10
9287500995 Rev B
Table 12. Droop Adjustment Ranges
Droop Adjust – LED #8 Blinking Slowly
Adjustment Range: 0 to 10%
Increment: 0.25%
LED
Minimum Value
*
Maximum Value
*
12
9.25
10.00
11
8.5
9.00
10
7.75
8.25
9
6.75
7.50
8
6.00
6.50
7
5.25
5.75
6
4.25
5.00
5
3.5
4.00
4
2.75
3.25
3
1.75
2.5
2
1
1.5
1
0
0.75
*
Minimum and maximum values may differ from the Table 12 values if
the value has been changed in BESTCOMS-BE2000E software.
BESTCOMS-BE2000E has 0.01% resolution compared to the 0.25
percent resolution of the HMI.
Table 13. Stability Range Selection Settings
Stability Range Select – LED #9 Blinking Slowly
Adjustment Range per LED: 1
Frame/Poles
LED
Range Selected
12
N/A
11
N/A
10
N/A
9
N/A
Programmable
8
21
1,000/6
7
7
740/6
6
6
1,000/4
5
5
740/4
4
4
570/4
3
3
430/4
2
2
360/4
1
1
Human-Machine Interface
BE2000E
Содержание BE2000E
Страница 1: ...INSTRUCTION MANUAL FOR BE2000E Digital Voltage Regulator Publication 9287500995 Revision B Jan 15 ...
Страница 2: ......
Страница 8: ...vi 9287500995 Rev B Contents BE2000E ...
Страница 10: ...2 9287500995 Rev B General Information BE2000E ...
Страница 28: ...20 9287500995 Rev B Figure 4 BE2000E Dimensions Installation BE2000E ...
Страница 29: ...9287500995 Rev B 21 Figure 5 Cutout and Drilling Dimensions BE2000E Installation ...
Страница 37: ...9287500995 Rev B 29 Figure 11 Typical Connections to a Single Phase Generator BE2000E Installation ...
Страница 40: ...32 9287500995 Rev B Installation BE2000E ...
Страница 68: ...60 9287500995 Rev B BESTCOMS Software BE2000E ...
Страница 74: ...66 9287500995 Rev B Maintenance and Troubleshooting BE2000E ...
Страница 80: ...72 9287500995 Rev B Revision History BE1 11f ...
Страница 81: ......