In England and Wales, the current edition of the Building Regulations issued by the
Department of the Environment and the Welsh Office. In Scotland the current edition
of the Building Standards (Scotland) Regulations issued by the Scottish Executive. In
Northern Ireland, the current edition of the Building Regulations (Northern Ireland)
issued by the Department of the Environment for Northern Ireland. In the Republic of
Ireland the installation must also conform with the relevant parts of:
The current editions of:-
IS 813 “Domestic Gas Installations”
ICP3
IS327
All relevant national and local rules in force.
Where no specific instructions are given, reference should be made to the relevant
British Standard Code of Practice.
4.2
In the United Kingdom,as supplied the appliance can be installed in the following
situations: -
For installations without the Spanish basket casting.
!
To a fireplace complete with surround and hearth as shown in figure 1 and
complying with BS1251.
For installations with the Spanish basket casting.
!
To a fireplace complete with surround and hearth as shown in figure 2 and
complying with BS1251.
For fireplace openings having dimensions different to those shown in figure 2 refer to
Table 1 and BS 5871-Part 3 for flue sizes.
Into a fireplace that has a fireback of nominal size 400mm and conforming to BS1251.
Into a Replacement Chair Brick as below: -
!
‘Quattro’, ‘Anthem’, ‘Majestic’ and models not supplied with a firefront
Into a Baxi Fires Division Replacement Chairbrick. Part number 0552311
!
‘Azure’ model
Into a B&Q Replacement Chairbrick. Part number 0552301
Suitable flues and minimum flue sizes are as follows: -
225mm x 225mm conventional brick flue.
175mm diameter lined brick or stone flue.
200mm diameter factory made insulated flue manufactured to BS4543.
175mm diameter flue pipe. See BS6461 Part 1 for suitable materials.
The minimum effective height of the flue must be 3m.
Page 8