Function test
Operation Manual
Safety I/O Terminals
SI4000 / SO4000
Document no.: 5.08009.05
Baumüller Nürnberg GmbH
60
8.1
The following course of action is recommended when conducting the function tests:
1
Separate all actuators and drives from the output terminals electrically.
2
Test the logic circuit by forcing variables in the ProSafety safe programming interface
(see chapter “FORCING AND OVERWRITING“ in the
>
Application Manual b maXX
safe PLC
<
). Check whether the behavior of the logic corresponds with the expected
function. Also check whether the evaluation of multi-channel safety components is con-
ducted in a multi-channel manner.
3
Only connect the actuators and drives to the safe output terminals once no errors have
been detected in the inspection of the logic circuit.
4
Conduct a complete function test with all sensors (initiators), switches, actuators and
drives.
To conduct the function tests, trigger all safety functions sequentially and document the
system’s reaction. Check whether the reaction corresponds with the expected behav-
ior.
The function test must lead to the following results:
n
the logical allocation of all system components is
correct
n
the allocation of all system components is
complete