Typ 07-351*-**************

3

Safety Instructions  

The ComEx control and indicating devices may be used only 
within the specified temperature range. Unprotected, incorrect 
installation can cause malfunctioning and the loss of explosion 
proofness. Utilization in areas other than those specified or 
the alteration of the product by anyone other than the manu-
facturer will exempt BARTEC from liability for defects or any 
further liability. When setting up or operating explosion resistant 
electrical systems, the IEC/EN 60079-14 (NEC for USA/CEC for 
Canada) and all relevant installation and operating regulations 
must be observed. The generally applicable statutory rules and 
other binding directives relating to workplace safety, accident 
prevention and environmental protection must be observed. 
The ComEx control and indicating device may be used only if it 
is in a clean and undamaged condition. It is not permissible to 
modify the ComEx control and indicating devices in any way. If 
limited components are used within the device e.g. cable glands 
the information of correct usage can be found on shipping 
documents and related certificates of the component. For 
intrinsically safety devices an appropriate barrier has to be used. 
The electrical limits that are decisive for “intrinsic safety” (see 
accompanying documents) must be adhered to.

Marking

Particularly important points in these instructions are marked 
with a symbol:

DANGER 

indicates a hazardous situation which, if not avoided, 

will result in death or serious injury.

WARNING

 

indicates a hazardous situation which, if not 

avoided, could result in death or serious injury.

CAUTION 

indicates a hazardous situation which, if not avoided, 

could result in minor or moderate injury. 

NOTICE

 is used to address practices not related to personal 

injury.

NOTE 

 Important instructions and information on effective, 

economical and environmentally compatible handling.

Standards conformed to  

See EU Declaration of Conformity 01-3510-7C0001_C

Assembly, Installation,  
and Commissioning  

WARNING

 

Risk of injury due to incorrect proceedings.

•  Only authorized and qualified personnel who are authorized 

and trained to assemble electric components in hazardous 
(potentially explosive) areas may do any of the assembly, 
disassembly, installation and commissioning work.

•  Use suitable tools.

Assembly/disassembly

Make sure the ComEx control and indicating device to be fitted is 
intact (no damage, no cracks).

Installation

NOTE 

 The connection has to be made in accordance with the 

valid operational instructions of the installation devices.
The valid operational instructions are available under:  
www.bartec.com or could be ordered directly from  
BARTEC GmbH.

Cables must be connected carefully, i.e:

 

– The insulation must extend up to the terminal.

 

– Take care not to damage the conductor.

 

– All screws on the connection terminals,  including unused 

ones, must be tightened securely.

 

– All unused cable entries must be sealed are with a certified 

stopper.

 

– It is essential to observe the necessary minimum protection 

level IP54 for protection against gas explosions and IP6x for 
protection against dust explosions. (The ComEx control and 
indicating devices are supplied with a minimum protection 
class of IP6x.)

 

– All cores must be connected to terminals

 

– approved under IEC/EN 60079-7

Commissioning

Before commissioning check that:

 

– The ComEx control and indicating device has been installed in 

compliance with regulations.

 

– The ComEx control and indicating device is not damaged.

 

– The junction box is clean.

 

– The connection has been established properly.

 

– The cable has been laid in an orderly fashion.

 

– All screws are tightened securely

NOTE 

 The spare parts, actuators, switching modules, and 

luminous modules are specified in the data sheet.

01-3511-7D0002-A-05/2020-ESS-409352