BUDE_Manual-CANopen_EN.doc
25/55
Baumer Hübner GmbH
23.10.2012/bja
Berlin, Germany
2100h Baud rate
U8
rw
2h yes After setting the baud rate, the EEPROM must
be saved and reinitialized
0 = 10 kBit/s
1 = 20 kBit/s
2 = 50 kBit/s
3 = 100 kBit/s
4 = 125 kBit/s
5 = 250 kBit/s
6 = 500 kBit/s
7 = 800 kBit/s
8 = 1000 kBit/s
2101h Node ID
U8
rw
1h yes Node number 1 - 127 possible
After setting the baud rate, the EEPROM must
be saved and reinitialized.
2110h Manufactures_Options
U32
rw
1h yes Bit1 = Code sequence (Object 6000h Bit0)
0 Not inverted
1 Inverted
Bit2 = scaling function (Object 6000h Bit2)
0 enabled
1 disabled
Bit3 = 0 BusOFF not removed
1 reinitate bus after BusOFF
Bit5 = 0 Heartbeat-Protokoll enabled
1 Nodeguarding-Protokoll enabled
Bit6 = 0 normal SYNC- response
1 fast SYNC- response (see Bit 7)
Bit7 = 0 all PDO Modes enabled
1 only SYNC- Mode enabled
lowest Jitter
(only together with set Bit 6)
Bit8 = PDO1 Delay 2ms
0 1800h-5h = 6200h
1 1800h-5h = 6200h + 2ms
Bit9 = Responce by write to object
Resolution/overall resolution
0 Offset reset
1 Offset not reset
(Version from V1.08)
Bit10 = Response by Reset Node (from V 1.09)
0 HW Reset
1 Init NMT state
2201h Statistics
REC
00h Biggest subindex
U8
ro
3h
No. of subindexes
01h No. of position errors
U32
ro
0h yes Position control
02h Time in seconds
U32
ro
0h yes Time since last reset
03h Number timer reset
watchdog
U32
ro
0h yes Timer watchdog
2300h Customer EEPROM range
ARR
Optional data can be stored in this object
00h Biggest subindex
U8
ro
7h
01h Data0
U16
rw
0h yes
02h Data1
U16
rw
0h yes
03h Data2
U16
rw
0h yes
04h Data3
U16
rw
0h yes
05h Data4
U16
rw
0h yes
06h Data5
U16
rw
0h yes
07h Data6
U16