Installation Manual
AURO KNX
©
2020
bas
alt
e v
7.0
Current consumption KNX bus:
10mA
Ambient temperature:
Operation: -5°C to 45°C
Storage: -15°C to 55°C
Transport: -15°C to 55°C
Max. humidity:
93% relative humidity,
no moisture condensation
Protection class:
II
Type of protection: IP 20
Certification:
CE
Important advice
• Never connect the device to 230V or in the vicinity of it.
Make sure to maintain the distance specified in the applicable standards and regulations.
• Do not paint over the central IR window since this will prevent Auro to operate correctly.
Installation and commissioning
•
Auro is intended for ceiling mounting. In order to install Auro, an opening should be made with a
diameter of 43mm.
•
Connect the bus line according to the KNX standard.
•
The required voltage to operate comes from the KNX bus.
•
Load the physical address into Auro from ETS via the KNX bus.
•
Commission the Auro using ETS and load the configuration into the device.
•
Please refer to the software manual to configure the Auro.
Technical data
Features:
•
PIR motion sensor
•
lux sensor (only white version)
•
temperature sensor
•
monochrome white LED
Initialisation
: after a bus voltage failure or a bus reset, Auro will not be ready for operation for at least 5
seconds.