Electromagnetic Flowmeter
BF
M921
BASI
30
Operation manual
5.1.6.2
High flowrate limit (LIMIT PF2)
Value is flowrate expressed in selected flowrate units. Available range is according to the nominal diameter.
5.1.6.3
Hysteresis of flowrate limits (HYSTERESIS)
Value is flowrate hysteresis of limits expressed in selected flowrate units. Available range is according to the
nominal diameter.
5.1.7
Dosing
The flowmeter is able to control dosing of measured liquid. For this function digital input (start of dosing)
and one of digital outputs (end of dosing) are required.
5.1.7.1
Volume
Function enables user to set volume for dosing.
5.1.7.2
Actual
Function displays actual state of measured dose.
5.1.7.3
Stop dosing
Function enables user to stop dosing in progress.
Example setting 1
Digital input mode:
Start Dose
State output mode:
Dose On
Dosing volume:
1m3
Active level on the digital input starts dosing. Flowmeter switches state output and counts the dose. As
soon as measured dose is reached, flowmeter activates the State output to stop dosing. State output can
control (through contractor) valve or pump.