Table 14. Gain Adjustment Ranges 

Gain Adjust – LED #10 Blinking Slowly 

Maximum Adjustment Range: 

0.5 to 4.5 kg for AVR and 0 to 100 kg for FCR 

When the unit is operating in AVR, PF, and var modes, gain adjustments are made to 
AVR kg. When in FCR mode, gain adjustments are made to FCR kg. Front Panel 
increments: AVR kg = 0.01  FCR kg = 0.1

 

LED 

Minimum Value 

*

 

Maximum Value 

*

 

AVR 

FCR 

AVR 

FCR 

 

12 

4.17 

11.1 

4.50 

12 

11 

3.84 

10.1 

4.16 

11 

10 

3.50 

9.1 

3.83 

10 

3.17 

8.1 

3.49 

2.84 

7.1 

3.16 

2.50 

6.1 

2.83 

2.17 

5.1 

2.49 

1.84 

4.1 

2.16 

1.50 

3.1 

1.83 

1.17 

2.1 

1.49 

0.85 

1.1 

1.16 

0.5 

0.84 

*

 

Minimum and maximum values may differ from the Table 14 values if 
the gain value has been changed in BE2000E software.  

† BESTCOMS-BE2000E software allows a maximum FCR kg setting 

of 1,000 kg. A kg setting of 12 or more entered in BESTCOMS-
BE2000E will be reduced to 12 with the first push of the HMI 
“DOWN” pushbutton when adjusting FCR kg via the front panel. 

Table 15. Fine Voltage Adjust Setting Ranges 

Fine Voltage Adjust – LED #11 Blinking Slowly 

Maximum Adjustment Range: 

15% to +15% 

Increment: 0.1V 

The adjustment range for Fine Voltage Adjust is based on the fine voltage 
adjustment band setting. The default adjustment range is –10% to +10%. See 
the 

BESTCOMS Software 

chapter for information about the Fine Voltage 

Adjustment Band Setting. 

Communication Port 

A communication port is located on the rear panel and consists of a female RS-232 (DB-9) connector. 
The communication port serves as an interface for programming (setup) of the BE2000E. Figure 2 
illustrates the location of the communication port. 

Programming requires a standard 9-pin serial communication cable connected between the BE2000E and 
an IBM-compatible PC or handheld computer operating with BESTCOMS-BE2000E software. 
BESTCOMS-BE2000E operates with systems using Windows

®

 XP 32-bit SP2/SP3, Windows Vista 32-bit 

(all editions), Windows 7 32-bit (all editions), and Windows 7 64-bit (all editions). BESTCOMS-BE2000E 
is supplied with the BE2000E. A detailed description of BESTCOMS-BE2000E is provided in the 

BESTCOMS Software

 chapter. 

BE2000E 

Human-Machine Interface 

Содержание BE2000E

Страница 1: ...INSTRUCTION MANUAL FOR BE2000E Digital Voltage Regulator Publication 9287500995 Revision B Jan 15 ...

Страница 2: ......

Страница 3: ...ting Specifications Conventions Used in this Manual Important safety and procedural information is emphasized and presented in this manual through warning caution and note boxes Each type is illustrated and defined as follows Warning Warning boxes call attention to conditions or actions that may cause personal injury or death Caution Caution boxes call attention to operating conditions that may le...

Страница 4: ... must be well understood prior to installation operation or maintenance For terms of service relating to this product and software see the Commercial Terms of Products and Services document available at www basler com terms This publication contains confidential information of Basler Electric Company an Illinois corporation It is loaned for confidential use subject to return on request and with th...

Страница 5: ...e Droop Compensation 16 Underfrequency 17 Protection 17 Generator Soft Start 18 Installation 19 Mounting 19 Connections 22 BE2000E Terminations 22 Generator Voltage Sensing Inputs 24 Phase B Line Current Sensing Input 24 Raise and Lower Contact Inputs 24 Var Power Factor Control Contact Input 24 Parallel Generator Compensation 24 Analog Auxiliary Adjust 24 Power Supply Inputs 24 Chassis Ground 24 ...

Страница 6: ...ubleshooting 61 Preventative Maintenance 61 Troubleshooting 61 Generator Voltage Does Not Build 61 Low Generator Output Voltage 62 High Generator Output Voltage 62 Poor Voltage Regulation 63 Generator Output Unstable Hunting 63 OVEREXCITATION SHUTDOWN Indicator Is Annunciating 63 LOSS OF GENERATOR SENSING Indicator Is Annunciating 64 OVEREXCITATION LIMITING Indicator Is Annunciating 64 UNDERFREQUE...

Страница 7: ...9287500995 Rev B v Metering 69 Environment 70 Type Tests 70 UL Approval 70 CSA Certification 70 CE Compliance 70 Physical 70 Revision History 71 BE2000E Contents ...

Страница 8: ...vi 9287500995 Rev B Contents BE2000E ...

Страница 9: ...power var regulation Programmable stability settings Soft start control with an adjustable time setting in AVR control mode Overexcitation OEL limiting in AVR var and PF control modes Underfrequency volts hertz regulation Crowbar circuitry protects the field Overtemperature protection Three phase or single phase generator voltage RMS sensing regulation in AVR mode Single phase generator current se...

Страница 10: ...2 9287500995 Rev B General Information BE2000E ...

Страница 11: ...riptions Control Description SELECT This pushbutton selects a function for adjustment Successive presses of the SELECT pushbutton scrolls through the list of BE2000E functions to be adjusted UP This pushbutton increases the setting level of the function being adjusted DOWN This pushbutton decreases the setting level of the function being adjusted UP SELECT DOWN Manual Mode Loss of Sensing Over Vol...

Страница 12: ...flashes for 5 seconds when the BE2000E is powered up following shutdown for loss of generator sensing condition Over Voltage LED 1 This LED blinks rapidly when the generator output voltage exceeds the setpoint for 0 75 seconds The BE2000E will shut down when a generator overvoltage condition is detected The Generator Overvoltage LED flashes for 5 seconds when the BE2000E is powered up following a ...

Страница 13: ...Pressing the SELECT button causes the regulator to exit the adjustment mode Mode status LEDs blink approximately twice per second Table 3 BE2000E Front Panel Adjustment Indicator Descriptions Indicator Description Fine Voltage LED 11 This LED blinks slowly when the Fine Voltage level is selected for adjustment via the front panel push buttons Gain LED 10 This LED blinks slowly when the Gain adjust...

Страница 14: ...e bottom LED which is labeled MIN and ABSORB LEAD The setting range for each LED is summarized in Tables 4 through 15 LEDs in the tables are numbered from 1 to 12 with 1 being the lowermost LED labeled MIN ABSORB LEAD and 12 being the uppermost LED labeled GEN LAG MAX Table 4 Coarse Voltage Adjust Setting Ranges Coarse Voltage LED 1 Blinking Slowly Maximum Adjustment Range Increment 6 Vac LED Incr...

Страница 15: ... 12 N A 11 N A 10 N A 9 N A 8 N A 7 N A 6 N A 5 N A 4 N A 3 N A 2 ON 1 OFF Table 7 Manual Mode If Limit Adjustment Ranges Manual Mode Adjust LED 4 Blinking Slowly Adjustment Range 0 to 3 Adc Increment 0 01 Adc LED Minimum Value Maximum Value 12 2 75 3 11 2 50 2 74 10 2 25 2 49 9 2 00 2 24 8 1 75 1 99 7 1 50 1 74 6 1 25 1 49 5 1 00 1 24 4 0 75 0 99 3 0 50 0 74 2 0 25 0 49 1 0 0 24 BE2000E Human Mac...

Страница 16: ...6 Blinking Slowly Maximum Adjustment Range 100 absorb to 100 generate Increment 1 0 LED Minimum Value Maximum Value 12 84 100 11 67 83 10 51 66 9 34 50 8 17 33 7 1 16 6 16 0 5 33 17 4 49 34 3 66 50 2 83 67 1 100 84 Minimum and maximum values may differ from the Table 9 values if the value has been changed in BESTCOMS BE2000E software BESTCOMS BE2000E has 0 5 percent resolution compared to the 1 0 ...

Страница 17: ...6 Minimum and maximum values may differ from the Table 10 values if the value has been changed in BESTCOMS BE2000E software BESTCOMS BE2000E has 0 001 resolution compared to the 0 01 resolution of the HMI Table 11 Underfrequency Adjustment Ranges Underfrequency Adjust LED 7 Blinking Slowly Maximum Adjustment Range 40 to 65 Hz Increment 0 1 Hz LED Minimum Value Maximum Value 12 63 0 65 0 11 60 9 62...

Страница 18: ...mum and maximum values may differ from the Table 12 values if the value has been changed in BESTCOMS BE2000E software BESTCOMS BE2000E has 0 01 resolution compared to the 0 25 percent resolution of the HMI Table 13 Stability Range Selection Settings Stability Range Select LED 9 Blinking Slowly Adjustment Range per LED 1 Frame Poles LED Range Selected 12 N A 11 N A 10 N A 9 N A Programmable 8 21 1 ...

Страница 19: ...ront panel Table 15 Fine Voltage Adjust Setting Ranges Fine Voltage Adjust LED 11 Blinking Slowly Maximum Adjustment Range 15 to 15 Increment 0 1V The adjustment range for Fine Voltage Adjust is based on the fine voltage adjustment band setting The default adjustment range is 10 to 10 See the BESTCOMS Software chapter for information about the Fine Voltage Adjustment Band Setting Communication Por...

Страница 20: ...12 9287500995 Rev B Figure 2 Location of Communication Port P 0007 41 WARNING LIVE TERMINALS AND HEATSINKS Human Machine Interface BE2000E ...

Страница 21: ...f BE2000E Operating Features Figure 3 Simplified Block Diagram BE2000E Function Blocks The following paragraphs describe each of the function blocks illustrated in Figure 3 The function of each block is explained along with the operation of all function block inputs and outputs Analog Inputs Six analog voltage and current inputs may be sensed and brought to the BE2000E input Generator Voltage Gene...

Страница 22: ...s monitored scaled and conditioned before being applied to the ADC This signal is used to calculate the dc value of field voltage for use in system protection Field Current IFIELD Current through the main power output switch is converted to a proportional voltage level This voltage signal is scaled and conditioned before being applied to the input of the ADC The result is used to calculate the dc ...

Страница 23: ... power supply Input power is single phase in the range of 180 to 240 Vac at a frequency of 200 to 360 hertz Power Supply The internal switch mode power supply receives power from the power input stage and supplies power at the required dc voltage levels to the internal circuitry of the BE2000E Power Amplifier Stage The power amplifier receives power from the power input stage and supplies a contro...

Страница 24: ...rrent quantities and then adjusts the dc excitation current to maintain vars at the setpoint Var control is enabled and disabled through the front panel switches or Windows communication software When the software is turned on var control is enabled or disabled through the var Power Factor Control 52J K contact input circuit The var setpoint is adjustable from 100 percent absorb to 100 percent gen...

Страница 25: ...g Activation Frequency Hz is entered as a value below the underfrequency corner where the engine unloading feature may be activated A frequency value of 0 9 to 9 0 Hz can be entered in 0 1 Hz increments The default value is 0 9 Hz Unloading Activation Rate Hz 25 ms of 0 to 25 5 Hz per 25 ms can be entered in 0 1 Hz per 25 ms increments The engine unloading feature is activated when the frequency r...

Страница 26: ...00E shuts down When the BE2000E is powered up following a loss of generator sensing shutdown the Loss of Sensing indication will flash for 5 seconds This function is disabled when a generator short circuit condition is detected or when sensed frequency drops below 12 Hz A generator short circuit is determined when the phase B CT current exceeds 3PU 15 Aac sensing current Loss of sensing is not act...

Страница 27: ...oisture and dust free environment Mounting The BE2000E is normally located in the generator conduit box It is designed for behind the panel mounting and requires a cutout for front panel viewing and access Mounting hardware consists of six customer supplied 12 thread forming screws that pass through mounting holes in the conduit box and thread into the plastic shell of the BE2000E The unit must be...

Страница 28: ...20 9287500995 Rev B Figure 4 BE2000E Dimensions Installation BE2000E ...

Страница 29: ...9287500995 Rev B 21 Figure 5 Cutout and Drilling Dimensions BE2000E Installation ...

Страница 30: ... two types of interface terminals Figure 6 One type is quarter inch quick connect terminals and the other is a nine pin DB9 connector All terminals are located on the rear of the unit The quarter inch quick connect terminal labels are located on the rear of the case Wires performing common functions such as voltage sensing leads should be grouped together The nine pin DB 9 type connector is used f...

Страница 31: ...9287500995 Rev B 23 Figure 6 BE2000E Rear Panel Terminals P 0007 41 WARNING LIVE TERMINALS AND HEATSINKS BE2000E Installation ...

Страница 32: ...s are connected to terminals 6U and 6D This remote adjust switch may be mounted up to 150 feet 45 meters away from the BE2000E when using twisted shielded cable Var Power Factor Control Contact Input A customer supplied enable disable contact for this function connects to the terminals labeled 52J and 52K This function is disabled by a closed contact Parallel Generator Compensation A customer supp...

Страница 33: ...re 7 illustrates the pin assignments of the communication port and Table 17 identifies the RS 232 connector pin functions A standard communication cable terminated with a DB 9 male connector is used for PC or hand held computer interface with the BE2000E as shown in Figure 8 Figure 7 Communication Port Pin Assignments Table 17 Communication Port Pin Functions Pin Function Name Direction 1 N C N A ...

Страница 34: ... 12 illustrates the connection of two BE2000E devices used in a Cross Current Reactive Differential application Note that the 0 1 ohm resistor shown may have to vary When operating in parallel reactive differential mode cross current attention must be paid to the use of the burden resistor shown in Figure 12 The burden resistor should have a value approximately 10 times the cross current loop resi...

Страница 35: ...9287500995 Rev B 27 Figure 9 Typical Connections with ABC Rotation and Three Phase Sensing BE2000E Installation ...

Страница 36: ...28 9287500995 Rev B Figure 10 Typical Connections with ABC Rotation and Single Phase Sensing Installation BE2000E ...

Страница 37: ...9287500995 Rev B 29 Figure 11 Typical Connections to a Single Phase Generator BE2000E Installation ...

Страница 38: ...ive Differential Connections for Two Generators Figure 13 Cross Current Reactive Differential Connections for Three or More Generators GEN 1 GEN 2 CTB1 CTB2 BE2000E CTB1 CTB2 BE2000E 0 1 0 1 CT CT LOAD CCC ENABLE CONTACT P0064 04 Installation BE2000E ...

Страница 39: ...front panel HMI connecting a handheld operating with BESTCOMS BE2000E software or connecting a PC operating with BESTCOMS BE2000E to the rear communications port of the BE2000E 6 Connect the rest of the BE2000E leads using the tagged identification 7 Start the prime mover generator and perform the final adjustments at rated speed and load 8 After the initial startup the BE2000E should not require ...

Страница 40: ...32 9287500995 Rev B Installation BE2000E ...

Страница 41: ...PC if desired Use the following procedure to install BESTCOMS BE2000E 1 Insert the CD ROM into the PC CD ROM drive 2 When the BESTCOMS Setup and Documentation CD menu appears click the Install button for the BESTCOMS application The setup utility automatically installs BESTCOMS BE2000E on your PC When the software is installed a Basler Electric folder is added to the Windows program menu This fold...

Страница 42: ...ration of the individual adjustments before attempting any initial adjustments Before starting the generator the procedures in the following paragraphs should be performed Remove the 5 ampere fuse before starting the generator for the first time Perform all preliminary engine governor adjustments without the regulator energized BESTCOMS Software BE2000E ...

Страница 43: ...ommunication is opened or the communication settings have been changed Open the BE2000E communication port by clicking on Communications on the menu bar hovering the mouse pointer over Open Comm Port and clicking RS 232 Port Figure 16 illustrates the menu selections for opening the BE2000E communication port Figure 16 Communications Port Menu Selection When RS 232 Port is selected the Password dia...

Страница 44: ...oup is accessed the individual settings of the group can be viewed and changed A setting is changed by clicking within the setting field and typing the new setting The range limit of a setting can be viewed by double clicking the setting Any setting changes made on a setting group screen must be sent to the BE2000E before viewing other screens Otherwise the setting changes will be lost A single se...

Страница 45: ...stem Configuration screen or click Screens on the menu bar and click System Configuration System Settings System settings are shown in Figure 20 and are described in the following paragraphs Sensing Voltage This setting is used to configure the BE2000E for either single phase or three phase sensing voltage Version Numbers These two version numbers are read only They indicate the BESTCOMS BE2000E s...

Страница 46: ...are scaled by the Voltage Low Line Scale Factor setting Single Phase Override When selected single phase three phase sensing mode dependent protection is changed to single phase mode Phase imbalance monitoring for loss of sensing detection is disabled Low Line and Single Phase Override When selected both the low line override and single phase override functions operate simultaneously Setting Adjus...

Страница 47: ...ed in the VAR Setpoint field Power Factor Control PF PF Setpoint The PF Setpoint determines the level of generator power factor maintained by the BE2000E when operating in Power Factor Control mode PF Setpoint values are adjustable from 0 6 to 1 1 or 0 6 to 1 in 0 001 increments Startup Tab The Startup tab settings of the Setting Adjustment screen are shown in Figure 22 Each setting of the Startup...

Страница 48: ...ature is activated when the frequency rate of change exceeds the setting of this field An unloading activation rate of 0 to 25 5 Hz per 25 ms can be entered in 0 1 Hz per 25 ms increments Unloading Droop Percentage The value in this field defines the percent drop in generator output voltage for each 1 5 percent decrease in generator frequency when operating in the Engine Unloading mode The Unloadi...

Страница 49: ... is set at 21 the PID button may be selected to access the PID window A Stability Range setting of 1 through 7 disables the PID button and prevents access to the PID window Table 18 BE2000E Stability Range Settings Frame Poles Time Constants Stability Range Generator T do Exciter Texc 360 4 1 0 0 17 1 430 4 1 5 0 25 2 570 4 2 0 0 33 3 740 4 2 5 0 42 4 1 000 4 3 0 0 50 5 740 6 3 5 0 58 6 1 000 6 4 ...

Страница 50: ...Loop Gain Kg FCR This setting adjusts the loop gain level of the PID algorithm for FCR Loop Gain values of 0 to 1 000 may be entered FCR operation in increments of 0 01 VAR PF PF Integral Gain KI This setting adjusts the integral gain and determines the characteristic of the BE2000E dynamic response to a changed PF setting PF KI values of 0 to 1 000 may be entered in increments of 0 01 VAR PF Var ...

Страница 51: ...n from gray to red Voltage Step Response Increment of AVR Setpoint V These two fields indicate the increase that occurs to the AVR setpoint when the corresponding Increment button is clicked The increase field is used to set and indicate the percentage that the AVR setpoint is increased when the Increment button is clicked The AVR Setpoint field indicates the value of voltage that corresponds to t...

Страница 52: ... FCR Tab Figure 27 illustrates the settings sensing values and alarm signal indicators of the FCR tab The settings of the FCR tab make it possible to increment and decrement the FCR setpoint of the BE2000E The sensing values and alarm signal indicators of the FCR tab are also displayed by the other tabs of the Analysis screen Field Current Step Response FCR Setpoint A This read only field indicate...

Страница 53: ...CR Setpoint indicates the value of current that corresponds to the decrease field Any setpoint value within range and lower than setpoint value can also be typed into The FCR Setpoint field which updates the decrease field also The FCR setpoint changes to this value when the adjacent button is clicked When clicked the Decrement button changes from gray to red to indicate that the FCR setpoint has ...

Страница 54: ...rement button is clicked Any setpoint value within the range and higher than setpoint value can be input to this filed The PF setpoint changes to this value when the adjacent button is clicked When clicked the Increment button changes from gray to red to indicate that the PF setpoint has increased to the value in the field Power Factor Step Response Decrement of PF setpoint This field indicates th...

Страница 55: ...Any setpoint value within the range and higher than setpoint value can be input to this filed The VAR setpoint changes to this value when the adjacent button is clicked When clicked the Increment button changes from gray to red to indicate that the VAR setpoint has increased to the value in the field VAR Step Response Decrement of VAR setpoint This field indicates the decrease that occurs to the V...

Страница 56: ...nts When the level of field current increases above the value of this field the OVEREXCITATION SHUTDOWN LED on the front panel lights and the OEL time delay starts timing down OEL Alarm Time Delay sec The value of this field determines the time delay between when the BE2000E recognizes an overexcitation condition and the BE2000E Alarm output terminals AL1 AL2 closes A time delay of 0 to 10 seconds...

Страница 57: ...ng Operation and Alarms screen can be frozen by clicking the Metering button while viewing the screen or by clicking Metering on the menu bar and clicking Disable Metering Metering can be resumed by clicking the Metering button or by clicking Metering on the menu bar and clicking Enable Metering The Metering Operation and Alarms screen consists of two tabs Operation and Alarm Status Operation Tab ...

Страница 58: ...Angle Degree This metering value indicates the phase angle difference in degrees between the generator voltage and the generator current Apparent Power VA This value is the calculated product of the metered generator voltage VAVG metered generator current Ib and the square root of 3 See Equation 1 3 I V VA B AVG Equation 1 Apparent Power Equation Real Power W This value is the calculated product o...

Страница 59: ...tpoint can also be entered at the Setting Adjustments screen Setpoint tab Reactive Power Control VAR VAR Setpoint of nom The background color of this field is green when the BE2000E is operating in AVR mode and is regulating the var setpoint Setpoint Power Factor This setting determines the level of power factor regulation maintained by the BE2000E The power factor setpoint can also be entered at ...

Страница 60: ...he low line and single phase override functions are active The Manual Mode Active indicator changes from black to red when the FCR control mode is active Switch Status Switch Status indicators indicate when the BE2000E control inputs are open or closed The 52JK switch open indicator changes from black to red when the user supplied contacts at terminals 52J and 52K are closed When this control inpu...

Страница 61: ... modified calculated and updated the PID window is closed by clicking the Update Setting Screen button The modified PID values are then shown on the Control Gain screen Figure 36 PID Window PID Calculation Based on Input Values The available range for the exciter time constant depends on the value entered for the generator time constant The default value for the exciter time constant is the genera...

Страница 62: ... To retrieve existing data pull down the PID List and select the record or list so that the gain and time constant parameters are displayed and highlighted Click the Get from a List button and the listed record input and output data displays in the boxes Settings Files BESTCOMS BE2000E enables you to print a list of BE2000E settings save BE2000E settings to a file and open a settings file and uplo...

Страница 63: ...E2000E unit Before uploading a file communication must be initiated with the BE2000E that is to receive the settings Refer to the paragraphs under the headings Starting the BESTCOMS BE2000E Application Caution Before uploading a settings file remove operating power from the BE2000E disconnect the field wiring from terminals F and F and reapply operating power to the BE2000E The upload process is s...

Страница 64: ...the new password is enabled and a dialog box appears to remind you to keep your password in a secure location Figure 39 Password Dialog Box Updating Embedded Firmware The BE2000E uses non volatile flash memory for storing its embedded firmware operating program and can be reprogrammed by connecting the RS 232 port located on the on the back of the device to a Windows compatible PC running the Embe...

Страница 65: ...lowing progress bar Figure 42 is shown while in process Figure 41 Communication Settings Figure 42 Reading Checking Settings Progress Bar The BE2000E Embedded Program Loader Figure 43 will be displayed Clicking the Get Device Information button displays the current device s model number style number application program version and serial number in the lower left hand corner of Figure 43 Figure 43 ...

Страница 66: ... Saved window will return the user to the BE2000E Embedded Program Loader screen Figure 43 Clicking Yes will display the Open Dialog box Figure 45 Figure 44 Settings File Saved Dialog Box Figure 45 Open Dialog Box Select the location of the embedded firmware update file select the file and click Open The embedded firmware will begin transferring from the PC to the BE2000E A progress bar as display...

Страница 67: ...Reading Checking Settings Figure 48 Sending Saved Settings Terminating Communication BE2000E communication is terminated by clicking on Communications on the menu bar and clicking Close Comm Port You are asked if you want to save the settings to EEPROM This question is asked even if no changes were made to the BE2000E settings When you execute the Close command with a Yes or No to save settings to...

Страница 68: ...60 9287500995 Rev B BESTCOMS Software BE2000E ...

Страница 69: ...t input power to the BE2000E Refer to the General Information chapter for input power requirements If voltage is not present refer to the generator manual for repair procedures If voltage is present proceed to Step 4 Step 4 Verify that the fuse is not open Replace any open fuse If no fuses are open proceed to Step 4 Step 5 Verify that the front panel OVEREXCITATION SHUTDOWN indicator is not lit If...

Страница 70: ...rmer is incorrect replace the sensing potential transformer If the sensing potential transformer is operating correctly proceed to Step 6 Step 6 Verify that the front panel OVEREXCITATION LIMITING indicator is not lit If the front panel OVEREXCITATION LIMITING indicator is lit check the generator and or load conditions Also check the field current limit setpoint for the correct level Interrupt inp...

Страница 71: ...p 5 Verify that regulation is not being affected by normal droop operation If droop operation is not affecting regulation proceed to Step 6 Step 6 Replace the BE2000E unit Generator Output Unstable Hunting Step 1 Verify that the governor for the prime mover is operating properly If the governor is not operating properly troubleshoot using the manufacturer s suggested procedures If the governor is ...

Страница 72: ...at the generator output voltage is present on all phases If the generator is missing a phase refer to the generator manual Generator is defective If generator output voltage is balanced on all phases proceed to Step 5 Step 5 Replace the BE2000E OVEREXCITATION LIMITING Indicator Is Annunciating Step 1 Check for generator overloading If the generator is operating with a larger than rated load shed l...

Страница 73: ...open circuit repair as necessary If there is no open circuit proceed to Step 5 Step 5 Verify that all connections are correct according to Figures 4 6 and 4 7 If connections are incorrect correct the problem If connections are correct proceed to Step 6 Step 6 Verify that the load being applied to the generator for droop testing is not purely resistive If only a resistive load is being applied to t...

Страница 74: ...66 9287500995 Rev B Maintenance and Troubleshooting BE2000E ...

Страница 75: ...40 Vac Range 2 240 Vac 200 to 280 Vac Range 3 480 Vac 400 to 560 Vac Range 4 600 Vac Generator Current Sensing Type 1 phase BØ 50 60 Hz Rating 5 Aac maximum continuous Burden 0 1 VA Terminals CT1 CT2 Contact Input Circuits Type Dry Contact Interrogation Voltage 13 Vdc Terminals Unit Parallel Control 52L 52M Raise 6U 7 Lower 6D 7 var PF Enable 52J 52K Common Alarm Output Type Form A Rated Load 7 Aa...

Страница 76: ... 100 Increment 0 1 PF Operating Mode Adjustment Range 0 6 lead to 0 6 lag Increment 0 001 Parallel Compensation Modes Reactive Droop and Reactive Differential cross current Droop Adjustment Range 0 to 10 Increment 0 01 Burden can exceed 1 VA if external resistors are added to the CT circuit Communication Port Interface Full Duplex RS 232 Connection DB 9 connector on rear panel Baud 4800 Data Bits ...

Страница 77: ... Metering Accuracy of all metering values assumes 25 C 50 60 Hz and less than 20 THD Generator Voltage Range 10 V to 79 kV Accuracy 0 5 Generator Current Range 0 1 to 5 000 A 5 A CTs Accuracy 0 5 Frequency Range 40 to 65 Hz Accuracy 0 2 Hz Field Voltage Range 0 to 200 Vdc Accuracy 5 0 Field Current Range 0 to 8 0 Adc Accuracy 0 5 Power Apparent Real and Reactive Range 0 to 99 MVA MW and Mvar Accur...

Страница 78: ...g and or mechanical products Standards used for evaluation CSA C22 2 No 14 CE Compliance This product has been evaluated and complies with the relevant essential requirements set forth by the EU legislation EC Directives Low Voltage Devices LVD 2006 95 EC Electromagnetic Compatibility EMC 2004 108 EC Harmonized Standards used for evaluation BS EN 50178 Electronic Equipment for use in Power Install...

Страница 79: ...indows 8 compatibility Table 21 Instruction Manual Revision History Manual Revision and Date Change May 11 Initial release A Nov 12 Corrected operating power frequency range and burden in the General Specifications chapter Added Storage statement in the Installation chapter Converted manual into new style and structure B Dec 14 Added settings and metering descriptions for the 52 JK function settin...

Страница 80: ...72 9287500995 Rev B Revision History BE1 11f ...

Страница 81: ......

Страница 82: ...dex FRANCE Tel 33 3 88 87 1010 Fax 33 3 88 87 0808 email franceinfo basler com No 59 Heshun Road Loufeng District N Suzhou Industrial Park 215122 Suzhou P R CHINA Tel 86 512 8227 2880 Fax 86 512 8227 2887 email chinainfo basler com 111 North Bridge Road 15 06 Peninsula Plaza Singapore 179098 Tel 65 68 44 6445 Fax 65 68 44 8902 email singaporeinfo basler com ...

Отзывы: