Drive Fault Messages and Trip Codes

See 

drive

 User Guide for further information.

Further Status Messages and Troubleshooting

T3-OPPAD

 uses various display messages to indicate different working status. See the following table for more information.

Status Messages

Message

Explanation

Scanning for Drive

xx

The 

T3-OPPAD

 is searching for the drive with address ‘xx’ in the network.

Load…

The 

T3-OPPAD

 has found the drive in the network and is loading the initialisation information from 

the drive. 

SC-OBS

The communication link between the 

drive

 and 

T3-OPPAD

 has failed.

Select Language

Displayed in the language selection screen, with a list of available languages. Press the Navigate 
key to select a language

Select drive address

xx

Displayed when selecting the address of the 

drive

 that the 

T3-OPPAD

 should try to communicate 

with. Press the Stop key to select the drive address.

Select 

T3-OPPAD

 ID

Displayed when selecting the 

T3-OPPAD

 ID (1 or 2) so that two 

T3-OPPADs

 can be 

connected to a single drive, or network of multiple drives.

Troubleshooting

Symptom

Explanation

Select drive address

xx

displayed after 

‘SCAN..’ message

The 

T3-OPPAD

 failed to successfully communicate with the specified drive address in the network.

Check that the RJ45 data cable connection is correct. Check that the drive with address XX is 
available in the network.
If XX > 1 and only one 

T3-OPPAD

 is connected, then check the 

T3-OPPAD

 device number, make 

sure the number is 1.

Display ‘Err-id’ on 

power up

This normally occurs when there are two 

T3-OPPAD

 units in the same drive network and both of 

them have the same device number. Check and change the device number of one 

T3-OPPAD

.

Display ‘Err-id’ during 

normal operation

This normally occurs when the user plugs a second 

T3-OPPAD

 into the drive network. Change 

the device number of one of the 

T3-OPPAD

 units.

Display 

‘SC-OBS’

Communication link between the 

T3-OPPAD

 and 

drive

 has failed during operation.

Check the electrical connection, and make sure the cable is connected correctly between the 

T3-

OPPAD

 and the drive. Press ‘STOP’ button to enable the 

T3-OPPAD

 to search for the drive again.

Содержание T3-OPPAD

Страница 1: ...Installation Operating Instructions User Guide T3 OPPAD TFT Remote Keypad IP55...

Страница 2: ...standard 2 wire 5V differential Operational 10 50 C Storage 40 C 60 C 95 non condensing IP55 25m 82 5ft shielded twisted pair Mechanical Installation Dimensions 1 10mm 100mm 90mm 80mm Through Panel M...

Страница 3: ...Operating Information Provides a real time display of key operating information e g output current and power Quick Help Button Provides access to short description of the displayed messages Function B...

Страница 4: ...PPAD is used on networks with multiple drives the user can change the drive address to set up communication with another drive in the same drive network at anytime Select Drive Address xx Select Drive...

Страница 5: ...9kW 23 7Hz 23 7Hz 15 3A 23 7Hz 15 3A Drive Inhibited The STO connections are not made Drive Stopped Disabled Drive is enabled running display shows the output frequency Hz Press the Navigate key to se...

Страница 6: ...equired parameter Display will show the present parameter value on the lower line of the display Press the Navigate key for 1 second Adjust the value using the Up and Down keys Display will show the m...

Страница 7: ...ting the T3 OPPAD ID 1 or 2 so that two T3 OPPADs can be connected to a single drive or network of multiple drives Troubleshooting Symptom Explanation Select drive address xx displayed after SCAN mess...

Страница 8: ...82 OPTFT IN_V2 00 82 OPTFT IN_V2 00 Bardac Drives 40 Log Canoe Circle Stevensville MD 21666 410 604 3400 888 667 7333 bardac com driveweb com automationthings com...

Отзывы: