Drive Fault Messages and Trip Codes
See
drive
User Guide for further information.
Further Status Messages and Troubleshooting
T3-OPPAD
uses various display messages to indicate different working status. See the following table for more information.
Status Messages
Message
Explanation
Scanning for Drive
xx
The
T3-OPPAD
is searching for the drive with address ‘xx’ in the network.
Load…
The
T3-OPPAD
has found the drive in the network and is loading the initialisation information from
the drive.
SC-OBS
The communication link between the
drive
and
T3-OPPAD
has failed.
Select Language
Displayed in the language selection screen, with a list of available languages. Press the Navigate
key to select a language
Select drive address
xx
Displayed when selecting the address of the
drive
that the
T3-OPPAD
should try to communicate
with. Press the Stop key to select the drive address.
Select
T3-OPPAD
ID
Displayed when selecting the
T3-OPPAD
ID (1 or 2) so that two
T3-OPPADs
can be
connected to a single drive, or network of multiple drives.
Troubleshooting
Symptom
Explanation
Select drive address
xx
displayed after
‘SCAN..’ message
The
T3-OPPAD
failed to successfully communicate with the specified drive address in the network.
Check that the RJ45 data cable connection is correct. Check that the drive with address XX is
available in the network.
If XX > 1 and only one
T3-OPPAD
is connected, then check the
T3-OPPAD
device number, make
sure the number is 1.
Display ‘Err-id’ on
power up
This normally occurs when there are two
T3-OPPAD
units in the same drive network and both of
them have the same device number. Check and change the device number of one
T3-OPPAD
.
Display ‘Err-id’ during
normal operation
This normally occurs when the user plugs a second
T3-OPPAD
into the drive network. Change
the device number of one of the
T3-OPPAD
units.
Display
‘SC-OBS’
Communication link between the
T3-OPPAD
and
drive
has failed during operation.
Check the electrical connection, and make sure the cable is connected correctly between the
T3-
OPPAD
and the drive. Press ‘STOP’ button to enable the
T3-OPPAD
to search for the drive again.