Operating Instructions
Level measurement
CleverLevel
®
PL20H/S
Adaptive trigger – hygienic/industrial
5.1 PL20S mounting
DANGER
Risk of injury from hazardous medium
f
Wear protective equipment for hazardous media (e.g. acids, alkaline solutions).
f
Empty vessel and pipelines before mounting.
PTFE
1
2
PL20S with the following process connections:
G 1/2 A ISO 228-1 (BCID G07)
1/2-14 NPT (BCID N02)
9
Vessel and pipelines are free of media.
f
Seal thread on sensor with Teflon tape (PTFE).
f
Screw in sensor.
G 1/2 A tightening torque: 30 Nm max.
NPT tightening torque: 20 Nm max.
PL20S with the following process connections:
G 1/2 A ISO 228-1 (BCID G07) with industrial
weld-in sleeve for universal use, Ø 30 x 26
(ZPW1-711, ZPW1-721)
G 1/2 A hygienic (BCID A03) with weld-in sleeve
or adapter from Baumer
G 1/2 A DIN 3852-E (BCID G51)
For these process connections, do not seal with
Teflon tape (PTFE) or elastomer.
9
Vessel and pipelines are free of media.
9
Adapter or weld-in sleeve are mounted free of
dead space.
f
Screw in sensor.
Tightening torque: 15 ... 20 Nm
www.baumer.com