Figure 3 Status Indicators
The indicators are grouped into 5 sections.
1. ALARM GROUP
(6, one for each group)
If the group is disabled:
Off
If the group is enabled:
No alarms in the group
Green
Group alarms are unacknowledged
Flashing Red
Group alarms are acknowledged
Solid Red
Group alarms are being reported
Flashing Yellow
2. ALARM
(12, ten hardware inputs, one power supply monitor & one system alarm)
If the input is disabled:
Off
If the input is enabled:
Configured as an alarm input
(digital, analog, watchdog)
Idle, no alarm
Off
Alarm is unacknowledged
Flashing Red
Alarm is acknowledged
Solid Red
Watchdog Reset Activity
Blink Green
Not Configured as an alarm input
(accumulator, totalizer, interval timer or
special purpose)
Idle
Off
Accumulator or Interval timer
Solid Green
while active
Totalizer
Blink Green
Special purpose - acknowledge
Solid Green
for 500 msec after each operation
Special purpose – shift 1 or 2
Shift 1
Solid Green
Shift 2
Flashing Green
Special purpose – advance shift
Blink Green