background image

Manual 2100-640D 

Page 

22 of 32

TROUBLESHOOTING NIDEC 

SELECTECH SERIES ECM MOTORS

If the Motor Is Running

1.  It is normal for the motor to rock back and forth 

on start up.  Do not replace the motor if this is the 
only problem identified.

2.  If the system is excessively noisy, does not appear 

to change speeds in response to a demand (Heat, 
Cool, Other) or is having symptoms during the 
cycle such as tripping limit or freezing coil, check 
the following:

 

A.  Wait for programmed delays to time out.

 

B.  Ensure that the motors control inputs are 

wired as shown in the factory-supplied wiring 
diagram to ensure motor is getting proper 
control signals and sequencing.

 

C.  Remove the filter and check that all dampers, 

registers and grilles are open and free flowing.  
If removing the filters corrects the problem, 
clean or replace with a less restrictive filter.  
Also check and clean the blower wheel or coil 
as necessary.

 

D.  Check the external static pressure (total of 

both supply and return) to ensure it is within 
the range as listed on the unit serial plate.  If 
higher than allowed, additional duct work is 
needed.

 

E.  If the motor does not shut off at the end of the 

cycle, wait for any programmed delays to time 
out (no more than 90 seconds).  Also make 
sure that there is no call for “Continuous Fan” 
on the “G” terminal.

 

F.  If the above diagnostics do not solve the 

problem, confirm the voltage checks in 
the next section below, then continue with 
the “Model SelecTech Communication 
Diagnostics”.

If the Motor Is Not Running

1.  Check for proper high voltage and ground at the 

(L/L1) (G) (N/L2) connections at the motor (see 
Figure 10).  Correct any voltage issues before 
proceeding to the next step.  The SelecTech motor 
is voltage specific.  Only the correct voltage should 
be applied to the proper motor.  Input voltage 
within plus or minus 10% of the nominal Line 
Power VAC is acceptable.

SERVICE

FIGURE 10

Motor Connections

Manual

2100-467H

Page

22 of 23

FIGURE  10

NOTE:  Bard Models PA13242; PA13302; PA13362-A, -B; PA13422-A, -B, -C; PA13482-A, -B, -C; PA13602-A, -B, -C

contain the X13-Series Motors.

TROUBLESHOOTING  GE  X13-SERIES ECM2.3

 MOTORS

If the Motor is Running

1.  It is normal for the motor to rock back and forth on start up.

Do not replace the motor if this is the only problem identified.

2.  If the system is excessively noisy, does not appear to change

speeds in response to a demand (Heat, Cool, Other), or is having

symptoms during the cycle such as tripping limit or freezing coil,

check the following:

a. Wait for programmed delays to time out.

b. Ensure that the motors control inputs are wired to the factory

supplied wiring diagram to insure motor is getting proper

control  signals  and  sequencing.

c. Remove the filter and check that all dampers, registers, and

grilles are open and free flowing.  If removing the filters

corrects the problem, clean or replace with a less restrictive

filter.  Also check and clean the blower wheel or coil as

necessary.

d. Check the external static pressure (total of both supply and

return) to insure that you are within the ranges as listed on the

unit serial plate.  If higher than allowed, additional duct work

is  needed.

e. If the motor does not shut off at the end of the cycle, wait for

any programmed delays to time out (no more than 90

seconds).   Also make sure that there is no call for

“Continuous Fan” on the "G" terminal.

f. If the above diagnostics do not solve the problem, confirm the

voltage checks in the next section below, then continue with

the   “Model  X13  Communication  Diagnostics”.

If the Motor is Not Running

1.  Check for proper high voltage and ground at the (L/L1) (G) (N/

L2) connections at the motor (see Figure 10).  Correct any voltage

issues before proceeding to the next step.  The X13 Motor is voltage

specific.  Only the correct voltage should be applied to the proper

motor.  Input voltage within plus or minus 10% of the nominal 230

VAC is acceptable.

2.  If the motor has proper high voltage and ground at the (L/L1)

(G) (N/L2) connections, then continue with the “Model X13

Communication  Diagnostics”.

L2 LINE

POWER

EARTH

GROUND

L1 LINE

POWER

NOTE:    MOTOR  IS  CONSTANTLY 

POWERED   BY LINE  VOLTAGE

LINE

POWER

LINE

POWER

GROUND

Содержание W72LA-A

Страница 1: ...o 43506 www bardhvac com Manual 2100 640D Supersedes 2100 640C Date 11 15 17 W18LA A W24LA A W24LA B W24LA F W30LA A W30LA B W30LA C W30LA F W36LA A W36LA B W36LA C W36LA F W42LA A W42LA B W42LA C W42...

Страница 2: ...ecommended Airflow 28 Table 10 Indoor Blower Performance 28 Table 11 Maximum ESP Electric Heat Only 28 Table 12 Electric Heat 29 Table 13 Vent and Control Options 30 Table 14A Optional Accessories Rig...

Страница 3: ...ummer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contract...

Страница 4: ...tended as a general recommended guide they do not supersede any national and or local codes in any way Authorities having jurisdiction should be consulted before the installation is made See page 3 fo...

Страница 5: ...r Grille Kit RG2 through RG5 or RFG2 through RFG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be o...

Страница 6: ...nit MOUNTING THE UNIT 1 These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides A bottom mounting bracket attached to skid for shipping is pro...

Страница 7: ...R S S S 44 E T B N L Disconnect Rain Hood Built In Lockable Low Voltage Access Panel Entrance Heater Electrical Entrance Access Cond Inlet Panel Air Electrical High Voltage Drain Side View 4 Pitch C...

Страница 8: ...AULKING ALONG PANEL FOAM AIR SEAL DUCT RAIN FLASHING HEATER ACCESS MIS 3157 A Wall Opening and Hole Location View Right Side View RETURN AIR TOP FLASHING AT TIME OF INSTALLATION OPENING THE SIDE MOUNT...

Страница 9: ...LY AIR DUCT IS REQUIRED FROM COMBUSTABLE MATERIALS RAIN FLASHING TOP SUPPLY AIR OPENING Right Side View HEATER ACCESS TOP FLASHING AT TIME OF INSTALLATION SEAL WITH BEAD IT IS RECOMMENDED THAT A BEAD...

Страница 10: ...9 3 4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MO...

Страница 11: ...ROM COMBUSTIBLE MATERIALS REQUIRED DIMENSIONS TO MAINTAIN OPENING COMBUSTIBLE MATERIALS B D E PANEL AIR DUCT IS REQUIRED 32 10 1 2 Right Side View SUPPLY AIR RECOMMENDED 1 CLEARANCE FROM MIS 3789 RAIN...

Страница 12: ...ply air duct and combustible materials This is required for the first 3 of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to do this could result in...

Страница 13: ...ORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR ACTUAL...

Страница 14: ...IC SUPPLYAIRDUCT SUPPLYAIRDUCT SUPPLYAIRDUCT RETURNAIR OPENINGW GRILLE OUTSIDE W GRILLE FALSEWALLINSTALLATION CEILING RAIN FLASHING RAIN FLASHING SUPPLYDUCTMAYBELOCATEDINANATTIC ORBELOWCEILINGRAFTERSA...

Страница 15: ...All 230 208V 1 phase and 3 phase equipment have dual primary voltage transformers All equipment leaves the factory wired on 240V tap For 208V operation reconnect from 240V to 208V tap The acceptable...

Страница 16: ...stage Heat Electronic Programmable Non Programmable HP or Conventional Auto or Manual changeover Dehumidification Output CS9B THO 3 stage Cool 3 stage Heat Programmable Non Programmable HP or Convent...

Страница 17: ...rogrammable and fan set to be programmed fan for the A output to function during scheduled occupied periods Must be configured for multi stage for Y1 output to be active 1st stage cooling For dehumidi...

Страница 18: ...nly See vent installation manual 6 For vent operation add jumper if optional CO2 controller is not used Vent will run while blower is energized 4 Factory installed jumper Remove jumper and connect to...

Страница 19: ...o being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used after leaks have occurred and then top off the ch...

Страница 20: ...nal is present at the phase monitor and phases are correct the green LED will light If phases are reversed the red fault LED will be lit and compressor operation is inhibited If a fault condition occu...

Страница 21: ...gize after the delay on make time delay has expired If the low pressure switch remains open or opens again for longer than 120 seconds the unit will go into manual lockout condition and the alarm rela...

Страница 22: ...3362 A B PA13422 A B C PA13482 A B C PA13602 A B C contain the X13 Series Motors TROUBLESHOOTING GE X13 SERIES ECM2 3 MOTORS If the Motor is Running 1 It is normal for the motor to rock back and forth...

Страница 23: ...r is failed and will require replacement 24VAC R Signal through thermostat output 24VAC Common 24VAC Common 24VAC R Signal through thermostat output 2 If the motor has proper high voltage and ground a...

Страница 24: ...harge REMOVAL OF FAN SHROUD 1 Disconnect all power to the unit 2 Remove the screws holding both grilles one on each side of unit and remove grilles 3 Remove nine screws holding fan shroud to condenser...

Страница 25: ...38 402 140 427 142 454 145 482 147 512 149 542 151 573 153 605 W36A L 75 62 Low Side High Side 117 323 120 346 122 370 124 394 127 419 129 446 131 473 134 500 136 528 137 558 138 587 80 67 Low Side Hi...

Страница 26: ...58 26 60 30 6 10 10 10 W30AA B00 B0Z B06 B09 B15 230 208 3 1 1 1 1 19 24 33 51 20 25 35 60 12 10 8 6 12 10 10 10 W30AA C00 C0Z C06 C09 C12 C15 460 3 1 1 1 1 1 9 12 17 21 26 15 15 20 25 30 14 14 12 10...

Страница 27: ...0 C0Z C06 460 3 1 1 9 11 15 15 14 14 14 14 W30LA A00 A0Z A05 A08 A10 A15 230 208 1 1 1 1 1 1 or 2 26 32 47 58 84 35 35 50 60 90 8 8 8 6 4 10 10 10 10 8 58 26 60 30 6 10 10 10 W30LA B00 B0Z B09 B15 230...

Страница 28: ...1940 1750 1700 2105 2010 1540 1460 2255 2155 2075 2015 1995 1930 0 1 965 950 700 690 960 925 1385 1320 930 920 1340 1260 940 930 1905 1880 1700 1640 1910 1865 1675 1615 2045 1960 1480 1395 2185 2095 2...

Страница 29: ...Amps BTUH Amps BTUH Amps BTUH 4 16 7 13650 14 4 10240 5 20 8 17065 18 1 12800 6 14 4 20500 12 5 15360 7 2 20500 8 33 3 27300 28 8 20475 9 21 7 30600 18 7 23030 10 8 30700 10 41 6 34130 36 2 25600 12...

Страница 30: ...VPC2 Energy Recovery Ventilator 460 Volt X BFAD 3 Barometric Fresh Air Damper Standard X BOP 3 Blank Off Plate X WMFADP3 Motorized Fresh Air Damper X WCRVPS3 Commercial Ventilator Spring Return X WECO...

Страница 31: ...W3TA B06 X EHW3TA B09 X X EHW3TA B15 X X EHW3TA C06 X X EHW3TA C09 X X EHW3TA C12 X X EHW3TA C15 X X EHW4TA A05 X X EHWA05 A10B X X X EHWA05 A15B X X X EHWA05 A20B X X X EHW4TA B06 X X X EHWA05 B09B X...

Страница 32: ...A10L X X EHW3TA A15L X X EHW3TA B09L X X EHW3TA B15L X X EHW3TA C09L X X EHW3TA C15L X X EHW4TA A05L X X X EHWA05 A10LB X X X EHWA05 A15LB X X X EHW4TA B06L X X X EHWA05 B09LB X X EHW6TA B06L X EHWA0...

Отзывы: