Manual
2100-376
I
Page
19 of 80
12. VENT RESIZING INSTRUCTIONS
When an existing furnace is removed from a venting
system servicing other appliances, the venting system is
likely to be too large to properly vent the remaining
attached appliances.
The following steps shall be followed with each of the
appliances remaining connected to the common venting
system, placed in operation one at a time while the
other appliances remaining connected to the common
venting system are not in operation.
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and
horizontal pitch, as required in the National Fuel Gas
code, ANSI Z223.1 or the CAN/CGA B149
Installation Codes and these instructions. Determine
that there is no blockage or restriction, leakage,
corrosion and other deficiencies which could cause
an unsafe condition.
3. In so far as is practical, close all building doors and
windows and all doors between the space in which
the appliance(s) connected to the venting system are
located and other spaces of the building. Turn on
clothes dryers and any appliances not connected to
the venting system. Turn on any exhaust fans, such
as range hoods and bathroom exhausts, so they will
operate at maximum speed. Do not operate a
summer exhaust fan. Close fireplace dampers.
4. Follow the lighting instructions. Place the appliance
being inspected in operation. Adjust thermostat so
appliance shall operate continuously.
5. Test for draft hood equipped appliance spillage at the
draft hood relief opening after 5 minutes of main
burner operation. Use the flame of a match or
candle.
6. After it has been determined that each appliance
connected to the venting system properly vents when
tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other gas-
burning appliances to their previous conditions of
use.
7. If improper venting is observed during any of the
above tests, the venting system must be corrected.
13. FRESH AIR INTAKE
All units are built with fresh air inlet slots punched in
the service panel.
If the unit is equipped with a fresh air damper
assembly, the assembly is shipped already attached to
the unit. The damper blade is locked in the closed
position. To allow the damper to operate, the
maximum and minimum blade position stops must be
installed. See Figure 9.
All capacity, efficiency and cost of operation
information as required for Department of Energy
“Energyguide” Fact Sheets is based upon the fresh air
blank-off plate in place and is recommended for
maximum energy efficiency.
The blank-off plate is available upon request from the
factory and is installed in place of the fresh air damper
shipped with each unit.
One of several other ventilation options may be
installed. Refer to model number and/or supplemental
installation instructions.
14. CONDENSATE DRAIN
A plastic drain hose extends from the drain pan at the
top of the unit down to the unit base. There are
openings in the unit base for the drain hose to pass
through. In the event the drain hose is connected to a
drain system of some type, it must be an open or vented
type system to assure proper drainage.
FIGURE 9
FRESH AIR DAMPER
MIS-938
Содержание WG242D
Страница 13: ...Manual 2100 376I Page 13 of 80 FIGURE 2A MOUNTING INSTRUCTIONS FOR WG42 WG48 AND WG60...
Страница 15: ...Manual 2100 376I Page 15 of 80 FIGURE 4 WALL MOUNTING INSTRUCTIONS FIGURE 5 WALL MOUNTING INSTRUCTIONS...
Страница 16: ...Manual 2100 376I Page 16 of 80 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...
Страница 22: ...Manual 2100 376I Page 22 of 80 FIGURE 11 LOW VOLTAGE WIRING...
Страница 23: ...Manual 2100 376I Page 23 of 80 FIGURE 11A LOW VOLTAGE WIRING...
Страница 24: ...Manual 2100 376I Page 24 of 80 FIGURE 12 GAS PIPE CONNECTION...
Страница 34: ...Manual 2100 376I Page 34 of 80 26 LIGHTING AND SHUTDOWN INSTRUCTIONS FIGURE 15 INSTRUCTION LABEL...
Страница 40: ...Manual 2100 376I Page 40 of 80 FIGURE 19 460 VOLT BLOWER MOTOR WIRING OPTIONS WG24 WG30 AND WG36 MODELS...
Страница 41: ...Manual 2100 376I Page 41 of 80 FIGURE 20 460 VOLT BLOWER MOTOR WIRING OPTIONS WG42 WG48 AND WG 60 MODELS...
Страница 56: ...Manual 2100 376I Page 56 of 80 WG242DA 230 208 60 1...
Страница 57: ...Manual 2100 376I Page 57 of 80 WG242DA WG362DA 230 208 60 1...
Страница 58: ...Manual 2100 376I Page 58 of 80 WG242DB 230 208 60 3...
Страница 59: ...Manual 2100 376I Page 59 of 80 WG242DB WG362DB 230 208 60 3...
Страница 60: ...Manual 2100 376I Page 60 of 80 WG242DC 460 60 3...
Страница 61: ...Manual 2100 376I Page 61 of 80 WG242DC WG362DC 460 60 3...
Страница 62: ...Manual 2100 376I Page 62 of 80 WG302DA 230 208 60 1...
Страница 63: ...Manual 2100 376I Page 63 of 80 WG302DA WG482DA WG602DA 230 208 60 1...
Страница 64: ...Manual 2100 376I Page 64 of 80 WG302DB 230 208 60 3...
Страница 65: ...Manual 2100 376I Page 65 of 80 WG302DB WG482DB WG602DB 230 208 60 3...
Страница 66: ...Manual 2100 376I Page 66 of 80 WG302DC 460 60 3...
Страница 67: ...Manual 2100 376I Page 67 of 80 WG302DC 460 60 3...
Страница 68: ...Manual 2100 376I Page 68 of 80 WG362DA 230 208 60 1...
Страница 69: ...Manual 2100 376I Page 69 of 80 WG362DB 230 208 60 3...
Страница 70: ...Manual 2100 376I Page 70 of 80 WG362DC 460 60 3...
Страница 71: ...Manual 2100 376I Page 71 of 80 WG423DA 230 208 60 1...
Страница 72: ...Manual 2100 376I Page 72 of 80 WG423DA 230 208 60 1...
Страница 73: ...Manual 2100 376I Page 73 of 80 WG423DB 230 208 60 3...
Страница 74: ...Manual 2100 376I Page 74 of 80 WG423DB 230 208 60 3...
Страница 75: ...Manual 2100 376I Page 75 of 80 WG423DC 460 60 3...
Страница 76: ...Manual 2100 376I Page 76 of 80 WG423DC 460 60 3...
Страница 77: ...Manual 2100 376I Page 77 of 80 WG482DA WG602DA 230 208 60 1...
Страница 78: ...Manual 2100 376I Page 78 of 80 WG482DB WG602DB 230 208 60 3...
Страница 79: ...Manual 2100 376I Page 79 of 80 WG482DC WG602DC 460 60 3...
Страница 80: ...Manual 2100 376I Page 80 of 80 WG482DC WG602DC 460 60 3...