background image

Manual 2100-530A
Page

9 of 22

INSTALLATION INSTRUCTIONS

        WARNING

Failure to provide the 1/4 inch clearance
between the supply duct and a combustible
surface for the first 3 feet of duct can result in
fire causing damage, injury or death.

WALL MOUNTING INFORMATION

1. Two holes for the supply and return air openings

must be cut through the wall as shown in Figure 3.

2. On wood frame walls, the wall construction must be

strong and rigid enough to carry the weight of the
unit without transmitting any unit vibration.

3. Concrete block walls must be thoroughly inspected

to insure that they are capable of carrying the weight
of the installed unit.

MOUNTING THE UNIT

1. These units are secured by wall mounting brackets

which secure the unit to the outside wall surface at
both sides.  A bottom mounting bracket, attached to
skid for shipping, is provided for ease of installation,
but is not required.

2. The unit itself is suitable for 0 inch clearance, but

the supply air duct flange and the first 3 feet of
supply air duct require a minimum of 1/4 inch
clearance to combustible material.  If a combustible
wall, use a minimum of 30½" x 10½" dimensions for
sizing.  However, it is generally recommended that a
1-inch clearance is used for ease of installation and
maintaining the required clearance to combustible
material.  The supply air opening would then be
32" x 12".  See Figures 3 and 4 for details.

3. Locate and mark lag bolt locations and bottom

mounting bracket location.  See Figure 3.

4. Mount bottom mounting bracket.

5. Hook top rain flashing, attached to front - right of

supply flange for shipping, under back bend of top.
Top rain flashing is shipped secured to the right side
of the back.

 6. Position unit in opening and secure with 5/16 lag

bolts; use 7/8 inch diameter flat washers on the lag
bolts.

7. Secure rain flashing to wall and caulk across entire

length of top.  See Figure 3.

8. For additional mounting rigidity, the return air and

supply air frames or collars can be drilled and
screwed or welded to the structural wall itself
(depending upon wall construction).  Be sure to
observe required clearance if combustible wall.

9. On side-by-side installations, maintain a minimum

of 20 inches clearance on right side to allow access
to control panel and heat strips, and to allow proper
airflow to the outdoor coil.  Additional clearance
may be required to meet local or national codes.

Содержание W38A1

Страница 1: ...ON INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS MODELS W38A1 W49A1 W61A1 Manual 2100 530A Supersedes 2100 530 File Volume III Tab 16 Date 12 15 11 Bard Manufacturing Company Inc Bryan Ohio 43506...

Страница 2: ...ed 19 Table 7 Optional Accessories 20 Getting Other Information and Publications 3 Wall Mount General Information Wall Mount Model Nomenclature 4 Shipping Damage 7 General 7 Duct Work 7 Filters 8 Fres...

Страница 3: ...Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Ham...

Страница 4: ...o Coating 1 Phenolic Coated Evaporator 2 Phenolic Coated Condenser 3 Phenolic Coated Evaporator and Condenser OUTLET OPTIONS X Front CAPACITY 38 3 Ton 49 4 Ton 61 5 Ton W 38 A 1 A 10 X X X X X X Note...

Страница 5: ...om Installation Bracket Back View E 44 M T R S2 P S2 L O S1 Q N S1 S1 B l a n i m o N s t n e m e r i u q e R n o i t a l l a t s n I d n a l a r u t c e t i h c r A r o f t i n U c i s a B f o s n o...

Страница 6: ...i n i M t i u c r i C y t i c a p m A 1 m u m i x a M e s u F l a n r e t x E r k r B t k C r o 2 d l e i F r e w o P e z i S e r i W 2 d n u o r G e z i S e r i W A t k C B t k C A t k C B t k C A t...

Страница 7: ...90B Where local regulations are at a variance with instructions installer should adhere to local codes DUCT WORK All duct work supply and return must be properly sized for the design airflow requireme...

Страница 8: ...shipped already attached to the unit The damper blade is locked in the closed position To allow the damper to operate the maximum and minimum blade position stops must be installed See Figure 2 All c...

Страница 9: ...a combustible wall use a minimum of 30 x 10 dimensions for sizing However it is generally recommended that a 1 inch clearance is used for ease of installation and maintaining the required clearance t...

Страница 10: ...2 Wall Opening and Hole Location View Right Side View 29 OPENING SUPPLIED Supply Opening NOTES SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF Return Opening SILICONE CAULKING BE PLACED BEHIND THE SIDE MO...

Страница 11: ...is is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible ma...

Страница 12: ...Manual 2100 530A Page 12 of 22 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Страница 13: ...Manual 2100 530A Page 13 of 22 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS...

Страница 14: ...circuit breaker that is to be used with the equipment The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high...

Страница 15: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Страница 16: ...minutes the compressor s internal protector will trip All three phase ZR compressors are wired identically internally As a result once the correct phasing is determined for a specific system or insta...

Страница 17: ...s and Lockout Sequence If the low pressure switch opens for more than 120 seconds the compressor contactor will de energize and go into a soft lockout Regardless the state of the low pressure switch t...

Страница 18: ...4 9 3 1 3 7 4 0 4 1 2 0 5 2 4 1 3 3 5 B D 5 8 B W 2 7 e d i S w o L e d i S h g i H 0 3 1 8 3 3 4 3 1 9 5 3 6 3 1 2 8 3 8 3 1 7 0 4 0 4 1 3 3 4 2 4 1 1 6 4 4 4 1 0 9 4 5 4 1 0 2 5 7 4 1 2 5 5 1 A 9 4...

Страница 19: ...S H E 0 1 A A 3 0 S H E 5 1 A A 4 0 S H E 5 8 0 1 5 1 6 0 B A 3 0 S H E 9 0 B A 4 0 S H E 5 1 B A 4 0 S H E 6 9 5 1 6 0 C A 3 0 S H E 9 0 C A 4 0 S H E 5 1 C A 4 0 S H E 6 9 5 1 1 A 1 6 W 5 0 A A 5 0...

Страница 20: ...r e m m o C t s u a h x E h t i w r e z i m o n o c E V 0 3 2 r o t a l i t n e V y r e v o c e R y g r e n E V 0 6 4 r o t a l i t n e V y r e v o c e R y g r e n E X X X X X X X X X X X X X X X X X...

Страница 21: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check...

Страница 22: ...Refer to the manufacturer s authorized replacement list USING THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION Orient the control module so that the 3 wire motor plug can be inserted...

Отзывы: