5-2
BE1-49 Operational Test
LOWER
TEMP. TRIP
CIRCUIT
POWER
SUPPLY
UPPER
TEMP. TRIP
CIRCUIT
AUXILIARY
CONTACTS
18
17
19
4
TEMP.
SENSING
RTD
SENSE
RTD
CURRENT
SOURCE
2
10
8
7
6
4
3
2
1
5
RESISTOR
DECADE
BOX
DS1
DS2
1
3
D.C.
+
5
8
6
7
}
APPROPRIATE AC OR
DC POWER SOURCE
Relay ground stud.
1
2
3
Not present in Options L and M.
DC source supplies a maximum of 250 Vdc.
DS3 and DS4 not required when Option 3 is 0. DS3 required when
Option 3 is 2. DS4 required when Option 3 is 1 or 3.
4
5
6
1/4 W Resistor is 10 ohms for copper RTD, 100 ohms for platinum.
If relay has current operated target, obtain minimum trip current by adding
parallel resistance to DS1 and DS2.
7
8
Omit DS2 when testing relays equipped with output options L or M.
Range of decade box is zero to 10 ohms for copper RTD; zero to
100 ohms for platinum.
D2817-10
07-09-98
DS4
DS3
9
Figure 5-1. Temperature Relay Test Setup
Содержание BE1-49
Страница 1: ...INSTRUCTION MANUAL FOR TEMPERATURE RELAY BE1 49 Publication Number 9 1267 00 990 Revision E 11 02...
Страница 2: ......
Страница 6: ...This page intentionally left blank...
Страница 12: ...This page intentionally left blank...
Страница 18: ...This page intentionally left blank...
Страница 27: ...BE1 49 Installation 4 9 Figure 4 8 S1 Case Panel Drilling Diagram Semi Flush Mounting...
Страница 28: ...4 10 BE1 49 Installation Figure 4 9 S1 Case Single Ended Projection Mount Panel Drilling Diagram Rear View...
Страница 29: ...BE1 49 Installation 4 11 Figure 4 10 S1 Case Double Ended Projection Mounting Panel Drilling Diagram Rear View...
Страница 30: ...4 12 BE1 49 Installation Figure 4 11 DC Connection Diagram...
Страница 38: ...This page intentionally left blank...
Страница 40: ...This page intentionally left blank...
Страница 41: ......