Manual 2100-640D
Page
18 of 32
FIGURE 9
Thermostat Connections
Optional CO2 Controller
Bard Part #8403-067
6
5
4
3
2
1
TEMP-OUT
CO2 OUT
24VAC
7
6
5
3
2
R
Unit Low
Voltage
Term. Strip
W2
C
G
RT
Y1
Y2
B/W1
L/1
D
A
W3/8
4
5 Do not add these wires if setting up for modulating control. See note 7.
7
Jumper needs added.
8
For 8403-058, change "system type", set up Function 1, From 5 (2 Heat/ 1 Cool heat Pump)
to 6 (2 Heat / 2 Cool Conventional). For 8403-059, No change required.
2B Install Jumper for 1 stage electric heat on units with more
than 10KW.
0-10 VDC Modulating CO2 control signal for modulating ventilation control
(Optional for ECON Only) - See vent installation manual.
6
For vent operation, add jumper if optional CO2 controller is not used.
Vent will run while blower is energized.
4
Factory installed jumper. Remove jumper and connect
to N.C fire alarm circuit if emergency shutdown required.
3
Wire not needed below 15KW.
2A
Wire required for dehumidification models only.
1
Thermostat will not work with units equipped with economizers.
9
10
12
11
9
4
12-Pin
Vent Plug
2
3
5
6
7
6
2B
7
ALL VENT OPTIONS PLUG IN HERE
4
2A
W
Rc
C
R
G
Y
Y2
W2
4
3
5
6
8403-038
G
Electronic Humidistat
Units With Dehumidification
W
C
Rc
Y
R
O
B
Mechanical Humidistat
3
If not equipped with a ventilation option to plug in, a jumper plug must be installed.
1
8403-047
5
8
9
MIS-3739 C
8403-058
(TH522OD1151)
8403-059
(TH522OD1219/U)
or T6 Pro 8403-090
8403-057
(TH311OD1040)
or T4 Pro 8403-089