BE1-50/51M-222 General Information
1-3
0.01
0.1
1
1 0
1 0 0
1 0 0 0
1 0 0 0 0
1
1 0
4 0
Instantaneous
Tap = 5 amps.
Time Tap = 1amp.
Curve S
Time Dial 4.0
1
2
3
4
5
M U L T I P L E O F P I C K U P
TIME IN SECONDS
Figure 1-2. Load Demand Characteristic Curve
SPECIFICATIONS
BE1-50/51M-222 Overcurrent Relays have the following features and capabilities.
Current Sensing Input
Continuous current: 14 amperes. One second current: 400 amperes.
TIME PICKUP Range
0.5 to 15.9 amperes in 0.1 ampere steps. Setting the TIME PICKUP to the
minimum pickup (0.5 ampere), places the relay in the most sensitive state
and may be used as a safety setting.
TIME Dropout
Dropout occurs at 95% of pickup value.