![Bausch Datacom DinBox RTU M4 Скачать руководство пользователя страница 38](http://html.mh-extra.com/html/bausch-datacom/dinbox-rtu-m4/dinbox-rtu-m4_reference-manual_2711470038.webp)
5.2
Configuration via the serial interface
Use the standard Bausch Datacom ‘white’ RJ45 to DB9 serial cable to connect to the
serial interface
DinBox RTU M4
. The asynchronous parameters are 115.200 bps 8N1
with RTS/CTS flow control enabled.
This interface is used to debug the
DinBox RTU M4
.
During startup some basic information is sent.
...
15:24:30 (INFO) **********************************
15:24:30 (INFO) *** DinBox RTU M4 ***
15:24:30 (INFO) **********************************
15:24:30 (INFO) Copyright: 2019 Bausch Datacom NV
15:24:30 (INFO) Version: v1.3-16-g91a23bf
15:24:30 (INFO) Compiled: Jun 7 2019 10:30:17
15:24:30 (INFO) Target: STM32F437 : Bank 1
15:24:30 (INFO) starting picoTCP...
15:24:30 (INFO) picoTCP stack initialized
15:24:31 (INFO) WM: 104 Server
15:24:41 (INFO) HL module up and running
15:25:00 (INFO) WAN IP address: 10.35.0.10
Via the
Administration-Traces
page it’s possible to enable trace information about
a specific functionality.
Via proprietary at-commands it’s possible to configure, test or debug the
DinBox RTU
M4
.
To gain full access a login in needed:
at#login
Username:admin
Password:********
OK
After 3 minutes if no serial activity the interface will automatically logout.
To see all the possible commands:
at#?
Bausch M4 command set:
1. at#?
2. at#info
3. at#gcfg
4. at#gbank
5. at#gwanip
6. at#rst
7. at#defaults
8. at#get#
9. at#set#
10. at#test
11. at#ftp