FIGURE 2
MOUNTING INSTRUCTIONS
The unit rating plate lists a “Maximum Time Delay
Relay Fuse” or “HACR” type circuit breaker that is to
be used with the equipment. The correct size must be
used for proper circuit protection and also to assure that
there will be no nuisance tripping due to the momentary
high starting current of the compressor motor.
The disconnect access door on this unit may be locked to
prevent unauthorized access to the disconnect.
To convert for the locking capability, bend the tab
located in the bottom left hand corner of the disconnect
opening under the disconnect access panel straight out.
This tab will now line up with the slot in the door.
When shut, a padlock may be placed through the hole in
the tab preventing entry.
See Start-up section for information on three phase
scroll compressor start-ups.
NOTE: It is recommended that a bead of silicone
caulking be placed behind the side mounting
flanges and under the top flashing at the
time of installation.