Parallel partial discharge and dissipation factor measurement
PD-TaD 62
64 / 114
822-187-3
Select existing evaluation
1. In the
Template
menu, select the input field for the evaluation and press the rotary knob
to confirm.
2. In the
Evaluation
menu, select an evaluation and press the rotary knob to confirm.
If you wish to (re-)use an evaluation in accordance with IEEE 400.2, select it, select the
Copy & modify
menu item in the context menu and, if required, adapt the evaluation.
3. In the context menu, select the
Select
menu item.
The evaluation is included in the current template.
4. To save the template, select the
Save
menu item.
9.1.2
Template according to IEEE 400.2: Set parameters
The parameters of this template correspond to the valid draft of the new IEEE 400.2. The
exact details about the implemented test voltages and evaluation criteria are given in the
frida TD or viola TD user manuals.
Test types according to IEEE 400.2:
Installation
- Test after installation of a cable system before installation of
terminations/joints, connection and transition sleeves. This test is conducted to detect
damage during transport, storage and installation.
Acceptance
- Test after installation of a cable system, including terminations/joints,
connection and transition sleeves before the cable system is put into normal operation.
This test is conducted to detect damage during installation.
Maintenance
- Test during life cycle of a cable system. This test is conducted to detect
the age of a cable system and to check the operational viability. Maintenance tasks can
be planned depending on the test results.