BE1-50/51M-222 General Information
1-6
Figure 1-5. Instantaneous Characteristic Curves
Time Reset
Reset occurs when the current drops below pickup and the relay has not
timed out. Switch SW8-4 provides selection of either an instantaneous or
integrating reset characteristic. Opening SW8-4 forces the instantaneous
reset timer to zero when timed dropout occurs. This fast reset
characteristic prevents the ratcheting effect that may occur with repeating
system faults. Closing SW8-4 selects the integrating reset characteristic.
The integrating reset characteristic simulates the disk reset of
electromechanical relays. BE1-50/51M-222 relays provide the integrating
reset function even when input current falls to zero. Integrating reset
characteristics are shown in Figure 1-6.
Target Indicators
Magnetically latched, manually reset targets indicate that current of 0.2
amperes or greater was present in the trip circuit. Target coil resistance is
less than 0.1 ohm and operate time is less than one millisecond. See
50/51 Output specifications for maximum current rating.
Содержание BE1-50/51M-222
Страница 18: ...BE1 50 51M 222 General Information 1 13 MULTIPLES OF PICK UP Figure 1 11 Time Characteristic Curve I Inverse ...
Страница 25: ...BE1 50 51M 222 Controls and Indicators 2 3 Figure 2 2 BE1 50 51M 222 Location of Controls and Indicators ...
Страница 29: ...BE1 50 51M 222 Installation 4 2 Figure 4 1 Outline Dimensions C1 Case ...
Страница 30: ...BE1 50 51M 222 Installation 4 3 Figure 4 2 Panel Drilling Diagram C1 Case ...
Страница 32: ...BE1 50 51M 222 Installation 4 5 Figure 4 4 DC Control Connections ...
Страница 33: ...BE1 50 51M 222 Installation 4 6 Figure 4 5 BE1 50 51M 222 Overcurrent Relay Rear View ...