Baxi Bermuda PW5 C5 Скачать руководство пользователя страница 4

page 4

Ventilation

Ventilation air supply should be in accordance with the
relevant standards. In GB this is BS 5440 Pt. 2. In IE this
is I.S. 813 “Domestic Gas Installations”. The permanent
ventilation area size requirements are
C5/C5W/PW5 Deluxe and 45/4  62.51cm

2

(9.7in

2

)

C5/C5W/PW5 Deluxe and 57/4  83.12cm

2

(12.88in

2

)

C5/C5W/PW5 Deluxe and 51/5  70.77cm

2

(11in

2

)

The permanent vent may be directly into the room
containing the appliance. The vent may also be sited in
another room provided an interconnecting vent is used.

The vent must not be installed inside the builders
opening. The vent should be sited following good practice
for a habitable room. We recommend the use of the
Stadium BM700 or BM701 ventilator which is available
from your local merchant.

Wall Fixing:

(Fig.2) The bottom of the fire (i.e. the hearth

on which the boiler rests) must be 100mm (4in) to 
125mm (5in) above the floor level.

It is strongly recommended that the fireplace opening is
made to the maximum dimensions.

GAS SUPPLY 

1. The gas installation should be in accordance with 
relevant standards. In GB this is BS 6891. In IE this is 
I.S. 813 “ Domestic Gas Installations”. The gas supply is
provided from the service tap on the boiler unit. A supply
pipe is provided with the fire. This pipe has one flared end
for connection to the fire and a plain end which is
connected to the service tap by a nut and olive.
2. Dependent upon the position of the boiler relevant to
the surround or wall finished face, it may be necessary to
shorten the supply pipe. IF THE PIPE HAS TO BE
SHORTENED CARE MUST BE TAKEN. The length of the
supply pipe is determined as follows:

(a) Measure the distance 'D' from the centre of the 

front positioning 'V' mark on the boiler tray, back 
to the surround face or finished wall face (Fig.3).

(b) FROM THE PLAIN END of the supply pipe cut off 

a length of pipe equal to the distance 'D' 
measured above. Take care to ensure that the cut
is square and the pipe is free from burrs and swarf.

ALTERNATIVELY

(c) The amount of pipe required to be cut off can be 

determined by holding the PLAIN END of the pipe 
against the surround or finished wall face, marking
the pipe at the position of the centre of the front 
positioning 'V' mark on the boiler tray.

3. After threading the steel flare nut on the above pipe,
connect the plain end to the service tap with the
remaining nut and olive. It is important to ensure that the
flared end of the pipe:

(a) Faces to the right.
(b) Is parallel with the hearth or floor.

Installation Instructions

These instructions must be read in conjunction with the
separate instructions for the boiler section

INTRODUCTION

This unit is the gas fire section of the Bermuda PW5
Deluxe, C5, C5W central heating boiler and gas fire. The
heat input is 4.67kW (15,900 Btu/h) and the fire is
available for use with Gas Type G20 (Natural Gas) at
20mbar or Gas Type G31 (Propane) (C5 & C5W
Mahogany only). The fire is controlled by a knob
positioned on the right hand side of the case (PW5 Deluxe
models) or on the top right hand side (C5 & C5W models).
Ignition is by piezo spark to the pilot. For details of
Propane appliances see page 15. The control knob has
five positions giving a choice of four output rates. 

Position

-

OFF

Position      1 -

IGNITION/LOW/PILOT 

Position

2 -

MEDIUM

Position

3 -

MED/HIGH 

Position

4 -

HIGH

There is no ‘Pilot Only’ position-the pilot and burner low
rate light simultaneously at position    1.

When the control knob is turned from    1 to    the pilot and
burner are extinguished.

SITE REQUIREMENTS

The principal site requirements are determined by the
boiler but the following details are essential for the correct
installation of the fire:

Fireplace opening:

(Figs. 1 & 2) 

Width

406mm (16in) MIN

584mm (23in) MAX 

Height

560mm (22in) 

Wherever possible always make the fireplace opening to
the maximum dimensions.

Hearth:

If the fire is to be hearth mounted, then the

hearth must be of a non-combustible material at least
13mm (

1

/

2

in) thick and measuring at least 340mm (13

3

/

8

in)

deep by 830mm (32

3

/

4

in) wide and fitted centrally about

the fireplace opening. The top surface of the hearth
should be a minimum of 50mm (2in) above floor level and
must be level with the base of the builders opening. On no
account should the fire unit be fitted directly onto a
combustible floor or carpet.

Surround or Wall Finish:

(Figs.1, 2 & 3) The

surround or wall finish must have a flat vertical area
central about the fireplace opening. This must be a
minimum of 860mm (33

7

/8in) wide (C5/C5W) or 991mm

(39in) wide (PW5 Deluxe). These dimensions include side
clearances of 70mm (2

3

/4in) both sides (C5/C5W) and

70mm (2

3

/4in) to the left and 89mm (3

1

/2in) to the right

(PW5 Deluxe). The surface must be 660mm (26in) high
(C5/PW5 Deluxe) or 675mm (26

9

/16in) high (C5W). The

area behind the fire must be non-combustible.
A shelf may be fitted over the fire provided that it is not
less than 76mm (3in) on PW5 Deluxe and 100mm (4in) on
C5/C5W above the fire top panel and does not exceed
229mm (9in) in depth. The area between the shelf and the
top of the fire must be non-combustible. 
If a surround is fitted, any gaps between it and the wall
must be sealed and it must have a rating of 100°C or
higher.
NOTE:- If when installing a PW5 Deluxe the flat area of a
surround or between two projections is to the minimum
width i.e. 991mm (39in) the fire will be offset to the left
within this area to comply with minimum side clearances.
A minimum width of 1010mm (39

3

/

4

in) is required to allow

the fire to be central.

Содержание Bermuda PW5 C5

Страница 1: ... these Instructions safe Should you move house please hand them over to the next occupier Baxi Bermuda PW5 Deluxe C5 C5W Fireside Gas Central Heating Unit Installation and Servicing Instructions PW5 Deluxe C5W C5 ...

Страница 2: ...lowing boilers Baxi Bermuda 45 4 M G C No 44 077 71 Baxi Bermuda 45 4 E G C No 44 077 73 Baxi Bermuda 57 4 M G C No 44 077 72 Baxi Bermuda 57 4 E G C No 44 077 74 Baxi Bermuda 51 5 G C No 44 075 06 Baxi is a BS EN ISO 9001 Accredited Company Renewal Baxi Bermuda PW5 Deluxe Renewal G C No 37 075 10A Baxi Bermuda C5 Renewal G C No 37 075 07A Baxi Bermuda C5W Oak Renewal G C No 37 075 08A Baxi Bermud...

Страница 3: ...es for domestic purposes BS 5449 Part 1 Forced circulation hot water systems IMPORTANT The addition of anything that may interfere with the normal operation of the appliance without express written permission from the manufacturer or his agent could invalidate the appliance warranty In GB this could also infringe the GAS SAFETY Installation and Use REGULATIONS Safe Installation The appliance is su...

Страница 4: ...UCTION This unit is the gas fire section of the Bermuda PW5 Deluxe C5 C5W central heating boiler and gas fire The heat input is 4 67kW 15 900 Btu h and the fire is available for use with Gas Type G20 Natural Gas at 20mbar or Gas Type G31 Propane C5 C5W Mahogany only The fire is controlled by a knob positioned on the right hand side of the case PW5 Deluxe models or on the top right hand side C5 C5W...

Страница 5: ...ler Push the fire backwards until the backing plate touches the finished wall face Adjust the feet to level the fire Fig 5 3 Mark the position of the most suitable pair of securing holes in the fire backing plate Fig 5 and remove the fire Drill and plug the wall with suitable plugs Replace the fire and secure to the wall with suitable fixing screws 4 Connect the gas supply pipe to the fire inlet c...

Страница 6: ...ndows are closed IMPORTANT NOTE If there is a ceiling or extractor fan in the room or adjoining room then the spillage test must be performed with the fan turned on and any interconnecting doors between the fan and the appliance left open b Light the fire and turn to position 4 c After running for 5 minutes take a lighted smoke match and insert it into the smoke tube at the left hand side of the f...

Страница 7: ...ndow Grey Push Button Target Aeration Hole Spark Electrode Spark Gap 3 0mm 4 0mm Service Tap Electronic Controls Boiler 45 4E 57 4E Fig 8 Outer Case Clearances PW5 Deluxe Fig 8 Outer Case Clearances C5 C5W C5W Not Shown Manual Controls Boiler 45 4M 57 4M Thermostat Knob Service Tap Fig 9 The Controls PW5 DELUXE Fig 9 The Controls C5 C5W Fig 10 Spark Gap Pilot Indicator Light Boiler Lockout Light L...

Страница 8: ...e Undo the injectors from the burner and clean carefully Do NOT use a pin or wire Using a soft brush remove any dirt or deposits from the burner and ensure that the ports are free from obstruction Clean any debris from the A S D assembly Do NOT use a pin or wire 8 Check that the spark gap is as in Fig 10 9 Replace the parts in reverse order of dismantling Make sure that the glass fibre sleeve is c...

Страница 9: ...sembly must be replaced in the event of one or other component failure s Only use a Genuine Baxi Spare Part Release the thermocouple and pilot feed pipe from the gas tap connection points Undo the pilot feed pipe nuts at each end and remove the pipe Undo the thermocouple nut from the tap Pull the electrode lead off it s terminal on the igniter and withdraw the lead and sleeve through the grommets ...

Страница 10: ...ilter Rectify flue YES Replace piezo igniter Check electrode lead insulation Is there a strong spark at the electrode Consult Gas Supplier Turn on gas supply Is gas supply turned on Is supply pressure correct 20mb working NO YES NO YES YES NO Has new pilot filter been fitted YES NO Is spark gap 3 to 4mm Adjust spark gap NO YES Is pilot burner clean Is flue blocked causing A S D to operate Change p...

Страница 11: ...ple output within limits Is meter pressure correct YES NO NO YES YES NO Pipe restricted or undersized Is supply pressure correct NO YES NO YES NO YES YES NO YES Are gas cocks fully open Is thermocouple tip sound NO YES Is flue blocked causing A S D to operate YES NO Open gas cocks Clean thermocouple tip Change pilot assembly Make good the connection Rectify flue Is pilot flame stable and approx 40...

Страница 12: ...ectrode E00 110 237840 H Arrester Lint 156 375 042779 J Radiant E00 129 237851 K Pilot Filter 205 723 082412 Key No Description G C Manufact rs No Part No A Dressguard 155 693 043036 B Knob Gas Tap Control 156 317 232705 Ca Tap Fire Control Piezo Unit E00 115 249763 D Injector C06 E00 131 238270 E Burner E00 116 237854 F Pilot ASD Assembly E00 113 238037 G Lead Electrode 280mm E00 117 250022 H Arr...

Страница 13: ... boiler hood and lift away Remove and discard the fire supply pipe from the service gas tap Disconnect and discard any electrical wiring between the boiler input terminal and the fire If the fire is wall mounted remove and discard the existing support frame Bermuda 401 only retain the two support brackets These will be needed in wall mounting the renewal fire If the fire is hearth mounted ensure t...

Страница 14: ... brackets from the previous plate must be fitted before the fire support plate can be fixed in place Push the support plate backwards until it touches the surround or wall face and tighten the screws to lock it in position BERMUDA 45 3 57 3 45 4 57 4 51 5 Take the fire support plate from the fire unit packaging and loosely attach it above the boiler base protruding from the fireplace opening using...

Страница 15: ...e CO7 37 0mbar 14 8 in wg Heat Input Gross Gas Group Injector Marking Supply Pressure The following spare components differ from Natural Gas models Description G C No Manufact rs Part No Injector Fire CO7 E00 130 238274 Pilot ASD Assy E00 114 238038 Pilot Shield Bracket Outercase Bermuda C5 Propane G C No 37 077 74 Bermuda C5W Mahogany Propane G C No 37 075 17 Pilot Shield Brackets Before fitting ...

Страница 16: ...Comp No 237650 Iss 11 1 03 B A X I P O T T E R T O N Brownedge Road Bamber Bridge Preston Lancashire PR5 6SN After Sales Service 08706 096 096 Technical Enquiries 08706 049 049 www baxi co uk ...

Отзывы: