11.0
Commissioning of solar controller
11.4
Menu “Programming”
1.All adjustable parameters can be checked in this menu and, if
necessary, changed. The default factory setting will usually give
efficient and problem free operation. However Baxi recommend
the following parameters marked * must be left at the default
settings. Any change to the Baxi recommended settings will
invalidate the warranty.
2. For more information or guidance please contact the Technical
Enquiries.
Press or to scroll
up or down to the required sub function.
The icon will flash, press to
select the function. Reset by pressing
or for
increase/decrease values. Press
and appears,
press to confirm and
disappears.
ok?
ok?
13:21
Time
0:00 - 23:59
12:00
dT max
7K
Min
100
Storage tank 1 or 2
Maximum permissible
temperature
40 °C
Meaning
dT
10 K
3 - 40K
Temperature difference
controller. Hysteresis dT max
Storage tank 1 or 2:
switch-off differential (dToff)
2 - 35K
Adjustment of pump rotational
speed.
100% = rotational speed
regulation set to 'off'
7K
1 - 30K
Switch-on temperature for
Heating/Cooling function
Hysteresis for Heating/Cooling
function
10K
30% - 100%
Value range
20 - 90°C
Typical
adjustment
3 - 40K
7K
3K
15 - 65°C
(15 - 95°C
Tank 2)
Indication
dT min
3 K
dT max
7 K
max
65 °C
65°C*
MAX
Storage tank 1 or 2:
switch-on differential (dTon)
100%
40°C
2
2 - 35K
3K
min
00:00
1(2,3)
Timeframe 1(2,3): Start
0:00 - 23:59
00:00
dT min
3K
Temperature difference
controller.
Hysteresis dT min
Timeframe 1(2,3): Start for the
collector function
0:00 - 23:59
06:00
max
23:59
1(2,3)
Timeframe 1(2,3): Stop
0:00 - 23:59
20:00
max
20:00
4
Timeframe 1(2,3):
Stop for the collector function
0:00 - 23:59
23:59
min
06:00
4
Meaning
Value range
Typical
adjustment
Indication
Fig. 30