Power Supply
The
DinBox RTU M4
is powered via a wide range 85-264 V AC mains or an optional 9-
25 V DC power supply. The AC powered RTU can be optionally delivered with 25F
SuperCap capacitor for -short time- power backup.
Configuration interface
Local and remote configuration is possible via a graphical user interface [GUI] via HTML
in a standard web browser. Additionally configuration, debugging and tracing is also
possible via the serial RS232 interface.
GSM Module
The InduBox RTU M4 is using a Sierra Wireless CF3 footprint GSM module as WAN
device. Thanks to the Sierra Wireless CF3 HL footprint for the WAN module, the
InduBox GSM M4 offers the flexibility to easily migrate communication technologies,
thus making it future proof.
Depending on the application, the modem can be provided with standard 3GPP cellular
2G GPRS, 3G UMTS, 4G LTE, LPWA (low power wide area), LTE Cat-M1 or NB-IoT.
LPWA with 3GPP 2G GPRS fallback is also possible. Most modules are available for
global or NAM, EMEA and APAC only regions.
The following options are possible (Q3 2018) :
3GPP
HL6528 – quad band GSM/GPRS & GSM Data
HL6528RD – quad band GSM/GPRS
HL8518 – dual band HSPA, GSM/GPRS/EDGE
HL8548 – quad band HSPA, GSM/GPRS/EDGE
HL7690 – FDE band LTE Cat-1 (*)
HL7692 – FDE band LTE Cat-1 with dual band GSM/GPRS/EDGE fallback (*)
LPWA
HL7800 – LTE Cat-M1, NB-IoT
HL7802 – LTE Cat-M1, NB-IoT with dual band GSM/GPRS fallback
(*) only with 1-SISO antenna connection
A standard FME connection is provided for connecting the external GSM antenna.