Electrical connections
Ex p Control unit
APEX
mv
Page 38 of 80
01-37A2-7D0005_MV_Manual_Exp-Control-Unit_2021005_0_en.docx
Rev. 0
For the bypass switch to be detected and the
function to be executed, a resistor with 620
Ω
must be connected to the closing contact.
The temperature sensor can be a PT 100 or
1000. Settings for the sensor are made in the
device. Two or three wire sensors can be
used.
Terminal
Connection
Function
1
Bypass IN
Contact for the bypass switch
2
Bypass OUT
Contact for the bypass switch
3
T-Sensor 1 IN
Temperature sensor connection
4
T Sensor 1 OUT
Temperature sensor connection
5
T Sensor 1 MESS
Temperature sensor connection
6.2.2.2
Terminal row “X14”
As an additional enable, an enable switch can be connected after the control unit
APEX has given the enable.
This function gives the enable when the control unit is enabled and the main
switch is activated.
The main switch does not require a
combination of resistors.
The temperature sensor can be a PT 100 or
1000. Settings for the sensor are made in the
device. Two or three wire sensors can be
used.
Terminal
Connection
Function
1
Main switch IN
Contact for the main switch
2
Main switch OUT
Contact for the main switch
3
T sensor 2 IN
Temperature sensor connection
4
T sensor 2 OUT
Temperature sensor connection
5
T sensor 2 MESS
Temperature sensor connection