11 Troubleshooting
76
Combi 2
Tab.34
List of warnings
DISPLAY
DESCRIPTION OF WARNINGS BEFORE A
FAULT IS DETECTED
CAUSE – Check/Solution
Group
code
Specific
code
A.00
.28
Solar temperature sensor is either removed or
measures
a
temperature below
range
Check the solar temperature sensor wiring. Re-
place
the
sensor
if
necessary.
In
case
of
removal
of the solar tank, set the parameter DP150=1.
A.00
.29
Solar temperature sensor is either shorted or
measures a temperature above range
Check the solar temperature sensor wiring. Re-
place the sensor if necessary.
A.00
.34
Outdoor temperature sensor expected but not detec-
ted
OUTDOOR SENSOR NOT DETECTED
Enter the correct value of the parameter AP091
Connect
the outdoor
sensor
Outdoor sensor is not connected correctly
A.02
.06
Low pressure in heating circuit
Check the installation pressure and restore
Check
the
expansion
vessel
pressure
Check for boiler/installation leaks
A.02
.36
Functional device disconnected
COMMUNICATION FAULT
Start the auto-detect function (parameter AD)
Check the devices connected to contact X9
A.02
.37
Passive functional device disconnected
COMMUNICATION FAULT
Start the auto-detect function (parameter AD)
Check the devices connected to contact X9
A.02
.45
Connection error
COMMUNICATION FAULT
Start the auto-detect function (parameter AD))
A.02
.46
Device priority error
COMMUNICATION FAULT
Start the auto-detect function (parameter AD))
A.02
.48
Unit function configuration error
ELECTRICAL CONNECTION ERROR
Start the auto-detect function (parameter AD))
Check electrical connections of external devices
A.02
.49
Failed node initialisation
ELECTRICAL CONNECTION ERROR
Start the auto-detect function (parameter AD))
Check electrical connections of external devices
A.02
.54
OpenTherm bus power supply error
Check the devices connected to contact X17 -
Terminal board M2 (7-8)
A.02
.55
Incorrect or missing serial number
Contact the Service Network
A.02
.76
Internal memory reserved for full customisation of set-
tings.
No further changes can be made
Contact the Service Network
Important
When connecting a Room Unit/Control Unit to the boiler, the code
“
254
” is always shown in the event of a fault. Read the fault code
shown on the boiler display.