background image

Manual 2100-692 

Page 

9 of 40

supply and/or return stub duct may be connected to the 
unit supply and return flanges before unit installation to 
help with duct connections inside the structure. Supply 
and return ducts must be properly sized for the design 
airflow requirement of the equipment. Air Conditioning 
Contractors of America (ACCA) is an excellent guide 
to proper sizing. All duct work or portions thereof not 
in the conditioned space should be properly insulated 
in order to conserve energy, reduce heat conductivity, 
and prevent condensation or moisture damage. Refer to 
Maximum External Static Pressure (ESP) of operation 
and Electric Heat Table 16 on page 36. Design the 
duct work according to methods given by the Air 
Conditioning Contractors of America (ACCA). When 
duct work is installed in unheated spaces, it should 
be insulated with a minimum of 1" of insulation. Use 
insulation with a vapor barrier on the outside of the 
insulation. Flexible joints should be used to connect 
the duct work to the equipment in order to keep the 
noise transmission to a minimum. Ducts through the 
walls must be insulated and all joints taped or sealed to 
prevent air or moisture from entering the wall cavity.
All model series require a 1/4" clearance to 
combustible material for the first 3' of duct attached 
to the outlet air frame is required. See instructions 
on page 11 and Figures 14 − 18 (pages 13 – 16) for 
further details.

A metallic return air grille is required for non-ducted 
applications. The spacing between louvers on the grille 
shall not be larger than 5/8". It is recommended that a 
Bard Return Air Grille Kit is installed that is designed 
specifically for the wall mount product. Contact the 
local Bard distributor or visit www.bardhvac.com for 
ordering information. A field-supplied return grille 
that meets the 5/8" louver criteria and does not cause 
the unit to exceed the maximum specified external 
static pressure (ESP) may be used. If using a return 
air filter grille, filters must be of sufficient size to 
allow a maximum velocity of 400 fpm. Filter return 
air grilles do not filter air being brought into the 
structure through ventilation options including fresh air 
dampers, ventilators, economizers and energy recovery 
ventilators. Be sure to install the return grille with the 
louvers pointed downward towards the floor. This will 
help ensure return air is drawn upward from the floor 
and improve air circulation in the room.

NOTE:

  If no return air duct is used, applicable 

installation codes may limit this cabinet to 

installation only in a single story structure.

Thermostat or Indoor Temperature Sensor Placement

The location and installation of the thermostat or 
temperature sensor that monitors indoor temperature is 
very important regarding unit operation. Avoid placing 
the thermostat in an area exposed to direct sunlight 
or air from doorways leading outdoors. Use a piece 
of insulating material to close off conduit openings 
or holes in the wall surface for wire entry into the 
thermostat or temperature sensor. This will help avoid 
non-conditioned air from entering the thermostat 
and effecting temperature and/or humidity readings. 
As common practice, the thermostat or temperature 
sensor should measure the temperature of the air 
being returned to the unit, and not the conditioned 
air being supplied by the unit. Placing the thermostat 
or temperature sensor near a return air opening will 
normally result in optimal unit performance.

Unit Installation

Make sure to have the proper tools at the work site that 
are needed for unit installation. The following steps 
are provided to ensure the unit is installed properly to 
the wall surface, and that the unit will provide years of 
service with minimal service requirements.

Materials/Tools List

Additional hardware and miscellaneous supplies are 
needed for installation. These items are field supplied 
and must be sourced before installation. This list also 
includes tools needed for installation.

•  Appropriate safety gear including gloves and safety 

glasses

•  5/16" hex bit with drill driver
•  Phillips head screwdriver

Fire hazard.

Maintain minimum 1/4" clearance between the 
supply air duct and combustible materials in 

the first 3' of ducting.
Failure to do so could result in fire causing 

damage, injury or death.

!

WARNING

Free Blow Applications

Some installations may not require extensive supply 
duct work throughout the structure and are referred 
to as free blow applications. A short field-fabricated 
supply duct must be used in the wall cavity to 
transition between the supply collar on the unit and 
the supply louver grille in the room. The duct must 
be properly insulated in order to conserve energy, 
reduce heat conductivity and prevent condensation or 
moisture damage. All joints must be taped or sealed to 
prevent air or moisture entering the wall cavity. Follow 
all clearances including distances to combustible 
materials and all instructions provided in this manual. 
A non-restrictive metallic supply air grille with 
deflectors is required for free blow applications. Contact 
the local Bard distributor or visit www.bardhvac.com for 
ordering information.

Содержание W42AC-A

Страница 1: ...DITIONER Models INSTALLATION INSTRUCTIONS W42AC A W42AC B W42AC C W48AC A W48AC B W48AC C Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 692 Supersedes NEW Date 6 13 19 W...

Страница 2: ...alanced ClimateTM Mode 24 Vent Connection Plug 25 Compressor Control Module 25 Features 25 Delay on Make Timer 25 Short Cycle Delay on Break 25 Low Pressure Detection 26 High Pressure Detection 26 Tes...

Страница 3: ...rch Park P O Box 9101 Quincy MA 02269 9901 Telephone 800 344 3555 Fax 617 984 7057 FIGURES Figure 1 Front Control Panel Cover 5 Figure 2 Removing Left Filter 5 Figure 3 Removing Second Filter 6 Figure...

Страница 4: ...read before beginning the installation Note particularly Starting Procedure and any tags and or labels attached to the equipment While these instructions are intended as a general recommended guide t...

Страница 5: ...ng instructions on page 6 and Figures 3 7 pages 8 12 for further details Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity So...

Страница 6: ...ray see Figure 7 FIGURE 6 Remove Four Screws 5 Re install the four 4 screws into the upper screw holes on the filter support brackets Then bend the tab up out of the way see Figure 8 FIGURE 7 Re Insta...

Страница 7: ...he damper opens so that the amount of fresh air that enters the structure is regulated Graphs found on pages 38 and 39 give approximate fresh air amounts based on the slide adjustment setting All capa...

Страница 8: ...condensate drainage A plastic drain hose extends from the drain pan in the upper section of the unit and extends down to the unit base An opening is supplied towards the back of the unit base for the...

Страница 9: ...used applicable installation codes may limit this cabinet to installation only in a single story structure Thermostat or Indoor Temperature Sensor Placement The location and installation of the thermo...

Страница 10: ...and mark bolt hole locations and bottom mounting bracket location Install bottom mounting bracket with field supplied fasteners to wall if it is to be used optional Bracket must be level and installed...

Страница 11: ...2AC 1 4 0 FIGURE 12 Vent Installation Removal Clearance Required 20 750 2 000 37 250 17 750 45 000 MIS 4042 KEEP AREA CLEAR FOR 45 VENT SHOWN OUTSIDE OF UNIT CLEARANCE NEEDED ON LEFT OR RIGHT SIDE OF...

Страница 12: ...Built In Low Voltage Electrical Entrance J A C I K D 2 250 H 1 375 Location Flashing Top Rain Shipping Side Wall Mounting Brackets Built In 375 B E O M N T S S S S S L R 375 TYP Width W Depth D Height...

Страница 13: ...OMMENDED 1 CLEARANCE FROM COMBUSTIBLE MATERIALS 32 12 5 1 2 2 29 16 1 7 8 W6AC W72AC UNITS REQUIRED DIMESIONS TO MAINTAIN 1 4 MIN CLEARANCE FROM COMBUSTIBLE MATERIALS 30 1 2 10 1 2 6 1 4 1 1 4 29 3 4...

Страница 14: ...OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1 4 CLEARANCE TO COMBUSTIBLE SURFACES Fire hazard Maintain minimum 1 4 clearance between the supply air duct and combustible materials in the first 3...

Страница 15: ...FINISH WALL OVER FRAME ATTACH TO BOTTOM PLATE OF WALL 1 000 CLEARANCE ALL AROUND DUCT ATTACH TO TOP PLATE OF WALL THIS STRUCTURAL MEMBER LOCATED TO MATCH STUD SPACING FOR REST OF WALL A SECOND MEMBER...

Страница 16: ...WERED GRILLE RAISED FLOOR RETURN AIR OUTSIDE SPACE RETURN AIR RAFTERS RAFTERS WALL OUTSIDE WALL SUPPLY AIR DUCT FALSE WALL OUTSIDE WALL OUTSIDE W GRILLE SURFACE RETURN AIR WALL FLASHING RAIN FLASHING...

Страница 17: ...IRE SHIELD FIELD WIRE SHIELD FRONT VIEW USE CONDUIT WHEN FIELD WIRES COME IN THROUGH THE BACK RIGHT SIDE VIEW FIGURE 19 High Voltage Connections the number of field power circuits required for the var...

Страница 18: ...cted with a brass jumper bar which can be removed and RT and R connected to an external NC normally closed contact such as a fire smoke detector that will cause shutdown of the equipment upon activati...

Страница 19: ...he switch is adjustable and measures pressure drop across the unit filter surface When pressure drop is higher than the switch setting NO and NC contacts are provided to indicate the filter needs to b...

Страница 20: ...Cool 3 stage Heat Programmable Non Programmable HP or Conventional Auto or Manual Changeover Humidity Sensor w dehumidification Motion Sensor w Intelligent Learning Control BACnet compatible CS9B THO...

Страница 21: ...cupied periods Must be configured for multi stage for Y1 output to be active 1st stage cooling For dehumidification must be configured for No Economizer for YO D to be active for humidity control 4 Fa...

Страница 22: ...CO2 control signal for modulating ventilation control Optional for ECON Only See vent installation manual 6 For vent operation add jumper if optional CO2 controller is not used Vent will run while bl...

Страница 23: ...refrigerant it must come out of the charging cylinder tank as a liquid to avoid any fractionation and to ensure optimal system performance Refer to instructions for the cylinder that is being utilize...

Страница 24: ...peed These models are factory wired on low speed Service Hints 1 Caution owner operator to maintain clean air filters at all times and also not to needlessly close off supply and return air registers...

Страница 25: ...led vent package it will be plugged in but the jumper plug will also be tethered next to the connection for troubleshooting purposes if necessary Compressor Control Module The compressor control modul...

Страница 26: ...timers can be set by DIP switches in order to delay signaling a power brownout for a specific length of time after compressor contactor is energized This allows the compressor a time period to start e...

Страница 27: ...3302 PA13362 A B PA13422 A B C PA13482 A B C PA13602 A B C contain the X13 Series Motors TROUBLESHOOTING GE X13 SERIES ECM2 3 MOTORS If the Motor is Running 1 It is normal for the motor to rock back a...

Страница 28: ...tput 24VAC Common 24VAC Common 24VAC R Signal through thermostat output 2 If the motor has proper high voltage and ground at the L L1 G N L2 connections then continue with the Model SelecTech Communic...

Страница 29: ...oil for cleaning or to service the outdoor fan first remove the side grilles 3 The fan shroud sides can then be removed for ease of access to the coil and the back side of the shroud by removing the s...

Страница 30: ...85 72 Low Side High Side 135 333 138 357 140 382 142 407 144 434 146 461 148 489 150 519 152 549 155 580 157 612 W48AC 75 62 Low Side High Side 128 331 131 352 133 374 135 398 137 422 138 448 140 474...

Страница 31: ...49 633 85 72 Low Side High Side 127 331 129 349 131 368 134 390 136 415 139 441 141 470 143 501 146 534 148 569 151 608 W48AC 75 62 Low Side High Side 122 320 123 341 125 365 127 388 129 412 132 438 1...

Страница 32: ...t C Ckt A Ckt B Ckt C W42AC A00 A0Z A05 A10 A15 A20 230 208 1 1 1 1 1 or 2 1 or 2 31 31 57 83 109 50 50 60 90 120 8 8 6 4 2 10 10 10 8 6 57 57 26 52 60 60 30 60 6 6 10 6 10 10 10 10 W42AC B00 B0Z B06...

Страница 33: ...page 35 for the corresponding airflow of each tap Set the unit duct static based on the highest airflow that the unit will run at NOTE Be sure to adjust the system static or blower speed to maintain a...

Страница 34: ...s used when Balanced Climate is called for by energizing the Y1 terminal of the low voltage terminal block with 24VAC Speed tap 2 is overridden if taps 3 4 or 5 are energized Speed Tap 3 Default LO Co...

Страница 35: ...1655 1555 1785 1685 1870 1780 0 25 1615 1520 1750 1645 1835 1745 0 30 1575 1485 1715 1610 1800 1710 0 40 1485 1405 1635 1540 1730 1635 050 1390 1325 1550 1475 1655 1560 W60AC 0 00 1540 1480 1960 1870...

Страница 36: ...5 18 1 12800 6 14 4 20500 12 5 15360 7 2 20500 9 21 7 30600 18 7 23030 10 8 30700 10 41 6 34130 36 2 25600 15 62 5 51250 54 0 38400 36 2 51200 31 2 38400 18 0 51200 18 43 3 61430 37 4 46060 20 83 2 68...

Страница 37: ...Off X CMA 42 Alarm Relay X CMA 43 ODT X CMA 44 DDC X BOP5 Blank Off Plate X FAD NE5 Fresh Air Damper No Exhaust X FAD BE5 Fresh Air Damper Barometric Exhaust X CRVF 5 Commercial Ventilator On Off Spri...

Страница 38: ...D B18 X EHWA42C C05 X EHWA42C C09 X EHWA42CD C09 X EHWA42C C15 X X EHWA48C A05 X X EHWA48CD A05 X EHWA48CD A10 X EHWA48CD B09 X EHWA48C B15 X EHWA48C B18 X X X X EHWA48CD B18 X EHWA48C C09 X X X EHWA6...

Страница 39: ...Manual 2100 692 Page 39 of 40 GRAPH 1 W42AC FAD NE5 W O Exhaust Ventilation Delivery GRAPH 2 W48AC FAD NE5 W O Exhaust Ventilation Delivery...

Страница 40: ...Manual 2100 692 Page 40 of 40 GRAPH 3 W60AC FAD NE5 W O Exhaust Ventilation Delivery GRAPH 4 W72AC FAD NE5 W O Exhaust Ventilation Delivery...

Отзывы: