first check to make sure that either the optional vent is 
plugged into the vent connection plug or the supplied 
jumper plug is in place.  

The unit will not operate 

without anything plugged in.  

This plug is located on 

the side of the control panel behind the front vent door 
(behind the filter access door).  If the unit is supplied 
with a factory-installed vent package, it will be plugged 
in but the jumper plug will also be tethered next to the 
connection for troubleshooting purposes, if necessary.

COMPRESSOR CONTROL MODULE

The compressor control module is standard on all 
models covered by this manual.  The compressor 
control module is an anti-short cycle/lockout timer with 
high and low pressure switch monitoring and alarm 
relay output.

Adjustable Delay-on-Make and Delay-on-Break Timer

On initial power up or anytime power is interrupted to 
the unit, the 

delay-on-make

 period begins, which will 

be 2 minutes plus 10% of the 

delay-on-break

 setting.  

When the delay-on-make is complete and the high 
pressure switch and low pressure switch are closed, the 
compressor contactor is energized.  Upon shutdown, 
the delay-on-break timer starts and prevents restart 
until the delay-on-break and delay-on-make periods 
have expired.  

During routine operation of the unit with no power 
interruptions, the compressor will operate on demand 
with no delay.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor 
contactor will de-energize immediately.  The lockout 
timer will go into a 

soft lockout

 and stay in soft lockout 

until the high pressure switch closes and the delay-
on-break time has expired.  If the high pressure switch 
opens again in this same operating cycle, the unit will 
go into 

manual lockout

 condition and the alarm relay 

circuit will energize.  Recycling the wall thermostat 
resets the manual lockout. 

Low Pressure Switch, Bypass and Lockout Sequence

If the low pressure switch opens for more than 120 
seconds, the compressor contactor will de-energize and 
go into a soft lockout.  Regardless the state of the low 
pressure switch, the contactor will re-energize after 
the delay-on-make time delay has expired.  If the low 
pressure switch remains open, or opens again for longer 
than 120 seconds, the unit will go into manual lockout 
condition and the alarm relay circuit will energize.  
Recycling the wall thermostat resets the manual lockout.

Alarm Relay Output

Alarm terminal is output connection for applications 
where alarm relay is employed.  This terminal is 
powered whenever the compressor is locked out due to 
HPC or LPC sequences as described.

NOTE:

  Both high and low pressure switch controls are 

inherently automatic reset devices.  The high 

pressure switch and low pressure switch cut 

out and cut in settings are fixed by specific air 

conditioner unit model.  The lockout features, 

both soft and manual, are a function of the 

compressor control module. 

Adjustments

Adjustable Delay-on-Make and Delay-on-Break Timer

The potentiometer is used to select delay-on-break time 
from 30 seconds to 5 minutes.  Delay-on-make (DOM) 
timing on power up and after power interruptions is equal 
to 2 minutes plus 10% of delay-on-break (DOB) setting:

0.5 minute (30 seconds) DOB = 123 second DOM
1.0 minute (60 seconds) DOB = 126 second DOM
2.0 minute (120 seconds) DOB = 132 second DOM
3.0 minute (180 seconds) DOB = 138 second DOM
4.0 minute (240 seconds) DOB = 144 second DOM
5.0 minute (300 seconds) DOB = 150 second DOM

During routine operation of the unit with no power 
interruptions, the compressor will operate on demand 
with no delay.

Typical Settings for Dual Unit Installation:

Unit 1:  DOB set at 2 minutes and DOM is 132 seconds

Unit 2:  DOB set at 4 minutes and DOM is 144 seconds

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on 
all units so that the system operating pressures can 
be observed.  A pressure table covering all models can 
be found on page 25.  It is imperative to match the 
correct pressure table to the unit by model number.

This unit employs high-flow Coremax valves instead of 
the typical Shrader type valves.

WARNING! Do NOT use a Schrader valve core removal 

tool with these valves. Use of such a tool could result 

in eye injuries or refrigerant burns!

To change a Coremax valve without first removing the 
refrigerant, a special tool is required which can be 
obtained at www.fastestinc.com/en/SCCA07H.  See the 
replacement parts manual for replacement core part 
numbers.

Содержание W72LA-A

Страница 1: ...o 43506 www bardhvac com Manual 2100 640D Supersedes 2100 640C Date 11 15 17 W18LA A W24LA A W24LA B W24LA F W30LA A W30LA B W30LA C W30LA F W36LA A W36LA B W36LA C W36LA F W42LA A W42LA B W42LA C W42...

Страница 2: ...ecommended Airflow 28 Table 10 Indoor Blower Performance 28 Table 11 Maximum ESP Electric Heat Only 28 Table 12 Electric Heat 29 Table 13 Vent and Control Options 30 Table 14A Optional Accessories Rig...

Страница 3: ...ummer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contract...

Страница 4: ...tended as a general recommended guide they do not supersede any national and or local codes in any way Authorities having jurisdiction should be consulted before the installation is made See page 3 fo...

Страница 5: ...r Grille Kit RG2 through RG5 or RFG2 through RFG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be o...

Страница 6: ...nit MOUNTING THE UNIT 1 These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides A bottom mounting bracket attached to skid for shipping is pro...

Страница 7: ...R S S S 44 E T B N L Disconnect Rain Hood Built In Lockable Low Voltage Access Panel Entrance Heater Electrical Entrance Access Cond Inlet Panel Air Electrical High Voltage Drain Side View 4 Pitch C...

Страница 8: ...AULKING ALONG PANEL FOAM AIR SEAL DUCT RAIN FLASHING HEATER ACCESS MIS 3157 A Wall Opening and Hole Location View Right Side View RETURN AIR TOP FLASHING AT TIME OF INSTALLATION OPENING THE SIDE MOUNT...

Страница 9: ...LY AIR DUCT IS REQUIRED FROM COMBUSTABLE MATERIALS RAIN FLASHING TOP SUPPLY AIR OPENING Right Side View HEATER ACCESS TOP FLASHING AT TIME OF INSTALLATION SEAL WITH BEAD IT IS RECOMMENDED THAT A BEAD...

Страница 10: ...9 3 4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MO...

Страница 11: ...ROM COMBUSTIBLE MATERIALS REQUIRED DIMENSIONS TO MAINTAIN OPENING COMBUSTIBLE MATERIALS B D E PANEL AIR DUCT IS REQUIRED 32 10 1 2 Right Side View SUPPLY AIR RECOMMENDED 1 CLEARANCE FROM MIS 3789 RAIN...

Страница 12: ...ply air duct and combustible materials This is required for the first 3 of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to do this could result in...

Страница 13: ...ORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR ACTUAL...

Страница 14: ...IC SUPPLYAIRDUCT SUPPLYAIRDUCT SUPPLYAIRDUCT RETURNAIR OPENINGW GRILLE OUTSIDE W GRILLE FALSEWALLINSTALLATION CEILING RAIN FLASHING RAIN FLASHING SUPPLYDUCTMAYBELOCATEDINANATTIC ORBELOWCEILINGRAFTERSA...

Страница 15: ...All 230 208V 1 phase and 3 phase equipment have dual primary voltage transformers All equipment leaves the factory wired on 240V tap For 208V operation reconnect from 240V to 208V tap The acceptable...

Страница 16: ...stage Heat Electronic Programmable Non Programmable HP or Conventional Auto or Manual changeover Dehumidification Output CS9B THO 3 stage Cool 3 stage Heat Programmable Non Programmable HP or Convent...

Страница 17: ...rogrammable and fan set to be programmed fan for the A output to function during scheduled occupied periods Must be configured for multi stage for Y1 output to be active 1st stage cooling For dehumidi...

Страница 18: ...nly See vent installation manual 6 For vent operation add jumper if optional CO2 controller is not used Vent will run while blower is energized 4 Factory installed jumper Remove jumper and connect to...

Страница 19: ...o being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used after leaks have occurred and then top off the ch...

Страница 20: ...nal is present at the phase monitor and phases are correct the green LED will light If phases are reversed the red fault LED will be lit and compressor operation is inhibited If a fault condition occu...

Страница 21: ...gize after the delay on make time delay has expired If the low pressure switch remains open or opens again for longer than 120 seconds the unit will go into manual lockout condition and the alarm rela...

Страница 22: ...3362 A B PA13422 A B C PA13482 A B C PA13602 A B C contain the X13 Series Motors TROUBLESHOOTING GE X13 SERIES ECM2 3 MOTORS If the Motor is Running 1 It is normal for the motor to rock back and forth...

Страница 23: ...r is failed and will require replacement 24VAC R Signal through thermostat output 24VAC Common 24VAC Common 24VAC R Signal through thermostat output 2 If the motor has proper high voltage and ground a...

Страница 24: ...harge REMOVAL OF FAN SHROUD 1 Disconnect all power to the unit 2 Remove the screws holding both grilles one on each side of unit and remove grilles 3 Remove nine screws holding fan shroud to condenser...

Страница 25: ...38 402 140 427 142 454 145 482 147 512 149 542 151 573 153 605 W36A L 75 62 Low Side High Side 117 323 120 346 122 370 124 394 127 419 129 446 131 473 134 500 136 528 137 558 138 587 80 67 Low Side Hi...

Страница 26: ...58 26 60 30 6 10 10 10 W30AA B00 B0Z B06 B09 B15 230 208 3 1 1 1 1 19 24 33 51 20 25 35 60 12 10 8 6 12 10 10 10 W30AA C00 C0Z C06 C09 C12 C15 460 3 1 1 1 1 1 9 12 17 21 26 15 15 20 25 30 14 14 12 10...

Страница 27: ...0 C0Z C06 460 3 1 1 9 11 15 15 14 14 14 14 W30LA A00 A0Z A05 A08 A10 A15 230 208 1 1 1 1 1 1 or 2 26 32 47 58 84 35 35 50 60 90 8 8 8 6 4 10 10 10 10 8 58 26 60 30 6 10 10 10 W30LA B00 B0Z B09 B15 230...

Страница 28: ...1940 1750 1700 2105 2010 1540 1460 2255 2155 2075 2015 1995 1930 0 1 965 950 700 690 960 925 1385 1320 930 920 1340 1260 940 930 1905 1880 1700 1640 1910 1865 1675 1615 2045 1960 1480 1395 2185 2095 2...

Страница 29: ...Amps BTUH Amps BTUH Amps BTUH 4 16 7 13650 14 4 10240 5 20 8 17065 18 1 12800 6 14 4 20500 12 5 15360 7 2 20500 8 33 3 27300 28 8 20475 9 21 7 30600 18 7 23030 10 8 30700 10 41 6 34130 36 2 25600 12...

Страница 30: ...VPC2 Energy Recovery Ventilator 460 Volt X BFAD 3 Barometric Fresh Air Damper Standard X BOP 3 Blank Off Plate X WMFADP3 Motorized Fresh Air Damper X WCRVPS3 Commercial Ventilator Spring Return X WECO...

Страница 31: ...W3TA B06 X EHW3TA B09 X X EHW3TA B15 X X EHW3TA C06 X X EHW3TA C09 X X EHW3TA C12 X X EHW3TA C15 X X EHW4TA A05 X X EHWA05 A10B X X X EHWA05 A15B X X X EHWA05 A20B X X X EHW4TA B06 X X X EHWA05 B09B X...

Страница 32: ...A10L X X EHW3TA A15L X X EHW3TA B09L X X EHW3TA B15L X X EHW3TA C09L X X EHW3TA C15L X X EHW4TA A05L X X X EHWA05 A10LB X X X EHWA05 A15LB X X X EHW4TA B06L X X X EHWA05 B09LB X X EHW6TA B06L X EHWA0...

Отзывы: