9287500995 Rev B
37
changes can be sent to the BE2000E by pressing the
Enter
key on your PC keyboard after changing the
setting.
Receiving Settings
BE2000E settings are retrieved by clicking the
GetFromUnit
button. This causes the BE2000E settings to
be displayed on the settings screen. Settings can also be received from the BE2000E by clicking
Communications
on the menu bar and clicking
Get From Unit.
Saving Settings to BE2000E Memory
Settings are saved in nonvolatile memory (EEPROM). In the event of a power loss, these are the settings
that are active at power up. If settings are changed and sent to the BE2000E but not sent to EEPROM,
the changed settings are lost if BE2000E operating power is lost. When exiting BESTCOMS-BE2000E or
closing communication, you are asked if you want to save the settings to EEPROM. This question is
asked even if no settings changes were made.
When communication is enabled, setting changes are saved to EEPROM by clicking the EEPROM
button. The opportunity to save settings to EEPROM is also given through a dialog box when exiting
BESTCOMS-BE2000E or closing communication.
Setting Definitions
Each of the six setting groups has a corresponding BESTCOMS-BE2000E screen. The settings of each
screen are categorized by one or more tabs. In the following paragraphs, settings are arranged and
defined according to the organization of the BESTCOMS-BE2000E screens and tabs.
System Configuration
The
System Configuration
screen consists of one tab labeled
System Settings
. Click the
Configure
button
to access the
System Configuration
screen or click
Screens
on the menu bar and click
System
Configuration.
System Settings
System settings are shown in Figure 20 and are described in the following paragraphs.
Sensing Voltage.
This setting is used to configure the BE2000E for either single-phase or three-phase
sensing voltage.
Version Numbers.
These two version numbers are read-only. They indicate the BESTCOMS-BE2000E
software version and the BE2000E embedded software version. If a BE2000E version number is not
shown, then the PC and software have not communicated with the BE2000E. The BE2000E version
number is indicated only when communication between the BE2000E and BESTCOMS-BE2000E occurs.
Bus PT Ratio.
The ratio of the bus sensing transformer is entered in this setting field. This ratio allows the
voltage displayed through BESTCOMS-BE2000E to match the actual bus output voltage. A ratio of 1 to
150 may be entered in increments of 0.01
Regulator Sensing Voltage (V).
The nominal generator line-to-line ac voltage obtained from the generator
sensing transformer is entered in this setting field. Voltages within the ranges of 100 to 140 Vac, 200 to
280 Vac, or 340 to 560 Vac may be entered in 0.1 Vac increments. A setting of 600 Vac is also possible.
Regulator Sensing Current (A).
This read-only field indicates the rated output of the current transformer
(CT) that supplies the BE2000E with B-phase generator line current.
Rated KVAR Value.
This read-only field displays the rated kvar value.
Voltage Low-Line Scale Factor.
This setting defines the scale value applied to the voltage setpoint, the
fine voltage adjust band limits, and the line voltage dependent protection thresholds when the 52JK input
is configured as Low-Line Override.
BE2000E
BESTCOMS
™
Software
Содержание BE2000E
Страница 1: ...INSTRUCTION MANUAL FOR BE2000E Digital Voltage Regulator Publication 9287500995 Revision B Jan 15 ...
Страница 2: ......
Страница 8: ...vi 9287500995 Rev B Contents BE2000E ...
Страница 10: ...2 9287500995 Rev B General Information BE2000E ...
Страница 28: ...20 9287500995 Rev B Figure 4 BE2000E Dimensions Installation BE2000E ...
Страница 29: ...9287500995 Rev B 21 Figure 5 Cutout and Drilling Dimensions BE2000E Installation ...
Страница 37: ...9287500995 Rev B 29 Figure 11 Typical Connections to a Single Phase Generator BE2000E Installation ...
Страница 40: ...32 9287500995 Rev B Installation BE2000E ...
Страница 68: ...60 9287500995 Rev B BESTCOMS Software BE2000E ...
Страница 74: ...66 9287500995 Rev B Maintenance and Troubleshooting BE2000E ...
Страница 80: ...72 9287500995 Rev B Revision History BE1 11f ...
Страница 81: ......