Operation and Installation Manual PBTC-200-E
21-54C3-7D0001/A
05/2023-EHT-441168
Notice:
Technical data subject to change without notice.
No claims for damage arising from alternations, errors or misprints shall be allowed.
Page 4 / 40
Specific Conditions of Use
All power and data line cable entries to the trace heater boxes shall be installed with Ex eb or Ex tb cable glands or blanking elements
providing a minimum ingress protection of IP66.
Supply cables and power cable entry glands shall be selected per manufacturer’s installation instructions for appropriate conductor
size and temperature range (refer to DesignGuide, chapter "Checklist customized entry port").
PBTC shall be applied for maintenance temperature control only. The Pt100 wiring shall be part of a fixed installation and shall be
effectively clamped to prevent pulling or twisting.
Trace heater boxes, Aluminium housing type 07-5180-****/****
The enclosure must not be used in areas affected by charge-producing processes, mechanical friction and separation processes,
electron emission (e.g. in the vicinity of electrostatic coating equipment), and pneumatically conveyed dust.
Temperature Controller Type 27-54C*-****/****
Shall be applied for maintaining temperature only.
The Pt100 wiring shall be part of a fixed installation and shall be effectively clamped to prevent pulling or twisting.
2.2
Certifications / Approvals / Marking
According to system certificate:
IECEx DEK 20.0055X
DEKRA 20ATEX0093 X
Junction Box with Electronic Thermostat Module PBTC-200-E
for BARTEC PSB, MSB trace heaters
IECEx DEK 20.0055X
Ex eb mb [ib] 60079-30-
1 IIC T6…T3
1
Gb
Ex tb [ib] 60079-30-
1 IIIC T80 °C… T170 °C
DEKRA 20ATEX0093 X
II 2G Ex eb mb [ib] 60079-30-
1 IIC T6…T3
II 2D Ex tb [ib] 60079-30-
1 IIIC T80 °C… T170 °C
According to enclosure certificate:
IECEx DEK 21.0074X
DEKRA 21ATEX0118 X
Junction Box with Electronic Thermostat Module PBTC-200-E
for BARTEC PSB, MSB, HSB+ or HTSB trace heaters
IECEx DEK 21.0074X
Ex eb mb [ib] 60079-30-
1 IIC T6…110 °C (T4)
Ex tb [ib] 60079-30-1 IIIC T
L
80 °C…T
L
110 °C
DEKRA 21ATEX0118 X
II 2G Ex eb mb [ib] 60079-30-
1 IIC T6…110 °C (T4)
II 2D Ex tb [ib] 60079-30-1 IIIC T
L
80 °C…T
L
110 °C
2.3
Reasonably foreseeable Misuse
The following activities are a misuse of the product and are not allowed:
Use of the Junction Box with Electronic Thermostat Module PBTC for purposes other than those described in the intended use
Installation, commissioning, operation, maintenance or disposal by unauthorised or unqualified personnel
Work on live parts or circuits without switching off the Junction Box with Electronic Thermostat Module PBTC or the system
Commissioning of damaged or faulty system components or incomplete installation
Unauthorized technical modification of the Junction Box with Electronic Thermostat Module PBTC or its components
1
For maximum surface temperature, see heating system design documentation