4.0 Site Requirements
10
1
4.5
Flue
1. The flue installation must conform to
BS 5440 Pt 1. The flue must have a minimum
vertical height of 3m (10ft) and have a minimum
internal cross section area of 12,700 mm
2
(20in
2
), this is satisfied by a flue of 125mm (5in)
internal diameter.
A suitable terminal is required for all
installations.
2. 9in X 9in Brick
Flues previously used for other fuels must be
thoroughly swept. The flue must be lined with a
125mm (5in) flexible liner. The bottom of the
liner should terminate 500mm (20in) above the
base of the builders opening. The flue must be
sealed between the liner and the brickwork at
both the top and bottom.
3. Acid Resistant Liner
A flue constructed of acid resistant liners is
satisfactory provided the size requirements are
met. The boiler flue outlet can be connected to
the flue by means of a short length of 125mm
(5in) of flue pipe. A seal must be made in the
annular space between the outer face of this
flue pipe and the acid resistant liner.
4. Precast Flues
These must conform to BS 5440 Pt 1 and be
correctly installed without intrusion of cement
into the flue passage.
5. Proprietary Flues
A flue of this type must meet the size
requirements specified and be installed in
accordance with the flue manufacturers
recommendation and relevant codes of practice.
An approved terminal must be installed.