9287500995 Rev B
39
Sensing Voltage (see Figure 20). Band Setting values are entered as a percentage over a range of 0 to
15 percent in 0.1 percent increments.
Droop - Setpoint (%).
This setting controls the reactive droop compensation feature of the BE2000E. The
setpoint value is based on a 0.8 power factor load and determines the amount of change permitted in the
generator voltage setpoint when the BE2000E responds to a reactive load. The setpoint value is
adjustable from 0 to 10 percent in increments of 0.01 percent.
Field Current Regulator (FCR) - FCR Setpoint (A).
This setting defines the field current setpoint when
operating in Manual mode. The FCR Setpoint field accepts a value of 0 to 3 Adc in increments of 0.01
Adc.
Figure 21. Setting Adjustments Screen, Setpoint Tab
Reactive Power Control (VAR) - VAR Setpoint (% of nom.).
The VAR Setpoint determines the level of
generator vars maintained by the BE2000E when operating in Var Control mode. Values from
–
100 to
+100 percent in 1.0 percent increments may be entered in the VAR Setpoint field.
Power Factor Control (PF) - PF Setpoint.
The PF Setpoint determines the level of generator power factor
maintained by the BE2000E when operating in Power Factor Control mode. PF Setpoint values are
adjustable from
–
0.6 to
–
1 (1) or 0.6 to +1 in 0.001 increments.
Startup Tab
The
Startup
tab settings of the
Setting Adjustment
screen are shown in Figure 22. Each setting of the
Startup
tab is described in the following paragraphs.
Startup Control - Gen Soft Start Time (sec).
This setting defines the time limit for the generator soft-start
voltage offset. The soft-start time can be set from 1 to 120 seconds in 1 second increments.
Underfrequency Setting - Corner Frequency (Hz).
The Corner Frequency setting defines the value of
frequency that causes the BE2000E to adjust the voltage setpoint so that the generator voltage follows
the selected volts per hertz slope. A value of 40 to 65 hertz can be entered in this setting field in 0.01
increments.
Underfrequency Setting - Slope (Volts/Hz).
The slope for generator underfrequency protection is selected
with this setting. A slope setting of 1 to 3.00 can be entered in increments of 0.01. The slope is a per-unit
setting.
BE2000E
BESTCOMS
™
Software
Содержание BE2000E
Страница 1: ...INSTRUCTION MANUAL FOR BE2000E Digital Voltage Regulator Publication 9287500995 Revision B Jan 15 ...
Страница 2: ......
Страница 8: ...vi 9287500995 Rev B Contents BE2000E ...
Страница 10: ...2 9287500995 Rev B General Information BE2000E ...
Страница 28: ...20 9287500995 Rev B Figure 4 BE2000E Dimensions Installation BE2000E ...
Страница 29: ...9287500995 Rev B 21 Figure 5 Cutout and Drilling Dimensions BE2000E Installation ...
Страница 37: ...9287500995 Rev B 29 Figure 11 Typical Connections to a Single Phase Generator BE2000E Installation ...
Страница 40: ...32 9287500995 Rev B Installation BE2000E ...
Страница 68: ...60 9287500995 Rev B BESTCOMS Software BE2000E ...
Страница 74: ...66 9287500995 Rev B Maintenance and Troubleshooting BE2000E ...
Страница 80: ...72 9287500995 Rev B Revision History BE1 11f ...
Страница 81: ......