IMPORTANT INSTALLER NOTE

For improved start-up performance, wash the indoor coil
with a dishwasher detergent.

HIGH PRESSURE SWITCH

The WL372 models are supplied with a remote reset
high pressure switch.  If tripped, this pressure switch
may be reset by turning the thermostat off then back on
again.

THREE PHASE SCROLL COMPRESSOR
START UP INFORMATION

Scroll compressors, like several other types of
compressors, will only compress in one rotational
direction.  Direction of rotation is not an issue with
single phase compressors since they will always start
and run in the proper direction.

However, three phase compressors will rotate in either
direction depending upon phasing of the power.  Since
there is a 50-50 chance of connecting power in such a
way as to cause rotation in the reverse direction,
verification of proper rotation must be made.  All three
phase units incorporate a phase monitor to ensure proper
field wiring.  See the 

Phase Monitor

 section in this

manual.

Verification of 

proper rotation

 must be made any time a

compressor is change or rewired.  If improper rotation is
corrected at this time there will be no negative impact on
the durability of the compressor.  However, reverse
operation for over one hour may have a negative impact
on the bearing due to oil pump out.

NOTE: If compressor is allowed to run in reverse

rotation for several minutes, the compressor's
internal protector will trip.

All three phase ZR3 compressors are wired identical
internally.  As a result, once the correct phasing is
determined for a specific system or installation,
connecting properly phased power leads to the same
Fusite terminal should maintain proper rotation
direction.

Verification of proper rotation direction is made by
observing that suction pressure drops and discharge
pressure rises when the compressor is energized.
Reverse rotation also results in an elevated sound level
over that with correct rotations, as well as, substantially
reduced current draw compared to tabulated values.

The direction of rotation of the compressor may be
changed by reversing any two line connections to the
unit.

START UP

PHASE MONITOR

All units with three phase compressors are equipped
with a 3 phase line monitor to prevent compressor
damage due to phase reversal.

The phase monitor in this unit is equipped with two
LEDs.  If the Y signal is present at the phase monitor
and phases are correct the green LED will light.

If phases are reversed, the red fault LED will be lit and
compressor operation is inhibited.

If a fault condition occurs, reverse two of the supply
leads to the unit.  Do not reverse any of the unit factory
wires as damage may occur.

SERVICE HINTS

1. Caution homeowner to maintain clean air filters at all

times.  Also, not to needlessly close off supply and
return air registers.  This reduces air flow through the
system, which shortens equipment service life as well
as increasing operating costs.

2. Switching to heating cycle at 75°F or higher outside

temperature may cause a nuisance trip of the remote
reset high pressure switch.  Turn thermostat off, then
on to reset the high pressure switch.

3. The heat pump wall thermostats perform multiple

functions.  Be sure that all function switches are
correctly set for the desired operating mode before
trying to diagnose any reported service problems.

4. Check all power fuses or circuit breakers to be sure

they are the correct rating.

5. Periodic cleaning of the outdoor coil to permit full

and unrestricted airflow circulation is essential.

SEQUENCE OF OPERATION

Cooling—Circuit R-Y makes at thermostat pulling in
compressor contactor, starting the compressor and
outdoor motor.  The G (indoor motor) circuit is
automatically completed on any call for cooling
operation or can be energized by manual fan switch on
subbase for constant air circulation.  On all 230 volt
units there is a one minute off delay on the blower
motor.  460 volt models do not have an off delay.  On a
call for heating, circuit R-W1 make at the thermostat
pulling in heat contact for the strip heat and blower
operation.  On a call for second stage heat, R-W2 makes
bringing on second heat contactor, if so equipped.

Содержание WL372

Страница 1: ...o 2100 405A Supersedes 2100 405 File Volume III Tab 16 Date 07 25 06 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Model WL302 WL372 WALL MOUNTED PACKAGED AIR...

Страница 2: ...SP 17 Table 11 Maximum ESP of Operation Electric Heat Only 17 Table 12 Cooling Pressure 18 Table 13 Optional Accessories 18 Getting Other Information and Publications For more information contact thes...

Страница 3: ...er and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Страница 4: ...uctors are in a raceway TABLE 1 ELECTRICAL SPECIFICATIONS s l e d o M d e t a R s t l o V s e s a h P o N d l e i F r e w o P s t i u c r i C 3 m u m i n i M t i u c r i C y t i c a p m A 1 m u m i x...

Страница 5: ...i W W h t p e D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q R S T A B C B 2 0 3 L W 1 7 3 L W 0 2 8 3 5 2 1 7 1 3 6 5 0 7 8 8 7 8 8 7 2 8 8 3 1 8 8 7 2 0 0 0 4 0 5 8 1 5 7 5 2 3 9...

Страница 6: ...National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type NFPA No 90A and Residence Type Warm Air Heating and Air Conditioning...

Страница 7: ...tructions and Figures 3 4 and 5 for further details Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity Any grille that meets t...

Страница 8: ...bustible wall 9 On side by side installations maintain a minimum of 20 inches clearance on left side to allow access to heat strips and control panel and to allow proper airflow to the outdoor coil Ad...

Страница 9: ...OPERATING VOLTAGE RANGE P A T E G N A R V 0 4 2 6 1 2 3 5 2 V 8 0 2 7 8 1 0 2 2 r e m r o f s n a r T A V A L F e g u a G e r i W m u m i x a M e c n a t s i D t e e F n I 5 5 3 2 e g u a g 0 2 e g u...

Страница 10: ...Manual 2100 405A Page 10 of 18 FIGURE 3 MOUNTING INSTRUCTIONS...

Страница 11: ...ual 2100 405A Page 11 of 18 FIGURE 4 WALL MOUNTING INSTRUCTIONS FIGURE 5 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS FOR OPENING SIZES SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSI...

Страница 12: ...Manual 2100 405A Page 12 of 18 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...

Страница 13: ...ustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheatin...

Страница 14: ...Manual 2100 405A Page 14 of 18 FIGURE 8 LOW VOLTAGE WIRING...

Страница 15: ...urrent draw compared to tabulated values The direction of rotation of the compressor may be changed by reversing any two line connections to the unit START UP PHASE MONITOR All units with three phase...

Страница 16: ...CONTROL MODULE The compressor control module is optional on the models covered by this manual The compressor control is an anti short cycle lockout timer with high and low pressure switch monitoring a...

Страница 17: ...hes from compressor as shown in the following table A AIRFLOW TABLE 8 SUCTION LINE TEMPERATURES s l e d o M d e t a R w o l f r i A F 5 9 p m e T D O F 2 8 p m e T D O 2 0 3 L W 0 0 0 1 9 5 6 5 6 6 4...

Страница 18: ...3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 3 8 8 2 2 4 8 3 4 2 6 8 9 5 2 8 8 4 7 2 9 8 2 9 2 0 9 9 0 3 2 9 7 2 3 3 9 7 4 3 4 9 6 6 3 2 7 3 L W B D g e d 5 7 B W g e d 2 6 e d i S w o...

Отзывы: