Manual 2100-376
I
Page
10 of 80
See Figure 3 and clearance information in Section 9
and Table 2 for additional information.
Design the duct work according to methods given by
the Air Conditioning Contractors of America (ACCA).
When duct runs through unheated spaces, it should be
insulated with a minimum of one inch of insulation.
Use insulation with a vapor barrier on the outside of
the insulation. Flexible joints should be used to
connect the duct work to the equipment in order to
keep the noise transmission to a minimum.
A one inch clearance to combustible material for the
first three feet of duct attached to the outlet air frame is
required. See Wall Mounting Instructions and Figures
2, 2A and 3 for further details.
Ducts through the walls must be insulated and all joints
taped or sealed to prevent air or moisture entering the
wall cavity.
Some installations may not require any return air duct.
A metallic return air grille is required with installations
not requiring a return air duct. The spacing between
louvers on the grille shall not be larger than 5/8 inch.
Any grille that meets with the 5/8 inch louver criteria
may be used. It is recommended that Bard Return Air
Grille or Return Filter Grille be installed when no
return duct is used. Contact distributor or factory for
ordering information. If using a return air filter grille,
filters must be of sufficient size to allow a maximum
velocity of 400 fpm.
NOTE: If no return air duct is used, applicable
installation codes may limit this cabinet to
installation only in a single story structure.
4.
HIGH ALTITUDE APPLICATIONS
Ratings of gas utilization equipment are based on sea
level operation and need not be changed for operation
at elevations up to 6,000 feet. For operation at
elevations above 6,000 feet and in the absence of
specific recommendations from the local authority
having jurisdiction, equipment ratings shall be reduced
as specified in Section 21.
5.
TRANSPORTATION DAMAGE
All units are packed securely in shipping container.
All units should be carefully inspected upon arrival for
damage. In the event of damage, the consignee should:
1. Note on delivery receipt of any damage to container.
2. Notify carrier promptly, and request an inspection.
3. In case of concealed damage, the carrier must be
notified as soon as possible within 15 days after
delivery.
4. Claims for any damage, apparent or concealed,
should be filed with the carrier, using the following
supporting documents:
A. Original Bill of Lading, certified copy, or
indemnity bond.
B.
Original paid freight bill of indemnity in lieu
thereof.
C.
Original invoice or certified copy thereof
showing trade and other discounts or
deductions.
D. Copy of the inspection report issued by
carrier’s representative at the time damage is
reported to carrier.
6. INSTALLATION
Size of unit for proposed installation should be based
on heat loss/heat gain calculations made according to
methods of Air Conditioning Contractors of America
(ACCA). The air duct should be installed in
accordance with the Standards of the National Fire
Protection Association for the Installation of Air
Conditioning and Ventilating Systems of Other Than
Residence Type, NFPA No. 90A, and Residence Type
Warm Air Heating and Air Conditioning Systems,
NFPA No. 90B. Where local regulations are at a
variance with instructions, installer should adhere to
local codes.
WARNING
In all cases, there must be a metal duct
connection made to the supply air flange, and
a one inch clearance to combustibles must be
maintained to this duct connection.
For free blow applications, a metal sleeve
must be used in the wall opening itself, again
maintaining a one inch clearance to
combustibles.
Failure to use the sheet metal can cause
fire resulting in property damage, injury, or
death.
Содержание WG242D
Страница 13: ...Manual 2100 376I Page 13 of 80 FIGURE 2A MOUNTING INSTRUCTIONS FOR WG42 WG48 AND WG60...
Страница 15: ...Manual 2100 376I Page 15 of 80 FIGURE 4 WALL MOUNTING INSTRUCTIONS FIGURE 5 WALL MOUNTING INSTRUCTIONS...
Страница 16: ...Manual 2100 376I Page 16 of 80 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...
Страница 22: ...Manual 2100 376I Page 22 of 80 FIGURE 11 LOW VOLTAGE WIRING...
Страница 23: ...Manual 2100 376I Page 23 of 80 FIGURE 11A LOW VOLTAGE WIRING...
Страница 24: ...Manual 2100 376I Page 24 of 80 FIGURE 12 GAS PIPE CONNECTION...
Страница 34: ...Manual 2100 376I Page 34 of 80 26 LIGHTING AND SHUTDOWN INSTRUCTIONS FIGURE 15 INSTRUCTION LABEL...
Страница 40: ...Manual 2100 376I Page 40 of 80 FIGURE 19 460 VOLT BLOWER MOTOR WIRING OPTIONS WG24 WG30 AND WG36 MODELS...
Страница 41: ...Manual 2100 376I Page 41 of 80 FIGURE 20 460 VOLT BLOWER MOTOR WIRING OPTIONS WG42 WG48 AND WG 60 MODELS...
Страница 56: ...Manual 2100 376I Page 56 of 80 WG242DA 230 208 60 1...
Страница 57: ...Manual 2100 376I Page 57 of 80 WG242DA WG362DA 230 208 60 1...
Страница 58: ...Manual 2100 376I Page 58 of 80 WG242DB 230 208 60 3...
Страница 59: ...Manual 2100 376I Page 59 of 80 WG242DB WG362DB 230 208 60 3...
Страница 60: ...Manual 2100 376I Page 60 of 80 WG242DC 460 60 3...
Страница 61: ...Manual 2100 376I Page 61 of 80 WG242DC WG362DC 460 60 3...
Страница 62: ...Manual 2100 376I Page 62 of 80 WG302DA 230 208 60 1...
Страница 63: ...Manual 2100 376I Page 63 of 80 WG302DA WG482DA WG602DA 230 208 60 1...
Страница 64: ...Manual 2100 376I Page 64 of 80 WG302DB 230 208 60 3...
Страница 65: ...Manual 2100 376I Page 65 of 80 WG302DB WG482DB WG602DB 230 208 60 3...
Страница 66: ...Manual 2100 376I Page 66 of 80 WG302DC 460 60 3...
Страница 67: ...Manual 2100 376I Page 67 of 80 WG302DC 460 60 3...
Страница 68: ...Manual 2100 376I Page 68 of 80 WG362DA 230 208 60 1...
Страница 69: ...Manual 2100 376I Page 69 of 80 WG362DB 230 208 60 3...
Страница 70: ...Manual 2100 376I Page 70 of 80 WG362DC 460 60 3...
Страница 71: ...Manual 2100 376I Page 71 of 80 WG423DA 230 208 60 1...
Страница 72: ...Manual 2100 376I Page 72 of 80 WG423DA 230 208 60 1...
Страница 73: ...Manual 2100 376I Page 73 of 80 WG423DB 230 208 60 3...
Страница 74: ...Manual 2100 376I Page 74 of 80 WG423DB 230 208 60 3...
Страница 75: ...Manual 2100 376I Page 75 of 80 WG423DC 460 60 3...
Страница 76: ...Manual 2100 376I Page 76 of 80 WG423DC 460 60 3...
Страница 77: ...Manual 2100 376I Page 77 of 80 WG482DA WG602DA 230 208 60 1...
Страница 78: ...Manual 2100 376I Page 78 of 80 WG482DB WG602DB 230 208 60 3...
Страница 79: ...Manual 2100 376I Page 79 of 80 WG482DC WG602DC 460 60 3...
Страница 80: ...Manual 2100 376I Page 80 of 80 WG482DC WG602DC 460 60 3...