6-1
CAUTION
Substitution of printed circuit boards or individual components does not necessarily
mean the relay will operate properly. Always test the relay before placing it in operation.
SECTION 6
MAINTENANCE
GENERAL
BE1-50/51M-222 Overcurrent Relays require no preventive maintenance. However, periodic checks
should be performed according to scheduled practices. A recommended periodic test is provided in this
Section. If the relay fails to function properly and factory repair is desired, contact the Customer Service
Department of the Power Systems Group, Basler Electric, for a return authorization number prior to
shipping.
IN-HOUSE REPAIR
In-house replacement of individual components should be performed by qualified technicians.
Replacement parts may be purchased locally. The quality of replacement parts must be at least equal
to that of the original components. These parts may be ordered directly from Basler Electric. Where
special components are involved, contact the Customer Service Department of the Power Systems
Group, Basler Electric. When complete boards or assemblies are needed, the following information is
required.
1. Relay model number
2. Relay serial number
STORAGE
This protective relay contains long life aluminum electrolytic capacitors. Life in excess of 20 years may
be expected if the storage temperature does not exceed 40
C (72
F).
PERIODIC TESTS
General
All relays should be tested periodically to identify and correct any problems that are found.
Single phase relays such as the BE1-50/51M-222 are normally used in groups of four (three phase and
ground) on the protected circuit. Only three are required at any one time to provide complete protection.
The fourth one assures that protection is maintained even if one relay failed.
This protection scheme also allows one unit at a time to be withdrawn from service for testing purposes
without losing protection during the test. Refer to Section 5 for recommended test setups.
Содержание BE1-50/51M-222
Страница 18: ...BE1 50 51M 222 General Information 1 13 MULTIPLES OF PICK UP Figure 1 11 Time Characteristic Curve I Inverse ...
Страница 25: ...BE1 50 51M 222 Controls and Indicators 2 3 Figure 2 2 BE1 50 51M 222 Location of Controls and Indicators ...
Страница 29: ...BE1 50 51M 222 Installation 4 2 Figure 4 1 Outline Dimensions C1 Case ...
Страница 30: ...BE1 50 51M 222 Installation 4 3 Figure 4 2 Panel Drilling Diagram C1 Case ...
Страница 32: ...BE1 50 51M 222 Installation 4 5 Figure 4 4 DC Control Connections ...
Страница 33: ...BE1 50 51M 222 Installation 4 6 Figure 4 5 BE1 50 51M 222 Overcurrent Relay Rear View ...