background image

Manual 2100-692 

Page 

33 of 40

TABLE 13

Recommended Airflow

FIGURE 26

Speed Taps

Speed Tap 1: Vent Speed
Speed Tap 2: Balanced Climate Speed
Speed Tap 3: Default Speed
Speed Tap 4: Medium Speed
Speed Tap 5: High Speed

Manual

2100-467H

Page

23 of 23

FIGURE  11

TROUBLESHOOTING  GE  X13-SERIES ECM2.3

 MOTORS 

CONT’D.

Model X13 Communication Diagnostics

The X13 motor is communicated through 24 VAC low voltage

(Thermostat Control Circuit Wiring).

1.

Start with unit wiring diagram to confirm proper

connections and voltage (see Figure 11).

2. Initiate a demand from the thermostat and check the

voltage between the common and the appropriate motor

terminal (1-5).  ("G" input is typically on terminal #1, but

refer to wiring diagram!)

a. If the low voltage communication is not present, check

the demand from the thermostat.  Also check the

output terminal and wire(s) from the terminal strip or

control relay(s) to the motor.

b. If the motor has proper high voltage as identified

above (Motor not Running #1), and proper low voltage

to a programmed terminal, and is not operating, the

motor is failed, and will require replacement.

24VAC "R" Sig nal thro ug h 

thermo stat o utp ut.

24VAC Co mmo n

24VAC Co mmo n

24VAC "R" Sig nal thro ug h 

thermo stat o utp ut.

24VAC Common

24VAC "R" 

signal through 

thermostat output

Model

Nominal 

Rated 

CFM*

Nominal 

Rated 

ESP*

Recommended 

Airflow Range

Factory 

Speed 

Connection

W42AC

1350

.15

1250 - 1600

Default

W48AC

1550

.20

1450 - 1750

W60AC

1750

.20

1650 - 2000

W72AC

1900

.25

1800 - 2100

* Rated CFM and ESP on factory speed connection.

Setting Unit Airflow

The unit is set from the factory at the default speed. 
Most units have three selectable cooling speed taps 
that can be utilized. The default speed is the lowest 
cooling speed. The two higher speed taps can be used 
for higher duct static applications so that the unit can 
maintain the recommended airflow as shown in Table 
13. The higher speeds can also be used when higher 
sensible cooling is desired. To change to the higher 
speed taps, move the orange/black wire on the blower 
speed terminal block to either MED or HI. Refer to 
Table 15 on page 35 for the corresponding airflow of 
each tap. Set the unit duct static based on the highest 
airflow that the unit will run at.

NOTE:

 Be sure to adjust the system static or 

blower speed to maintain airflows above the 

minimum recommendations to prevent freeze 

up conditions if Balanced Climate mode is 

activated.

Do not operate the unit in Balanced Climate mode 
if running high static applications as indicated in 
the blower performance table. If Balanced Climate 
mode is activated as described on page 18, the unit 
will run in this mode at all times unless there is a 

call for ventilation, electric heat or 2nd stage cooling 
from a 2-stage thermostat. At that time, the unit will 
automatically activate a higher speed tap.

Blower Speeds

The ECM motor blower speeds are communicated 
through 24VAC low voltage signals from the low voltage 
terminal block inside the control panel area to speed 
taps. Each speed tap is programmed by Bard at the 
factory to different motor torque settings (see Figure 26).

Unit 

Operation

Thermostat Inputs – 24VAC

Speed Taps

Blower Speed

Compressor 

Operation

G

Y1

Y2 W1 W2

A

D

1

2

3-4-5

1

Blower Only

X

X

Vent/Blower Only

Off

Balanced Climate Cooling

X

X

X

X

Balanced Climate

On

Full Load Cool

X

X

X

X

X

X

Lo/Med/Hi

On

1st Stage Heat

X

X

Lo/Med/Hi

Off

2nd Stage Heat

X

X

X

Lo/Med/Hi

Off

Dehumidify

2

X

X

X

Balanced Climate

On

¹ 

Fan speed is selectable through the blower speed control terminal block. LO (default), MED or HI speeds can be used.

2

 

Dehumidification operation is disabled when a call for heating or cooling occurs. Unit runs at Balanced Climate speed 
during dehumidification operation.

TABLE 14

Blower Speeds for Unit Operational Modes

Five factory programmed speed taps (torque settings) 
are available for the motor, and are selected through 
different unit modes of operation. These modes are 
energized by 24VAC signals from the low voltage 
terminal block located inside the control panel by a 
thermostat or other controlling device.
Multiple motor speed taps may be energized 
simultaneously by 24VAC power during different modes 
of operation. The highest number speed tap energized 
takes priority with 5 being the highest and 1 being 
the lowest. See Table 14 for the corresponding blower 
speeds with the different modes of operation.

Содержание W42AC-A

Страница 1: ...DITIONER Models INSTALLATION INSTRUCTIONS W42AC A W42AC B W42AC C W48AC A W48AC B W48AC C Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 692 Supersedes NEW Date 6 13 19 W...

Страница 2: ...alanced ClimateTM Mode 24 Vent Connection Plug 25 Compressor Control Module 25 Features 25 Delay on Make Timer 25 Short Cycle Delay on Break 25 Low Pressure Detection 26 High Pressure Detection 26 Tes...

Страница 3: ...rch Park P O Box 9101 Quincy MA 02269 9901 Telephone 800 344 3555 Fax 617 984 7057 FIGURES Figure 1 Front Control Panel Cover 5 Figure 2 Removing Left Filter 5 Figure 3 Removing Second Filter 6 Figure...

Страница 4: ...read before beginning the installation Note particularly Starting Procedure and any tags and or labels attached to the equipment While these instructions are intended as a general recommended guide t...

Страница 5: ...ng instructions on page 6 and Figures 3 7 pages 8 12 for further details Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity So...

Страница 6: ...ray see Figure 7 FIGURE 6 Remove Four Screws 5 Re install the four 4 screws into the upper screw holes on the filter support brackets Then bend the tab up out of the way see Figure 8 FIGURE 7 Re Insta...

Страница 7: ...he damper opens so that the amount of fresh air that enters the structure is regulated Graphs found on pages 38 and 39 give approximate fresh air amounts based on the slide adjustment setting All capa...

Страница 8: ...condensate drainage A plastic drain hose extends from the drain pan in the upper section of the unit and extends down to the unit base An opening is supplied towards the back of the unit base for the...

Страница 9: ...used applicable installation codes may limit this cabinet to installation only in a single story structure Thermostat or Indoor Temperature Sensor Placement The location and installation of the thermo...

Страница 10: ...and mark bolt hole locations and bottom mounting bracket location Install bottom mounting bracket with field supplied fasteners to wall if it is to be used optional Bracket must be level and installed...

Страница 11: ...2AC 1 4 0 FIGURE 12 Vent Installation Removal Clearance Required 20 750 2 000 37 250 17 750 45 000 MIS 4042 KEEP AREA CLEAR FOR 45 VENT SHOWN OUTSIDE OF UNIT CLEARANCE NEEDED ON LEFT OR RIGHT SIDE OF...

Страница 12: ...Built In Low Voltage Electrical Entrance J A C I K D 2 250 H 1 375 Location Flashing Top Rain Shipping Side Wall Mounting Brackets Built In 375 B E O M N T S S S S S L R 375 TYP Width W Depth D Height...

Страница 13: ...OMMENDED 1 CLEARANCE FROM COMBUSTIBLE MATERIALS 32 12 5 1 2 2 29 16 1 7 8 W6AC W72AC UNITS REQUIRED DIMESIONS TO MAINTAIN 1 4 MIN CLEARANCE FROM COMBUSTIBLE MATERIALS 30 1 2 10 1 2 6 1 4 1 1 4 29 3 4...

Страница 14: ...OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1 4 CLEARANCE TO COMBUSTIBLE SURFACES Fire hazard Maintain minimum 1 4 clearance between the supply air duct and combustible materials in the first 3...

Страница 15: ...FINISH WALL OVER FRAME ATTACH TO BOTTOM PLATE OF WALL 1 000 CLEARANCE ALL AROUND DUCT ATTACH TO TOP PLATE OF WALL THIS STRUCTURAL MEMBER LOCATED TO MATCH STUD SPACING FOR REST OF WALL A SECOND MEMBER...

Страница 16: ...WERED GRILLE RAISED FLOOR RETURN AIR OUTSIDE SPACE RETURN AIR RAFTERS RAFTERS WALL OUTSIDE WALL SUPPLY AIR DUCT FALSE WALL OUTSIDE WALL OUTSIDE W GRILLE SURFACE RETURN AIR WALL FLASHING RAIN FLASHING...

Страница 17: ...IRE SHIELD FIELD WIRE SHIELD FRONT VIEW USE CONDUIT WHEN FIELD WIRES COME IN THROUGH THE BACK RIGHT SIDE VIEW FIGURE 19 High Voltage Connections the number of field power circuits required for the var...

Страница 18: ...cted with a brass jumper bar which can be removed and RT and R connected to an external NC normally closed contact such as a fire smoke detector that will cause shutdown of the equipment upon activati...

Страница 19: ...he switch is adjustable and measures pressure drop across the unit filter surface When pressure drop is higher than the switch setting NO and NC contacts are provided to indicate the filter needs to b...

Страница 20: ...Cool 3 stage Heat Programmable Non Programmable HP or Conventional Auto or Manual Changeover Humidity Sensor w dehumidification Motion Sensor w Intelligent Learning Control BACnet compatible CS9B THO...

Страница 21: ...cupied periods Must be configured for multi stage for Y1 output to be active 1st stage cooling For dehumidification must be configured for No Economizer for YO D to be active for humidity control 4 Fa...

Страница 22: ...CO2 control signal for modulating ventilation control Optional for ECON Only See vent installation manual 6 For vent operation add jumper if optional CO2 controller is not used Vent will run while bl...

Страница 23: ...refrigerant it must come out of the charging cylinder tank as a liquid to avoid any fractionation and to ensure optimal system performance Refer to instructions for the cylinder that is being utilize...

Страница 24: ...peed These models are factory wired on low speed Service Hints 1 Caution owner operator to maintain clean air filters at all times and also not to needlessly close off supply and return air registers...

Страница 25: ...led vent package it will be plugged in but the jumper plug will also be tethered next to the connection for troubleshooting purposes if necessary Compressor Control Module The compressor control modul...

Страница 26: ...timers can be set by DIP switches in order to delay signaling a power brownout for a specific length of time after compressor contactor is energized This allows the compressor a time period to start e...

Страница 27: ...3302 PA13362 A B PA13422 A B C PA13482 A B C PA13602 A B C contain the X13 Series Motors TROUBLESHOOTING GE X13 SERIES ECM2 3 MOTORS If the Motor is Running 1 It is normal for the motor to rock back a...

Страница 28: ...tput 24VAC Common 24VAC Common 24VAC R Signal through thermostat output 2 If the motor has proper high voltage and ground at the L L1 G N L2 connections then continue with the Model SelecTech Communic...

Страница 29: ...oil for cleaning or to service the outdoor fan first remove the side grilles 3 The fan shroud sides can then be removed for ease of access to the coil and the back side of the shroud by removing the s...

Страница 30: ...85 72 Low Side High Side 135 333 138 357 140 382 142 407 144 434 146 461 148 489 150 519 152 549 155 580 157 612 W48AC 75 62 Low Side High Side 128 331 131 352 133 374 135 398 137 422 138 448 140 474...

Страница 31: ...49 633 85 72 Low Side High Side 127 331 129 349 131 368 134 390 136 415 139 441 141 470 143 501 146 534 148 569 151 608 W48AC 75 62 Low Side High Side 122 320 123 341 125 365 127 388 129 412 132 438 1...

Страница 32: ...t C Ckt A Ckt B Ckt C W42AC A00 A0Z A05 A10 A15 A20 230 208 1 1 1 1 1 or 2 1 or 2 31 31 57 83 109 50 50 60 90 120 8 8 6 4 2 10 10 10 8 6 57 57 26 52 60 60 30 60 6 6 10 6 10 10 10 10 W42AC B00 B0Z B06...

Страница 33: ...page 35 for the corresponding airflow of each tap Set the unit duct static based on the highest airflow that the unit will run at NOTE Be sure to adjust the system static or blower speed to maintain a...

Страница 34: ...s used when Balanced Climate is called for by energizing the Y1 terminal of the low voltage terminal block with 24VAC Speed tap 2 is overridden if taps 3 4 or 5 are energized Speed Tap 3 Default LO Co...

Страница 35: ...1655 1555 1785 1685 1870 1780 0 25 1615 1520 1750 1645 1835 1745 0 30 1575 1485 1715 1610 1800 1710 0 40 1485 1405 1635 1540 1730 1635 050 1390 1325 1550 1475 1655 1560 W60AC 0 00 1540 1480 1960 1870...

Страница 36: ...5 18 1 12800 6 14 4 20500 12 5 15360 7 2 20500 9 21 7 30600 18 7 23030 10 8 30700 10 41 6 34130 36 2 25600 15 62 5 51250 54 0 38400 36 2 51200 31 2 38400 18 0 51200 18 43 3 61430 37 4 46060 20 83 2 68...

Страница 37: ...Off X CMA 42 Alarm Relay X CMA 43 ODT X CMA 44 DDC X BOP5 Blank Off Plate X FAD NE5 Fresh Air Damper No Exhaust X FAD BE5 Fresh Air Damper Barometric Exhaust X CRVF 5 Commercial Ventilator On Off Spri...

Страница 38: ...D B18 X EHWA42C C05 X EHWA42C C09 X EHWA42CD C09 X EHWA42C C15 X X EHWA48C A05 X X EHWA48CD A05 X EHWA48CD A10 X EHWA48CD B09 X EHWA48C B15 X EHWA48C B18 X X X X EHWA48CD B18 X EHWA48C C09 X X X EHWA6...

Страница 39: ...Manual 2100 692 Page 39 of 40 GRAPH 1 W42AC FAD NE5 W O Exhaust Ventilation Delivery GRAPH 2 W48AC FAD NE5 W O Exhaust Ventilation Delivery...

Страница 40: ...Manual 2100 692 Page 40 of 40 GRAPH 3 W60AC FAD NE5 W O Exhaust Ventilation Delivery GRAPH 4 W72AC FAD NE5 W O Exhaust Ventilation Delivery...

Отзывы: