5.4.3 Installing the configuration file
Installing the configuration in the
DinBox RTU M4
can be done remotely via FTP or
locally via the HTML GUI.
A. Remotely
To make this option possible all FTP parameters must be proper configured via the
Configuration-Modbus-General
page
The download must be triggered through the IEC 60870-5-104 command “IOA to trigger
FTP download”. Default IOA is 6000. This ASDU TI58 “single command with time tag”
that should be turned “on”.
The status of the FTP download can be monitored through the “IOA for download
status” event. Default IOA is 6001. This is a IEC 60870-5-104 item of type MME-C.
IOA Value
0 → no download done
1 → downloading
2 → download successful
3 → download error
B. Locally
It's possible to locally upload the *.json file via the
Configuration-Modbus-
Mapping
page.
If needed, the saved Modbus mapping information can be checked via the
Configuration-Modbus_Mapping
page. There you will find a complete detailed
overview.