23. MEASURING AIR TEMPERATURE
RISE
Air temperature rise (supply air temperature minus
return air temperature) must be within allowable air
temperature rise range specified on furnace rating plate
and in Table 1.
You will need 2 thermometers with 1 degree resolution
capable of reading up to 200 degrees F. Check
thermometers to make sure they agree, or compensate
accordingly.
Follow this procedure:
1. Open supply air registers and return air grilles.
Make sure the registers and grilles are free of
obstruction from rugs, carpets, drapes or furniture.
22. CONVERSION OF GAS INPUT BTUH
FROM HIGH TO LOW RATING
All the derated WG series units are produced with
maximum BTUH input orifices installed. To field
convert input, a change to main burner orifices is
required.
NOTE:
No change to air orifices is necessary. A set
of low input orifices is shipped with every
unit. They will be found packaged in a bag
behind the burner door. Refer to the unit
rating plate to confirm the proper orifice size.
Proper installation of the orifices is detailed
as follows:
A. Shut off electrical supply to the unit.
B. Shut off gas supply to the unit.
C. Remove burner access panel.
D. Disconnect gas valve from gas supply piping.
E. Disconnect the two wires from the gas valve.
F. Remove the manifold assembly so that orifices are
now accessible and remove orifices.
G. Apply a modest amount of pipe compound to the
new orifices and screw them into the manifold.
H. To assemble burner reverse steps A through G.
2. Set balancing dampers in supply duct system.
3. Check duct work for obstructions or leaks.
4. Make sure filters are clean and in place.
5. Place one thermometer in supply air plenum
approximately 2 feet from furnace. Locate
thermometer tip in center of plenum to ensure proper
temperature measurement.
6. Place second thermometer in return air duct
approximately 2 feet from furnace. Locate
thermometer tip in center of duct to ensure proper
temperature measurement.
7. Set room thermostat on highest temperature setting.
Operate furnace 10 minutes. Record supply air and
return air temperatures.
8. Calculate air temperature rise by subtracting return
air temperature from supply air temperature.
•
If air temperature rise is above the temperature
rise range on rating plate, furnace is overfired
or has insufficient airflow. Check gas input
following the instructions in Section, “Checking
Gas Input Rate”. If air temperature rise is still
above temperature rise range specified, more
heating air flow is needed. Check duct work and
grilles to make sure all are properly sized.
•
If air temperature rise is below the temperature
rise range on rating plate, furnace is underfired
or has too much airflow. Check gas input
following the instructions in Section, “Checking
Gas Input Rate”. If air temperature rise is still
below temperature rise range specified, less
heating air flow is needed. Adjust dampers or
grilles as needed.
•
After making adjustments, you must check air
temperature rise to verify that resulting air
temperature rise is within allowable range. If
air temperature rise is still outside the
temperature rise range specified on rating
plate, check duct system design with a
qualified heating engineer. It may be
necessary to re-size the duct work. Recheck
air temperature rise after revising duct systems.
9. Set room thermostat to desired setting.
10. Remove thermometers and seal duct work holes.
NOTE: Failure to seal holes could result in reduced
system performance.
WARNING
Failure to follow these instructions could
create a hazard resulting in property damage,
bodily injury, or death.
Содержание WG242D
Страница 13: ...Manual 2100 376I Page 13 of 80 FIGURE 2A MOUNTING INSTRUCTIONS FOR WG42 WG48 AND WG60...
Страница 15: ...Manual 2100 376I Page 15 of 80 FIGURE 4 WALL MOUNTING INSTRUCTIONS FIGURE 5 WALL MOUNTING INSTRUCTIONS...
Страница 16: ...Manual 2100 376I Page 16 of 80 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...
Страница 22: ...Manual 2100 376I Page 22 of 80 FIGURE 11 LOW VOLTAGE WIRING...
Страница 23: ...Manual 2100 376I Page 23 of 80 FIGURE 11A LOW VOLTAGE WIRING...
Страница 24: ...Manual 2100 376I Page 24 of 80 FIGURE 12 GAS PIPE CONNECTION...
Страница 34: ...Manual 2100 376I Page 34 of 80 26 LIGHTING AND SHUTDOWN INSTRUCTIONS FIGURE 15 INSTRUCTION LABEL...
Страница 40: ...Manual 2100 376I Page 40 of 80 FIGURE 19 460 VOLT BLOWER MOTOR WIRING OPTIONS WG24 WG30 AND WG36 MODELS...
Страница 41: ...Manual 2100 376I Page 41 of 80 FIGURE 20 460 VOLT BLOWER MOTOR WIRING OPTIONS WG42 WG48 AND WG 60 MODELS...
Страница 56: ...Manual 2100 376I Page 56 of 80 WG242DA 230 208 60 1...
Страница 57: ...Manual 2100 376I Page 57 of 80 WG242DA WG362DA 230 208 60 1...
Страница 58: ...Manual 2100 376I Page 58 of 80 WG242DB 230 208 60 3...
Страница 59: ...Manual 2100 376I Page 59 of 80 WG242DB WG362DB 230 208 60 3...
Страница 60: ...Manual 2100 376I Page 60 of 80 WG242DC 460 60 3...
Страница 61: ...Manual 2100 376I Page 61 of 80 WG242DC WG362DC 460 60 3...
Страница 62: ...Manual 2100 376I Page 62 of 80 WG302DA 230 208 60 1...
Страница 63: ...Manual 2100 376I Page 63 of 80 WG302DA WG482DA WG602DA 230 208 60 1...
Страница 64: ...Manual 2100 376I Page 64 of 80 WG302DB 230 208 60 3...
Страница 65: ...Manual 2100 376I Page 65 of 80 WG302DB WG482DB WG602DB 230 208 60 3...
Страница 66: ...Manual 2100 376I Page 66 of 80 WG302DC 460 60 3...
Страница 67: ...Manual 2100 376I Page 67 of 80 WG302DC 460 60 3...
Страница 68: ...Manual 2100 376I Page 68 of 80 WG362DA 230 208 60 1...
Страница 69: ...Manual 2100 376I Page 69 of 80 WG362DB 230 208 60 3...
Страница 70: ...Manual 2100 376I Page 70 of 80 WG362DC 460 60 3...
Страница 71: ...Manual 2100 376I Page 71 of 80 WG423DA 230 208 60 1...
Страница 72: ...Manual 2100 376I Page 72 of 80 WG423DA 230 208 60 1...
Страница 73: ...Manual 2100 376I Page 73 of 80 WG423DB 230 208 60 3...
Страница 74: ...Manual 2100 376I Page 74 of 80 WG423DB 230 208 60 3...
Страница 75: ...Manual 2100 376I Page 75 of 80 WG423DC 460 60 3...
Страница 76: ...Manual 2100 376I Page 76 of 80 WG423DC 460 60 3...
Страница 77: ...Manual 2100 376I Page 77 of 80 WG482DA WG602DA 230 208 60 1...
Страница 78: ...Manual 2100 376I Page 78 of 80 WG482DB WG602DB 230 208 60 3...
Страница 79: ...Manual 2100 376I Page 79 of 80 WG482DC WG602DC 460 60 3...
Страница 80: ...Manual 2100 376I Page 80 of 80 WG482DC WG602DC 460 60 3...