PD-TaD 62
Connecting the system
822-187-3
41 / 114
6.10.3 Connecting the system using an HV connection cable with operational
earthing (option)
Prerequisites
The workplace must be de-energised, earthed and short-circuited.
Further information: Chapter
Ensuring there is no voltage at the work place
(on page 33)
The connection points and far end are prepared for the measurement tasks.
Further information: Chapter
Preparing the test object terminals
(on page 33)
HV coupling unit of PD-TaD and the cable terminations of the test object are clean and
dry.
Further information: Chapter
Cleaning the PD-TaD 62 and system components
(on page
Required equipment
PD-TaD incl. connection cables
HF filter
PoE cable
Laptop incl. Ethernet and USB cable
Anti-corona protection
Note:
All the necessary connection cables and connecting elements are included in the
standard delivery.
Procedure