INSTALLATION AND USE MANUAL
SERVO DRIVE TYPE
– DB21
M.DRIVE.DB-21.GEN.ENG
Ed.
2022
Rev.11
Pag.
19 di 34
9.
DRIVE
SET-UP
(NEW
TURRET
INSTALLATION)
CAREFULLY CHECK THE SERVO DRIVE
INPUT VOLTAGE
SETTING.
A WRONG SETTING OF THE INPUT VOLTAGE WOULD DAMAGE IRREVERSIBLY THE UNIT.
THE DRIVE ARRIVE WITH THE TURRET PRE-SET, IN CASE OF WRONG PRESELECTION OF THE
TURRET SIZE AND TYPE CONTACT BARUFFALDI.
Sequence of operations N°2
(VOLTAGE SETTING)
1. Drive OFF (24Vdc Off)
2. Set OFF dipswitch n°6 if the input voltage
is 400V, set ON dipswitch n°6 if input voltage
is 230V.
3. Drive ON
Dipswitch
ON
OFF
1 2 3 4 5 6 7 8 9 10
220V
400V
Dipswitch
ON
OFF
1 2 3 4 5 6 7 8 9 10