Installation
• The HF-connection of a screen with ground can also occur capacitively. This avoids low-frequent errors
due to ground loops. Screening cables which pass different EMC ranges, may not be opened at the
terminals, because the screening attenuation otherwise decreases highly. These must lead to the next
module without interruption.
• The screen connection must occur with large surface area and low impedance. Cable tails with a length
of only 3cm (1cm wire = 10nH) reduce the screening effect at errors in the MHz range up to 30dB!
NOTE
The braided screen must have a coverage of at least 85%. The following cables possess an
especially high interference potential :
• Motor cable
• Cable to external chopper resistors
• Cable between mains filter and mains choke
• Cable between mains choke and converter
Figure 6.9: Suggestions for the screening plate at the device
66
Instrution
Manual
b
maXX®
BM3400
from
206
Do
ument
No.:
5.07013.03
Baumueller
Kamenz
GmbH
Содержание b maXX BM3400 Series
Страница 1: ...E 5 07013 03 Instruction Manual b maXX BM3400 ...
Страница 2: ......
Страница 4: ......
Страница 10: ...T 0 10 Instru tion Manual b maXX BM3400 from 206 Do ument No 5 07013 03 Baumueller Kamenz GmbH ...
Страница 144: ...T 10 Repair 144 Instru tion Manual b maXX BM3400 from 206 Do ument No 5 07013 03 Baumueller Kamenz GmbH ...
Страница 165: ...De laration of Conformity C 5 T Instru tion Manual b maXX BM3400 165 Do ument No 5 07013 03 from 206 ...
Страница 191: ...E Appendix E List of gures Instru tion Manual b maXX BM3400 191 Do ument No 5 07013 03 from 206 ...
Страница 195: ...F Appendix F Index Instru tion Manual b maXX BM3400 195 Do ument No 5 07013 03 from 206 ...
Страница 196: ...T F Appendix F Index 196 Instru tion Manual b maXX BM3400 from 206 Do ument No 5 07013 03 Baumueller Kamenz GmbH ...
Страница 202: ...T F Index 202 Instru tion Manual b maXX BM3400 from 206 Do ument No 5 07013 03 Baumueller Kamenz GmbH ...
Страница 204: ......
Страница 205: ... ...