Manual 2100-376L
Page
26 of 81
19. MANIFOLD PRESSURE
ADJUSTMENT
You will need a 0 to 15 inch water manometer with 0.1
inch resolution and a 1/8" NPT manual shut off valve to
measure actual manifold pressure.
Depending on your local gas heating value and
elevation, you may need to adjust manifold pressure or
change orifices to get proper gas input rate. Check
with your local gas supplier to determine heating value
(BTU/cu. ft.) of natural gas in your area.
NOTE: If furnace is being installed at an altitude of
more than 6,000 feet above sea level, you
must derate the furnace. See Section 21
“Standard Orifice Sizing and High Altitude
Derate”.
20. CHECKING GAS INPUT RATE
It is the installer's responsibility to see that the BTU
input rate of the furnace is properly adjusted. Under-
firing could cause inadequate heat, excessive
condensation or ignition problems. Overfiring could
cause sooting, flame impingement or overheating of
heat exchanger.
1. Turn off gas at equipment shut off valve in gas
supply line just ahead of furnace.
2. Remove plug from outlet pressure tap in gas control
or gas manifold.
3. Install 1/8" NPT manual shut off valve in hole
vacated by plug. Make sure shut off valve is in off
position.
4. Attach manometer to 1/8" NPT manual shut off
valve just installed.
PROPANE (LP) GAS CONVERSION
This unit may be converted in the field for
use with Propane (LP) gas. Propane gas
conversion kit number WGCK-1 is designed
for conversions of units installed from
0 – 6,000 feet elevations. Propane gas
conversion kit number WGCK-2 is designed
for conversions of units installed from 6,001
– 10,000 feet elevations. These kits may
be purchased from your local distributor.
5. Slowly open equipment shut off valve in gas supply
line just ahead of furnace. Start furnace following
“Operating Instructions” on front door.
6. Slowly open 1/8" NPT manual shut off valve leading
to manometer.
7. Read manifold pressure on manometer.
8. Adjust manifold pressure by turning gas control
regulator adjusting screw clockwise to increase
pressure or turning counterclockwise to decrease
pressure. Manifold pressure must be within
allowable range as follows:
•
Natural gas manifold pressure must be between
3.2 and 3.8 inches W.C. Rated pressure is 3.5
inches.
•
Propane gas (LP) manifold pressure must be
between 9.7 and 10.3 inches W.C. Rated
pressure is 10 inches.
NOTE: For natural gas, if gas flow rate can't be
properly set within these pressure ranges
then you must change main burner orifices to
obtain proper gas flow rate.
9. Shut off furnace. Turn off gas at equipment shut off
valve in gas supply line just ahead of furnace. Install
outlet pressure tap plug in gas control. Turn on gas.
10. Check regulator adjustment cover screw and gas
control plug for gas leaks. Use a commercial soap
solution made for leak detection.
WARNING
When converting from propane (LP) gas to
natural gas, the gas orifice spuds and gas
valve spring must be replaced and the gas
valve regulator pressure must be adjusted
correctly. Failure to do so can result in fire,
injury or death. Refer to Tables 8 and 8A for
proper orifice sizing.
Natural gas spring kit, Part number 5603-007,
can be purchased through your local
distributor.
WARNING
Correct manifold pressure is necessary for
proper ignition and burner operation. Failure
to accurately adjust pressure could cause
heat exchanger failure.
WARNING
Failure to adjust furnace to the proper firing
rate could cause heat exchanger failure.
Содержание WG242DA
Страница 13: ...Manual 2100 376L Page 13 of 81 FIGURE 2A MOUNTING INSTRUCTIONS FOR WG42 WG48 AND WG60...
Страница 15: ...Manual 2100 376L Page 15 of 81 FIGURE 4 WALL MOUNTING INSTRUCTIONS FIGURE 5 WALL MOUNTING INSTRUCTIONS...
Страница 16: ...Manual 2100 376L Page 16 of 81 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...
Страница 22: ...Manual 2100 376L Page 22 of 81 FIGURE 11 LOW VOLTAGE WIRING...
Страница 23: ...Manual 2100 376L Page 23 of 81 FIGURE 11A LOW VOLTAGE WIRING...
Страница 24: ...Manual 2100 376L Page 24 of 81 FIGURE 12 GAS PIPE CONNECTION...
Страница 34: ...Manual 2100 376L Page 34 of 81 26 LIGHTING AND SHUTDOWN INSTRUCTIONS FIGURE 15 INSTRUCTION LABEL...
Страница 56: ...Manual 2100 376L Page 56 of 81 WG242DA 230 208 60 1...
Страница 57: ...Manual 2100 376L Page 57 of 81 WG242DA WG362DA 230 208 60 1...
Страница 58: ...Manual 2100 376L Page 58 of 81 WG242DB 230 208 60 3...
Страница 59: ...Manual 2100 376L Page 59 of 81 WG242DB WG362DB 230 208 60 3...
Страница 60: ...Manual 2100 376L Page 60 of 81 WG243DC 460 60 3...
Страница 61: ...Manual 2100 376L Page 61 of 81 WG243DC 460 60 3...
Страница 62: ...Manual 2100 376L Page 62 of 81 WG302DA 230 208 60 1...
Страница 63: ...Manual 2100 376L Page 63 of 81 WG302DA WG482DA WG602DA 230 208 60 1...
Страница 64: ...Manual 2100 376L Page 64 of 81 WG302DB 230 208 60 3...
Страница 65: ...Manual 2100 376L Page 65 of 81 WG302DB WG482DB WG602DB 230 208 60 3...
Страница 66: ...Manual 2100 376L Page 66 of 81 WG303DC 460 60 3...
Страница 67: ...Manual 2100 376L Page 67 of 81 WG303DC 460 60 3...
Страница 68: ...Manual 2100 376L Page 68 of 81 WG362DA 230 208 60 1...
Страница 69: ...Manual 2100 376L Page 69 of 81 WG362DB 230 208 60 3...
Страница 70: ...Manual 2100 376L Page 70 of 81 WG363DC 460 60 3...
Страница 71: ...Manual 2100 376L Page 71 of 81 WG363DC 460 60 3...
Страница 72: ...Manual 2100 376L Page 72 of 81 WG423DA 230 208 60 1...
Страница 73: ...Manual 2100 376L Page 73 of 81 WG423DA 230 208 60 1...
Страница 74: ...Manual 2100 376L Page 74 of 81 WG423DB 230 208 60 3...
Страница 75: ...Manual 2100 376L Page 75 of 81 WG423DB 230 208 60 3...
Страница 76: ...Manual 2100 376L Page 76 of 81 WG424DC 460 60 3...
Страница 77: ...Manual 2100 376L Page 77 of 81 WG424DC 460 60 3...
Страница 78: ...Manual 2100 376L Page 78 of 81 WG482DA WG602DA 230 208 60 1...
Страница 79: ...Manual 2100 376L Page 79 of 81 WG482DB WG602DB 230 208 60 3...
Страница 80: ...Manual 2100 376L Page 80 of 81 WG483DC WG603DC 460 60 3...
Страница 81: ...Manual 2100 376L Page 81 of 81 WG483DC WG603DC 460 60 3...