94
instructions pertaining to the instaLLer
924.493.3
it
at
gB
Carry out the following operations in the given sequence:
1)
Calibration of the maximum heat output. Check that the CO
2
measured on the flue, with the boiler operating at the
maximum heat output, is the same as that shown in table 1. Otherwise, turn the regulation screw (V) on the gas valve.
Turn the screw clockwise to reduce the concentration of CO
2
and anticlockwise to increase it.
2)
Calibration of reduced heat output. Check that the CO
2
measured on the flue, with the boiler operating at the minimum
heat output, is the same as that shown in table 1. Otherwise, turn the offset regulation screw (K) on the gas valve. Turn
the screw clockwise to increase the concentration of CO
2
and anticlockwise to reduce it.
0310_0114
Figure 13
pi:
Gas supply pressure connection point
p out:
Gas pressure to burner connection point
p:
Pressure connection point
for measurement of the OFFSET
pl:
Air signal input from fan
V:
Gas flow adjuster screw
K:
OFFSET adjuster screw
iMportant:
If the appliance is being converted from natural gas to propane (LPG), the following operations must be
performed before calibrating the gas valve as instructed above.
• Turn adjuster screw (V) on the gas valve clockwise through the number of complete revolutions specified in table 3.
To simplify calibration of the gas valve, the “calibration function” can be set directly on the boiler control panel by pro-
ceeding as follows:
1) Press the
keys (2-3) together until the display shows the pointer “ ” alongside the symbol (about 6 secon-
ds).
2) Press the
keys to set the fan speed at the minimum and maximum heat output (%PWM);
N.b - to set the
minimum
and
maximum
heat output quickly, press the
keys respectively;
3) press either of the two
keys to exit the function.
14. gas valve adjustment