Possible Malfunctions
104609
21 / 32
EN
Malfunction
Alarm
Appliance Condition
Solution
(AL04)
Damaged storage
container probe
alarm
Appliance stops
Check if ohm value is correct. If
not, replace the probe. If you
check free space in the storage
container first, you may produce
ice for subsequent 30 minutes by
touching the control key.
(AL05)
Maintenance
order required
Appliance continues
operation
Contact the service company
(Reset the alarm by touching the
control key for 10 seconds)
(AL06)
High temperature
at the inlet of the
condenser
Appliance stops,
condenser fan remains
on to reduce
condenser's temperature
or the water valve
remains open with
condensed water (when
the appliance is cooled,
it re-starts, undertakes a
few attempts to check if
the alarm is cleared and
then stops for good)
Check condenser for cleanliness
and ventilation
Check if condenser fan rotates
Check condenser probe location
Check water salinity and water
supply for operation
(AL07)
Alarm of
condenser's
sensor
Damaged condenser
probe or outside the
allowable value limits;
appliance operates with
continuous ventilation or
water supply is always
on
Check condenser probe
connection to PCB
Check if the measured ohm value
is correct; if not, exchange the
probe