Terminal assignment and commissioning 

9.1 

Electrical connection 

The bus cover must rest fully against the housing and be firmly screwed in place. 
For electrical connection, pull off the bus cover using the following method: 

  Release the fastening screws of the bus cover 

  Carefully loosen the bus cover and lift off in the axial direction 

 
 

9.1.1 

Setting the user address 

The user address (MAC ID) is set decimally using two rotary switches in the bus cover. The maximum 
number of users is 63. 
 
Set the user address decimally using the two rotary switches 1 and 2. 
 

 

 

Example: 23 

 
 

9.1.2 

Setting the baud rate 

The baud rate setting is binary, using switches 2 and 3 of the 3-pin DIP switch in the bus cover. 
The default value is 125 KBit/s. 
 

Baud rate 

Setting of the 3 DIP switches 

 

 

Switch 1 

Switch 2 

Switch 3 

125 kBit/s 

OFF 

OFF 

250 kBit/s 

OFF 

ON 

500 kBit/s 

ON 

OFF 

  125 kBit/s * 

ON 

ON 

 

X = don`t care 
* As this switch setting is not defined, it is set internally to the default value 125 kbit/s. 

 
 
 

9.1.3 

Terminating resistor 

If the connected encoder is the last device in the bus line, the bus must be terminated with a resistor. 
The resistor is in the bus cover and is connected using a DIP switch. 

 

  The terminating resistor must be switched to "ON" at the last user with a DIP switch (default setting OFF). 

 

 

ON = Final user 
OFF = User X 

 

 

 

 

 

 

 

 

Содержание AMG 11 D13

Страница 1: ...Baumer H bner GmbH Max Dohrn Str 2 4 D 10589 Berlin Phone 49 0 30 690 03 0 Fax 49 0 30 690 03 104 info baumerhuebner com www baumer com Manual Absolute Encoder with Firmware version from 1 01...

Страница 2: ...Poll Mode 6 3 2 Change of state Mode COS 6 3 3 Cyclic Mode 6 4 Encoder operating parameters 6 5 Object model 7 6 I O assembly instances 8 7 Configuration of the encoder 9 8 Encoder position object 10...

Страница 3: ...eserved For this reason Baumer Huebner GmbH rejects any liability for the information compiled in the present manual Baumer Huebner GmbH nor the author will accept any liability for direct or indirect...

Страница 4: ...D with EDS file and manual also available as download in the Internet 1 2 Product assignment Shaft encoders Produkt Produkt Code Eds Datei Produktfamilie AMG 11 D13 0x0B AMG11D13 eds AMG 11 Singleturn...

Страница 5: ...afety remarks can result in malfunctions personal injury or damage to property Transport and storage Only ever transport or store encoders in their original packaging Never drop encoders or expose the...

Страница 6: ...adjustable between 1 and 65535 ms 4 Encoder operating parameters Description of operating parameters Parameter Description Value range Default value Product decimal hex Bit decimal Sense of rotation...

Страница 7: ...connection set It is a group 2 only server The table below indicates the object classes and the number of entities available in each class Object class No of instances 01h Identity 1 02h Message Route...

Страница 8: ...r supplies the following data From the viewpoint of the master this is input data Instance Type Name 1 Input Position value 2 Input Position value Warning flag Alarm flag Format of I O assembly data a...

Страница 9: ...6 5 Steps per turn 7 6 Total resolution in steps 8 7 Measurement steps not used 9 8 Preset value 10 9 Position value 12 10 Operating status 80 11 Singleturn resolution 81 12 Number of revolutions 82 1...

Страница 10: ...f required steps per turn See op parameters 8 read write Total resolution UDINT Number of required steps over the measurement range See operating parameters 9 read Reserved UDINT Reserved 0 10 read wr...

Страница 11: ...ons UINT Internal number of revolutions See operating parameters 83 Read Alarm signals UINT Error can lead to an incorrect encoder position Bit 0 0 No position error 1 Pos error 84 Read Supported alar...

Страница 12: ...set with each warning Offset value Attribute 91 contains the parameter offset value The offset value is calculated within the preset function and shifts the position value by the calculated value The...

Страница 13: ...ecimally using the two rotary switches 1 and 2 Example 23 9 1 2 Setting the baud rate The baud rate setting is binary using switches 2 and 3 of the 3 pin DIP switch in the bus cover The default value...

Страница 14: ...re end sleeves Use preferably isolated twin core end sleeves for supply voltage CAN_L Drain shield wire CAN_H Insert the drain wire into the drain terminal The drain wire of the cable must not touch t...

Страница 15: ...ption Off Not connected No power supply Dupl MAC ID Check not finished Power supply not connected Green flashing Device active and online No connections set up The device is working under normal condi...

Отзывы: