5
|
Installation
Baumer Hübner
20
Operating Manual
HMG10 & HMG10P EtherNet/IP | V1, T1
1
3
2
9
7
8
4
4
1
1
4
≥
ø
d
>113 mm
ø
d
5 6
1
Self-locking nut M6 (ISO 10511)
2
Threaded rod M6 (variable length ≤ 210 mm)
3
Grounding strap
4
Washer B6.4 (ISO 7090)
5
Through hollow shaft
6
Torx screw M3x12 mm (ISO 7045)
7
Torque arm
8
Cheese-head screw M6x8 mm for grounding
strap (ISO 1207)
9
Washer B6.4 for grounding strap
(ISO 7090)
Tool
n
10 mm
n
10 mm
n
1,6×8 mm
n
Measuring gauge
Instruction:
a) Verify drive shaft about any concentricity error (see further links).
b) Mount the encoder in a way ensuring the electrical connection is protected against water
ingress.
c) Apply grease onto the drive shaft.
d) Loosen the Torx screw on the clamping ring a little. Do not unscrew the screw completely.
e) Slide the encoder onto the drive shaft.
f) Tighten the Torx screw on the clamping ring with a torque of 2-3 Nm.
g) Mount the torque arm together with threaded rod, washers (3x) and self-locking nuts (3x).
Observe the torque arm mounting instructions (see further links).
h) Attach grounding strap using cheese head screw and washer.