertical chimney 2 meters Shutter kit installed in each boiler in cascade The pipes of the chimney and the connections between the manifold pipes of the cascade...

Страница 18: ...0 has not already been installed in the boiler then remove the protective cover on the back of the command panel on the boiler place the OCI345 interface in the relative slot and once the boiler s electronic circuit has been turned on connect the interface using the cable provided to the connector of the electronic circuit X30 2 If the extension module AGU2 550 has already been installed in the bo...

Страница 19: ...e probes on the manifold heater and solar pump This accessory is installed in the boiler dashboard You must remove cover A from dashboard B Raise dashboard B and hook up the flat cable between connector X50 of accessory AGU2 550 and connector X41 of the boiler board passing through the hole in dashboard B Close dashboard B and insert the AGU2 550 Carry out the electrical hook ups necessary for ins...

Страница 20: ...s The AVS75 may also be used to manage solar plant by means of the boiler In this case the connections supplied by the expansion module AVS75 are the two inlets related to the probe on the manifolds and to the probe on the heater whereas the outlet regards control of the solar pump see figure N L EX21 FX23 L C S T QX23 QX22 L N QX21 N L N L X50 H2 M BX22 M BX21 X30 n n n A D C B M ON 1 2 1 2 1 2 3...

Страница 21: ... boilers by means of a local bus through which the information regarding the devices connected is received and transmitted AVS 75 n n n X30 BX21 M BX22 M H2 M X50 L N L N QX21 N L QX22 QX23 T S C L FX23 EX21 2 1 1 2 3 1 2 ON 230V M2 2 1 3 10 M1 KEY FOR CONNECTOR HOOK UP AVS 75 n n n X30 BX21 M BX22 M H2 M X50 L N L N QX21 N L QX22 QX23 T S C L FX23 EX21 2 1 1 2 3 1 2 ON X50 Connector for hook up b...

Страница 22: ...iler LUNA PLATINUM 2 Manifold pipes two boilers in cascade 3 Flue tube kit for two boilers 4 Flow return sensor 5 Hydraulic separator 6 Outdoor sensor QAC34 7 Interface for cascade installation OCI 345 8 DHW sensor 9 Single coil tank SC 10 Safety device ISPESL available as optional SYSTEM WITH 2 CONDENSING BOILERS LUNA PLATINUM 1 HIGH TEMPERATURE DIRECT CIRCUIT 1 LOAD TANK CIRCUIT SINGLE COIL 2 3 ...

Страница 23: ...ctions of Expansion Module AVS75 are highlighted in the figure KEY FOR CONNECTOR HOOK UP AVS 75 n n n X30 BX21 M BX22 M H2 M X50 L N L N QX21 N L QX22 QX23 T S C L FX23 EX21 2 1 1 2 3 1 2 ON X50 Connector for hook up between SIEMENS electronic board and accessory AVS 75 C EX21 FX23 Not used for cascades S QX23 L Relay outlet 230V programmable T QX21 N Relay outlet 230V supply CASCADE PUMP T QX22 N...

Страница 24: ... 6040 Common delivery probe B10 Control of cascade delivery temperature Configuration 6041 Cascade return probe B70 Control of cascade return temperature Configuration 6046 Ambiance thermostat CR1 Enabling of thermostat in inlet H2 of the AVS75 Configuration 6200 Si Memorisation of modifications carried out LPB 6630 Always Identification of master boiler LPB 6640 Autonomous Setting of master casca...

Страница 25: ...EMPERATURE DIRECT CIRCUIT 1 LOAD TANK CIRCUIT WITH INTEGRATION WITH SOLAR SYSTEM OPTION BUILT IN HEAT BOXES LUNA SAT RH 2C 6 4 8 9 QAD 2 3 5 10 4 OCI 345 OCI 345 1 1 7 1 Condensing boiler LUNA PLATINUM 2 Manifold pipes two boilers in cascade 3 Flue tube kit for two boilers 4 Flow return sensor 5 Hydraulic separator 6 Outdoor sensor QAC34 7 Interface for cascade installation OCI 345 8 DHW sensor 9 ...

Страница 26: ... N L N QX21 N L QX22 QX23 T S C L FX23 EX21 2 1 1 2 3 1 2 ON X50 Connector for hook up between SIEMENS electronic board and accessory AVS 75 C EX21 FX23 Not used for cascades C FX23 L Safety thermostat 230V not used for cascades S QX23 L Relay outlet 230V programmable T QX21 N Relay outlet 230V supply CASCADE PUMP T QX22 N Relay outlet 230V supply any loading PUMP for sanitary water STORAGE NOL L ...

Страница 27: ... described in the previous paragraph proceed to configuration of the other boilers The operations listed below are repeated for each boiler in the cascade excluding the MASTER boiler For correct system functioning an address must be assigned to each boiler so that it can be recognised by the master boiler the master boiler has default 1 Moreover it is also necessary to synchronise the boiler clock...

Страница 28: ... LUNA PLATINUM 2 HIGH TEMPERATURE DIRECT CIRCUITS 2 MIXED LOW TEMPERATURE CIRCUITS 1 LOAD TANK FOR SOLAR INTEGRATION OPTION 1 Condensing boiler LUNA PLATINUM 2 Safety device ISPESL available as optional 3 Flue tube kit for two boilers 4 Flue tube for the third boiler 5 Flow return contact sensor 6 Hydraulic separator 7 Outdoor sensor QAC 34 8 Interface for cascade installation OCI 345 9 Module AVS...

Страница 29: ...S 75 n n n X30 BX21 M BX22 M H2 M X50 L N L N QX21 N L QX22 QX23 T S C L FX23 EX21 2 1 1 2 3 1 2 ON X50 Connector for hook up between SIEMENS electronic board and accessory AVS 75 C EX21 FX23 Not used for cascades C FX23 L Safety thermostat 230V not used for cascades S QX23 L Relay outlet 230V programmable T QX21 N Relay outlet 230V supplying CASCADE PUMP T QX22 N Relay outlet 230V supply any load...

Страница 30: ...be configured and proceed as follows The operations listed below are repeated for each boiler in the cascade excluding the MASTER boiler For correct system functioning an address must be assigned to each boiler so that it can be recognised by the master boiler the master boiler has default 1 Moreover it is also necessary to synchronise the boiler clocks with that of the master boiler Using the con...

Страница 31: ...inum temperature for the mixed zone N L EX21 FX23 L C S T QX23 QX22 L N QX21 N L N L X50 H2 M BX22 M BX21 X30 n n n A D C B M ON 1 2 1 2 1 2 3 230V A Flow sensor QAD36 B Mixing valve C Mixed zone pump D Safety thermostat A Flow sensor QAD36 D OCI 345 B Outdoor sensor E Mixing valve C Remote control F Mixed zone pump In the case of a mixed zone hook up the safety thermostat between the FX23 L termi...

Страница 32: ...ree boilers in cascade 3 Flue tube kit for two boilers 4 Flue tube for the third boiler 5 Flow return contact sensor 6 Hydraulic separator 7 Interface for cascade installation OCI 345 8 Built in heat boxes LUNA SAT RS2Z 9 Safety device ISPESL available as optional 6 10 5 SYSTEM WITH 3 CONDENSING BOILERS LUNA PLATINUM 1 HIGH TEMPERATURE DIRECT CIRCUIT BUILT IN HEAT BOXES LUNA SAT RS2Z 10 10 10 10 1...

Страница 33: ... X30 BX21 M BX22 M H2 M X50 L N L N QX21 N L QX22 QX23 T S C L FX23 EX21 2 1 1 2 3 1 2 ON X50 Connector for hook up between SIEMENS electronic board and accessory AVS 75 C EX21 FX23 Not used for cascades C FX23 L Safety thermostat 230V not used for cascades S QX23 L Relay outlet 230V programmable T QX21 N Relay outlet 230V supply CASCADE PUMP T QX22 N Relay outlet 230V supply any loading PUMP for ...

Страница 34: ...aragraph proceed to configuration of the other boilers The operations listed below are repeated for each boiler in the cascade excluding the MASTER boiler For correct system functioning an address must be assigned to each boiler so that it can be recognised by the master boiler the master boiler has default 1 Moreover it is also necessary to synchronise the boiler clocks with that of the master bo...

Страница 35: ...room temperature C 5 40 Diameter mm 87 5 Height mm 365 Maximum condensate water flow l h 56 Max potentiality of the boiler kcal h from 201 000 to 300 000 Max potentiality of the boiler kW 234 349 Maximum working pressure bar 2 Maximum temperature of the water content C Corresponding to the max tempe ratures of the condensing waters Min Max room temperature C 5 40 Quantity of the first charge of pr...

Страница 36: ...ube kit Ø 160 for the third boiler KHW 714097610 PP flue tube kit ø200 for the third boiler KHW 714098010 PP shutter kit 110 80 with condensing trap KHG 714093411 PP 90 bend Ø 125 KHG 714094410 PP 90 bend Ø 160 KHW 714097810 PP 90 bend Ø 200 KHW 714098210 PP 45 bend Ø 125 pack of 2 KHG 714094510 PP tube extension Ø 125 L 1000 KHG 714094610 PP tube extension Ø 160 L 1000 KHW 714097710 PP tube exten...

Страница 37: ...tems taps and connection pipes 710351201 Connection pipes for combi boilers 710351102 Connection pipes for heating only boilers 710351001 Picture Description Code Manifold pipes for 2 Platinum boilers in cascade KHG 714117110 Manifold pipes for the 3rd Platinum boiler in cascade KHG 714117210 Hydraulic accessories for single installation Hydraulic accessories for cascade installation ...

Отзывы: