background image

Manual 2100-451E
Page

14 of 24

START UP

These units require R-410A refrigerant and polyolester
oil.

GENERAL:

1. Use separate service equipment to avoid cross

contamination of oil and refrigerants.

2. Use recovery equipment rated for R-410A

refrigerant.

3. Use manifold gauges rated for R-410A (800 psi/250

psi low).

4. R-410A is a binary blend of HFC-32 and HFC-125.

5. R-410A is nearly azeotropic - similar to R-22 and

R-12.  Although nearly azeotropic, charge with
liquid refrigerant.

6. R-410A operates at 40-70% higher pressure than

R-22, and systems designed for R-22 cannot
withstand this higher pressure.

7. R-410A has an ozone depletion potential of zero,

but must be reclaimed due to its global warming
potential.

8. R-410A compressors use polyolester oil.

9. Polyolester oil is hygroscopic; it will rapidly absorb

moisture and strongly hold this moisture in the oil.

10. A liquid line dryer must be used - even a deep

vacuum will not separate moisture from the oil.

11. Limit atmospheric exposure to 15 minutes.

12. If compressor removal is necessary, always plug
compressor immediately after removal.  Purge with
small amount of nitrogen when inserting plugs.

TOPPING OFF SYSTEM CHARGE

If a leak has occurred in the system, Bard Manufacturing
recommends reclaiming, evacuating (see criteria above),
and charging to the nameplate charge.  Topping off the
system charge can be done without problems.

With R-410A, there are no significant changes in the
refrigerant composition during multiple leaks and
recharges.  R-410A refrigerant is close to being an
azeotropic blend (it behaves like a pure compound or
single component refrigerant).  The remaining refrigerant
charge, in the system, may be used after leaks have
occurred and then “top-off” the charge by utilizing the
charging charts on the inner control panel cover as a
guideline.

REMEMBER:  

When adding R-410A refrigerant, it must

come out of the charging cylinder/tank as a liquid to
avoid any fractionation, and to insure optimal system
performance.  Refer to instructions for the cylinder that
is being utilized for proper method of liquid extraction.

SAFETY PRACTICES:

1. Never mix R-410A with other refrigerants.

2. Use gloves and safety glasses, polyolester oils can

be irritating to the skin, and liquid refrigerant will
freeze the skin.

3. Never use air and R-410A to leak check; the

mixture may become flammable.

4. Do not inhale R-410A – the vapor attacks the

nervous system, creating dizziness, loss of
coordination and slurred speech.  Cardiac
irregularities, unconsciousness and ultimate death
can result from breathing this concentration.

5. Do not burn R-410A.  This decomposition

produces hazardous vapors.  Evacuate the area if
exposed.

6. Use only cylinders rated DOT4BA/4BW 400.

7. Never fill cylinders over 80% of total capacity.

8. Store cylinders in a cool area, out of direct

sunlight.

9. Never heat cylinders above 125°F.

10. Never trap liquid R-410A in manifold sets, gauge

lines or cylinders.  R-410A expands significantly
at warmer temperatures.  Once a cylinder or line is
full of liquid, any further rise in temperature will
cause it to burst.

Содержание WA3S1

Страница 1: ...File Volume III Tab 16 Date 09 02 08 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Models WA3S1 WA4S1 WA5S1 WALL MOUNTED PACKAGED AIR CONDITIONER INSTALLATIO...

Страница 2: ...General 14 Topping Off System Charge 14 Safety Practices 14 Important Installer Note 15 Crankcase Heaters 15 High Low Pressure Switch 15 Three Phase Scroll Compressor Start Up Information 15 Service...

Страница 3: ...Manual N Summer Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design for Winter Manual Q and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air C...

Страница 4: ...8 0 6 2 8 6 0 0 5 1 1 2 7 5 9 1 1 5 y l n o s t i n u V 8 0 2 0 3 2 n i e l b a l i a v a e r a s r e t a e h c i r t c e l e e s e h T 1 y l n o s t i n u V 0 8 4 n i e l b a l i a v a e r a s r e t...

Страница 5: ...U h t d i W W h t p e D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q S T A B C B 1 S 3 A W 5 7 0 2 4 2 3 4 2 2 5 7 8 4 8 8 8 9 8 8 9 2 8 8 5 1 8 8 9 2 8 8 3 4 0 1 9 1 6 6 1 3 0 0 0...

Страница 6: ...2 5 2 5 6 2 5 4 5 4 5 4 0 3 0 6 0 6 0 3 8 8 8 0 1 6 6 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 Z 0 B 1 S 4 A W 6 0 B 9 0 B 5 1 B 3 8 0 2 0 3 2 1 1 1 1 8 2 9 2 8 3 6 5 0 4 0 4 0 4 0 6 0 1 0 1 8 6 0 1 0 1 0 1 0...

Страница 7: ...ortions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage Refer to Table 9 for maximum static pressure avai...

Страница 8: ...nting rigidity the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself depending upon wall construction Be sure to observe required clearance...

Страница 9: ...n this unit may be locked to prevent unauthorized access to the disconnect To convert for the locking capability bend the tab located in the bottom left hand corner of the disconnect opening under the...

Страница 10: ...2100 451E Page 10 of 24 FIGURE 4 WALL MOUNTINGINSTRUCTIONS FIGURE 3 WALL MOUNTINGINSTRUCTIONS SEEFIGURE3 MOUNTINGINSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FORACTUALDIMENSIONS SEE FIGURE 1 FOR DUCTDIME...

Страница 11: ...Manual 2100 451E Page 11 of 24 FIGURE 5 COMMON WALL MOUNTING INSTALLATIONS...

Страница 12: ...t c e l E e l b a m m a r g o r P n o N e l b a m m a r g o r P l a n o i t n e v n o C r o P H r e v o e g n a h c l a u n a M r o o t u A 8 5 0 3 0 4 8 1 5 1 1 D 0 2 2 5 H T t a e H e g a t s 2 l o...

Страница 13: ...Manual 2100 451E Page 13 of 24 FIGURE 7 LOW VOLTAGE WIRING...

Страница 14: ...rigerant composition during multiple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refriger...

Страница 15: ...ation must be made any time a compressor is change or rewired If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor However reverse operat...

Страница 16: ...eters depending on outdoor temperatures and the load stage of the system This cycling maintains a minimum liquid pressure affecting the minimum suction pressure This effect insures an evaporating temp...

Страница 17: ...o that the system operating pressures can be observed Pressure tables can be found later in the manual covering all models It is imperative to match the correct pressure table to the unit by model num...

Страница 18: ...click as the solenoid returns to its original position 3 If clicks can t be heard shut off power and remove the control circuit molded plug from the compressor and measure the solenoid coil resistanc...

Страница 19: ...vice as shown in Table 8 or by pressures as shown in Table 9 Page 22 The liquid line temperatures in Table 8 are based upon 80 F dry bulb 67 F wet bulb 50 percent R H temperature and rated airflow acr...

Страница 20: ...1 6 1 2 9 3 1 7 3 2 0 4 1 8 5 2 1 4 1 9 7 2 2 4 1 0 0 3 3 4 1 1 2 3 6 4 1 6 4 3 8 4 1 0 7 3 1 5 1 5 9 3 3 5 1 9 1 4 5 5 1 7 4 4 7 5 1 4 7 4 8 5 1 2 0 5 0 6 1 9 2 5 G N I L O O C Y T I C A P A C W O L...

Страница 21: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check...

Страница 22: ...ication Refer to the manufacturer s authorized replacement list USING THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION Orient the control module so that the 3 wire motor plug can be in...

Страница 23: ...call for W2 or Emergency Heat signal from thermostat TABLE 10 INDOOR BLOWER PERFORMANCE 1 l e d o M P S E d e t a R P S E X A M 2 s u o u n i t n o C M F C 3 t s 1 d e t a R M F C e g a t S 4 d n 2 d...

Страница 24: ...E e g a k c a P r e t a e H X 9 0 C S 3 A W H E e g a k c a P r e t a e H X 6 0 C S 4 A W H E e g a k c a P r e t a e H X 6 0 B S 5 A W H E e g a k c a P r e t a e H X X 9 0 B S 5 A W H E e g a k c a...

Отзывы: